[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-112-1-water-chemical-001":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":26,"sameNumber":52,"hasEssay":25},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":12,"stem":13,"options":14,"answer":19,"answerNote":20,"images":21,"imagesPending":22,"lawTimestamp":11,"explanation":23,"explanationDeep":24,"freq":12,"indexable":25},"fire-112-1-水與化學系統消防安全設備概要-001","fire-112-1-water-chemical-001",112,1,"某一新建建築物設有室內消防栓設備，其加壓送水裝置全閉揚程為 60 公尺，今於上午 9 時施作消防立管管系加壓試驗，試驗壓力應大於 X kgf\u002Fcm2 以上之水壓，且須持續維持試驗壓力至 Y 時止均無漏水現象方為合格。其中 X 與 Y 分別為多少？",{"A":15,"B":16,"C":17,"D":18},"X=6、Y=上午 10 時","X=9、Y=上午 11 時","X=12、Y=中午 12 時","X=14、Y=下午 13 時","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 33 條消防立管管系竣工加壓試驗的試驗壓力與維持時間。\n【正解理由】第 33 條明定「室內消防栓設備之消防立管管系竣工時，應做加壓試驗，試驗壓力不得小於加壓送水裝置全閉揚程一點五倍以上之水壓」，並規定「試驗壓力以繼續維持二小時無漏水現象為合格」。全閉揚程 60 公尺乘以 1.5 倍為 90 公尺水頭，換算為 9 kgf\u002Fcm2；上午 9 時起持續 2 小時至上午 11 時，故選 B。\n【演算步驟】試驗水頭 H＝全閉揚程×1.5＝60 公尺×1.5＝90 公尺；以 10 公尺水頭≒1 kgf\u002Fcm2 換算，X＝90 公尺÷10 公尺＝9 kgf\u002Fcm2。維持時間 Y＝上午 9 時＋2 小時＝上午 11 時。\n【逐項排除】\n(A) X＝6 只把 60 公尺水頭換算成壓力而漏乘 1.5 倍，Y＝上午 10 時亦只維持 1 小時。\n(B) 正確：9 kgf\u002Fcm2 與上午 11 時同時滿足 1.5 倍與 2 小時。\n(C) X＝12 相當於誤乘 2 倍，Y＝中午 12 時為維持 3 小時，均與條文不符。\n(D) X＝14 無對應的計算依據，Y 為維持 4 小時，亦非條文所定。\n【記憶點】立管加壓試驗記「全閉揚程 1.5 倍、撐足 2 小時不漏水」。","《各類場所消防安全設備設置標準》第 33 條規範消防立管管系竣工時的加壓試驗，屬施工完成後的耐壓驗證。以全閉揚程為基準，是因為離心式消防幫浦在出水量為零時所產生的揚程即為系統可能承受的最高靜壓，再乘以 1.5 倍作為安全係數，可涵蓋水錘等瞬時壓力；規定持續二小時而非數分鐘，則是要讓微小滲漏有足夠時間反映在壓力表上。\n單位換算是本題的第二個關卡：水的密度使 10 公尺水頭約等於 1 kgf\u002Fcm2，而 1 kgf\u002Fcm2 約等於 0.098 MPa，因此 90 公尺水頭約為 9 kgf\u002Fcm2、約 0.88 MPa。條文以公尺表示揚程、以每平方公分公斤表示壓力，兩種單位在同一題內交錯出現是常見的命題手法，第 37 條的重力水箱必要落差式 H＝h1＋h2＋17（公尺）與壓力水箱必要壓力式 P＝P1＋P2＋P3＋1.7（kgf\u002Fcm2）也是同一組換算關係的體現。\n同屬 1.5 倍家族但持續時間各自不同的規定可並列記憶：第 33 條室內消防栓立管，全閉揚程 1.5 倍以上、繼續維持二小時；第 181 條連結送水管配管，能承受送水設計壓力 1.5 倍以上之水壓且持續三十分鐘，設有中繼幫浦時其二次側配管應能承受幫浦全閉揚程 1.5 倍以上之水壓；《防火牆及防火水幕設置基準》第 7 點第五款防火水幕配管，試驗壓力為加壓送水裝置全閉揚程 1.5 倍以上之水壓，須持續兩小時無漏水現象。三者倍數相同，時間與基準壓力各自記住即可。\n另一個容易與試驗壓力混淆的「全閉」數值出現在《消防安全設備測試報告書測試方法及判定要領》室內消防栓設備之性能試驗：全閉揚程應在額定負荷運轉時測得揚程的 140% 以下，那是幫浦性能曲線的判定項目，與配管耐壓試驗分屬不同試驗。",true,[27,32,36,40,44,48],{"webId":28,"stem":29,"number":30,"year":31,"session":12},"fire-111-1-water-chemical-040","二氧化碳滅火設備採全區放射方式，採用高壓系統在進行綜合檢查時，以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之 X%核算，每公斤核算空氣量或氮氣量 Y（公升），請問前述 X、Y 為何？",40,111,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-water-chemical-002","依公共危險物品等場所設置之滅火設備分類，自動撒水設備係屬下列何種滅火設備？",2,{"webId":37,"stem":38,"number":39,"year":31,"session":12},"fire-111-1-water-chemical-039","可燃性高壓氣體儲存場所任一點至滅火器之步行距離在 X 公尺以下，並不得妨礙出入作業；每具滅火器對普通火災具有 Y 個以上之滅火效能值，請問前述 X、Y 為何？",39,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-water-chemical-003","室外儲槽儲存閃火點在 70℃以下第四類公共危險物品之顯著滅火困難場所，依規定設置冷卻撒水設備，其加壓送水裝置應設置手動啟動裝置及遠隔啟動裝置。但送水區域距加壓送水裝置在多少公尺以內者，得免設遠隔啟動裝置？",3,{"webId":45,"stem":46,"number":47,"year":31,"session":12},"fire-111-1-water-chemical-038","一間變壓機房採全區放射二氧化碳滅火設備，其防護區域體積 1250 立方公尺，無其它開口部，此防護區域需要多少二氧化碳藥劑量？",38,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-water-chemical-004","依水道連結型自動撒水設備設置基準之規定，採民生水箱共用式，其配管、配件及閥類之規定，下列敘述何者錯誤？",4,[53,57,60,64,68],{"webId":54,"year":55,"stem":56,"number":12},"fire-113-1-water-chemical-001",113,"有關消防安全設備水源容量之放水時間，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",{"webId":58,"year":31,"stem":59,"number":12},"fire-111-1-water-chemical-001","依各類場所消防安全設備設置標準規定，下列何種場所不需設置室外消防栓設備？",{"webId":61,"year":62,"stem":63,"number":12},"fire-110-1-water-chemical-001",110,"公共危險物品等場所消防設計及消防安全設備，電氣設備使用之處所，每多少平方公尺（含未滿）應設置第五種滅火設備一具以上？",{"webId":65,"year":66,"stem":67,"number":12},"fire-109-1-water-chemical-001",109,"下列場所何者未達依法應設置滅火器之條件？",{"webId":69,"year":70,"stem":71,"number":12},"fire-108-1-water-chemical-001",108,"在應設置室內消防栓設備之場所，但設有室外消防栓設備時，在第一層水平距離 X 公尺以下、第二層步行距離 Y 公尺以下有效滅火範圍內，室內消防栓設備限於第一層、第二層免設。X、Y 分別為何？",1785129971783]