[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-112-1-water-chemical-003":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-水與化學系統消防安全設備概要-003","fire-112-1-water-chemical-003",112,1,3,"室外儲槽儲存閃火點在 70℃以下第四類公共危險物品之顯著滅火困難場所，依規定設置冷卻撒水設備，其加壓送水裝置應設置手動啟動裝置及遠隔啟動裝置。但送水區域距加壓送水裝置在多少公尺以內者，得免設遠隔啟動裝置？",{"A":16,"B":17,"C":18,"D":19},"50","100","300","500","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 216 條冷卻撒水設備得免設遠隔啟動裝置的距離門檻。\n【正解理由】第 216 條就室內、室外儲槽儲存閃火點在攝氏七十度以下第四類公共危險物品之顯著滅火困難場所，於第七款明定加壓送水裝置應設置手動啟動裝置及遠隔啟動裝置，但書則寫「送水區域距加壓送水裝置在三百公尺以內者，得免設遠隔啟動裝置」，故選 C。\n【演算步驟】判定式：設送水區域至加壓送水裝置之距離為 d。d≦300 公尺時得免設遠隔啟動裝置；d＞300 公尺時，手動啟動裝置與遠隔啟動裝置均應設置。題目所問即為該門檻值，故 d＝300 公尺。\n【逐項排除】\n(A) 50 公尺並非本款所定之距離，條文未以此為免設門檻。\n(B) 100 公尺同樣未見於本條，屬混淆用數值。\n(C) 正確：第七款但書逐字所定即三百公尺以內得免設遠隔啟動裝置。\n(D) 500 公尺是同條第八款「加壓送水裝置距撒水區域在五百公尺以下」的規定，該款併同要求啟動後五分鐘以內能有效撒水，與免設遠隔啟動裝置無關。\n【記憶點】冷卻撒水設備記兩個距離：三百公尺以內免設遠隔啟動裝置、加壓送水裝置距撒水區域五百公尺以下。","《各類場所消防安全設備設置標準》第 216 條規範室內、室外儲槽儲存閃火點在攝氏七十度以下第四類公共危險物品之顯著滅火困難場所，除固定式泡沫滅火設備外並應設冷卻撒水設備，全條可整批記為一組數值：撒水噴孔孔徑在四毫米以上；撒水管設於槽壁頂部，遇風樑或補強環等阻礙水路徑者於其下方增設撒水管及撒水噴孔；撒水量按槽壁總防護面積每平方公尺每分鐘二公升以上計算；加壓送水裝置為專用，幫浦出水量在撒水量乘以防護面積以上；水源容量在最大一座儲槽連續放水四小時之水量以上；選擇閥設於防液堤外，操作位置距地面零點八公尺以上一點五公尺以下；加壓送水裝置啟動後五分鐘以內能有效撒水，且距撒水區域在五百公尺以下，設有保壓措施者不在此限；緊急電源之供電容量在連續放水時間以上。\n本題所考的第七款採「原則設置、例外免設」的立法形式：手動啟動裝置與遠隔啟動裝置原則上均應設置，僅在送水區域距加壓送水裝置三百公尺以內時得免設遠隔啟動裝置。條文並明定遠隔啟動裝置的兩種方式，一為開啟選擇閥使啟動用水壓開關裝置或流水檢知裝置連動啟動，二為設於監控室等平常有人駐守處所直接啟動；手動啟動裝置的操作部則設於加壓送水裝置設置之場所。\n檢修與驗收面可對照記憶：《消防安全設備及必要檢修項目檢修基準》冷卻撒水設備之綜合檢查載明，公共危險物品室外儲槽場所實測放射量除以所防護儲槽側壁面積應在每分鐘每平方公尺二公升以上；可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽為五公升以上，以厚度規定以上之岩棉等隔熱材被覆者為二點五公升以上。同一組判定值亦見於《消防安全設備測試報告書測試方法及判定要領》冷卻撒水設備之綜合試驗。\n延伸考點為第 215 條泡沫射水槍滅火設備，其適用要件為閃火點在攝氏四十度以下之第四類公共危險物品且設於岸壁、碼頭並連接輸送設備者，與本條的閃火點門檻不同。",true,[28,32,36,39,43,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-water-chemical-002","依公共危險物品等場所設置之滅火設備分類，自動撒水設備係屬下列何種滅火設備？",2,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-water-chemical-004","依水道連結型自動撒水設備設置基準之規定，採民生水箱共用式，其配管、配件及閥類之規定，下列敘述何者錯誤？",4,{"webId":37,"stem":38,"number":12,"year":11,"session":12},"fire-112-1-water-chemical-001","某一新建建築物設有室內消防栓設備，其加壓送水裝置全閉揚程為 60 公尺，今於上午 9 時施作消防立管管系加壓試驗，試驗壓力應大於 X kgf\u002Fcm2 以上之水壓，且須持續維持試驗壓力至 Y 時止均無漏水現象方為合格。其中 X 與 Y 分別為多少？",{"webId":40,"stem":41,"number":42,"year":11,"session":12},"fire-112-1-water-chemical-005","有關補助撒水栓與第二種室內消防栓之比較，下列敘述何者正確？",5,{"webId":44,"stem":45,"number":46,"year":47,"session":12},"fire-111-1-water-chemical-040","二氧化碳滅火設備採全區放射方式，採用高壓系統在進行綜合檢查時，以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之 X%核算，每公斤核算空氣量或氮氣量 Y（公升），請問前述 X、Y 為何？",40,111,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-water-chemical-006","某百貨公司進行消防安全設備檢修作業，天花板上設有密閉式撒水頭，今有一撒水頭側邊有類似樑造型之裝修構造，經測量該密閉式撒水頭與此構造側面距離為 85 公分，則撒水頭迴水板應高出此構造底面尺寸多少公分以下方符合規定？",6,[53,57,60,64,68],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-003",113,"公共危險物品場所設置泡沫滅火設備，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",{"webId":58,"year":47,"stem":59,"number":13},"fire-111-1-water-chemical-003","某公共危險物品場所設置室外消防栓設備，在裝置全部消防栓數量 5 支時，其所需之水源容量至少應為多少立方公尺以上？",{"webId":61,"year":62,"stem":63,"number":13},"fire-110-1-water-chemical-003",110,"公共危險物品等場所消防設計及消防安全設備，顯著滅火困難場所之室外儲槽場所，儲存硫磺，應設置何種滅火設備？",{"webId":65,"year":66,"stem":67,"number":13},"fire-109-1-water-chemical-003",109,"某建築物之室內、外消防栓、自動撒水及水霧滅火等設備配管採連通設計並共用消防幫浦，其共用消防幫浦之出水量和全揚程之要求標準為何？",{"webId":69,"year":70,"stem":71,"number":13},"fire-108-1-water-chemical-003",108,"中央主管機關認定儲存大量可燃物之場所天花板高度超過 X 公尺，或其他場所天花板高度超過 Y 公尺者，應採用放水型撒水頭。X、Y 分別為何？",1785129971797]