[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-112-1-water-chemical-004":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":51,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-水與化學系統消防安全設備概要-004","fire-112-1-water-chemical-004",112,1,4,"依水道連結型自動撒水設備設置基準之規定，採民生水箱共用式，其配管、配件及閥類之規定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"室內水平配管應避免傾斜且裝置時儘量縮短配管與撒水頭間管距","撒水頭應配接防止水滯留之管接頭","配管末端應連結末端查驗閥，俾使配管內水源流動不滯留","配管材質應符合自來水配管之相關規定","C",null,[],false,"本題考點：《水道連結型自動撒水設備設置基準》中「民生水箱共用式」對配管、配件及閥類的規定，核心目的是防止管內用水滯留變質。\n【正解理由】依《水道連結型自動撒水設備設置基準》關於民生水箱共用式之規定，該型式係將撒水配管與日常生活用水管路併用，因此配管末端必須連接經常使用之衛生設備（如水龍頭、便器沖水裝置），使日常用水行為即可帶動管內水體流動更新；末端查驗閥是密閉式自動撒水設備用以查驗末端放水壓力與流量的裝置，平時關閉不流動，與共用式要求「水不滯留」的設計前提相反，故選C為錯誤敘述。\n【逐項排除】\n(A) 水平配管避免傾斜並縮短配管與撒水頭間之管距，可減少低點積水與支管死水段，符合防滯留的設計要求，敘述正確。\n(B) 撒水頭配接防止水滯留之管接頭，使支管末端仍有水流路徑而不形成死水，正是共用式的專屬配件要求，敘述正確。\n(D) 共用式管路同時輸送民生飲用水，配管材質自應符合自來水配管之相關規定以確保水質衛生，敘述正確。\n(C) 以末端查驗閥作為配管末端，管內水體將長期停滯而有水質劣化之虞，與共用式規定應連接經常使用衛生設備的要求不符，為本題所要挑出的錯誤選項。\n【記憶點】共用式的靈魂是「水要一直流」，末端接的是常用的水龍頭，不是末端查驗閥。","水道連結型自動撒水設備是為了解決小型長照與社福機構的火災風險而發展出的設備型式。此類場所住民行動不便、夜間人力稀少，一旦起火避難極為困難，但傳統自動撒水設備需要專用水源、加壓送水裝置與大量配管，改裝成本與空間需求都超出小型場所負荷。制度上因此開放以自來水（水道）壓力直接供水的簡易型式，把設備成本壓到可普及的程度，這是理解全部條文設計邏輯的起點：所有規定都在「借用民生水路」與「確保滅火可靠」之間取平衡。\n設置型式可分為獨立水箱式與民生水箱共用式兩大類。獨立水箱式另設撒水專用水箱，水體與民生用水分離，優點是水量掌握明確，末端查驗閥亦僅於此型式設置；共用式則直接借用日常生活用水管路，優點正是天天有人用水、管內水體自然更新，缺點是設計上必須嚴防出現死水段與斷水風險。因此共用式的配管規定幾乎都指向同一個要件：不得有滯留。避免傾斜、縮短撒水頭與配管間距、撒水頭配接防滯留管接頭、末端連接經常使用之衛生設備，四項合起來就是一套「讓水一直走」的設計語言。\n最容易混淆的是末端查驗閥。密閉濕式自動撒水設備依《各類場所消防安全設備設置標準》須於配管系統末端設末端查驗閥，用以模擬一個撒水頭動作的放水狀況，查驗壓力、流量與流水檢知裝置連動是否正常，該閥平時關閉，末端管段本來就是靜止水。把這套用在共用式上，等於在民生飲用水路上留一段長期不流動的水，衛生與滅火可靠度兩頭落空。命題者選這個選項，正是要測驗考生能否辨識兩種設備的設計前提差異，而不是死背條文字句。\n延伸考點常見於適用場所範圍、撒水頭放水量與放水壓力的簡化要求，以及與一般自動撒水設備在水源容量、加壓送水裝置有無上的對照，可與同一節條文一起整理成比較表記憶。",true,[28,32,36,40,44,47],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-water-chemical-003","室外儲槽儲存閃火點在 70℃以下第四類公共危險物品之顯著滅火困難場所，依規定設置冷卻撒水設備，其加壓送水裝置應設置手動啟動裝置及遠隔啟動裝置。但送水區域距加壓送水裝置在多少公尺以內者，得免設遠隔啟動裝置？",3,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-water-chemical-005","有關補助撒水栓與第二種室內消防栓之比較，下列敘述何者正確？",5,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-water-chemical-002","依公共危險物品等場所設置之滅火設備分類，自動撒水設備係屬下列何種滅火設備？",2,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-water-chemical-006","某百貨公司進行消防安全設備檢修作業，天花板上設有密閉式撒水頭，今有一撒水頭側邊有類似樑造型之裝修構造，經測量該密閉式撒水頭與此構造側面距離為 85 公分，則撒水頭迴水板應高出此構造底面尺寸多少公分以下方符合規定？",6,{"webId":45,"stem":46,"number":12,"year":11,"session":12},"fire-112-1-water-chemical-001","某一新建建築物設有室內消防栓設備，其加壓送水裝置全閉揚程為 60 公尺，今於上午 9 時施作消防立管管系加壓試驗，試驗壓力應大於 X kgf\u002Fcm2 以上之水壓，且須持續維持試驗壓力至 Y 時止均無漏水現象方為合格。其中 X 與 Y 分別為多少？",{"webId":48,"stem":49,"number":50,"year":11,"session":12},"fire-112-1-water-chemical-007","有關水系統滅火設備之放射（水）區域，下列敘述何者正確？",7,[52,56,60,64,68],{"webId":53,"year":54,"stem":55,"number":13},"fire-114-1-water-chemical-004",114,"依各類場所消防安全設備設置標準規定，鹵化烴滅火設備，蓄壓式儲存容器儲存 HFC-227ea、 FK-5-1-12 之儲存壓力，應以氮氣加壓至 X MPa 以上。加壓式儲存容器，應設置可調整壓力至 Y MPa 之壓力調整裝置。則 X+Y 為多少？",{"webId":57,"year":58,"stem":59,"number":13},"fire-113-1-water-chemical-004",113,"有關連結送水管設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":61,"year":62,"stem":63,"number":13},"fire-111-1-water-chemical-004",111,"裝置於舞臺之開放式自動撒水設備，依規定下列何者正確？",{"webId":65,"year":66,"stem":67,"number":13},"fire-110-1-water-chemical-004",110,"下列有關室內消防栓設備之規定，何者錯誤？",{"webId":69,"year":70,"stem":71,"number":13},"fire-109-1-water-chemical-004",109,"供集會堂使用之舞臺，應設置何種自動撒水設備？",1785129971802]