[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-fire-law-036":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-消防法規概要-036","fire-112-1-fire-law-036",112,1,36,"依建築技術規則之定義，自室內經由陽台或排煙室始得進入之安全梯稱為下列何者？",{"A":16,"B":17,"C":18,"D":19},"安全梯","特別安全梯","直通樓梯","剪刀梯","B",null,[],false,"本題考點：《建築技術規則》對安全梯三型的構造要求，何者以「經陽臺或排煙室」為進入動線。\n【正解理由】依《建築技術規則建築設計施工編》第 97 條第三款特別安全梯之構造，明定「自室內通陽臺或進入排煙室之出入口，應裝設具有一小時以上防火時效及半小時以上阻熱性之防火門，自陽臺或排煙室進入樓梯間之出入口應裝設具有半小時以上防火時效之防火門」，其動線即室內→陽臺（或排煙室）→樓梯間；同編第 97-1 條並規定特別安全梯不得經由他座特別安全梯之排煙室或陽臺進入，故選 B。\n【逐項排除】\n(A) 安全梯：第 97 條第一款室內安全梯是由室內直接進入，「進入安全梯之出入口」須裝設具一小時以上防火時效及半小時以上阻熱性且具遮煙性能之防火門，寬度不得小於九十公分，中間並未夾陽臺或排煙室。\n(B) 特別安全梯：構造要求即以陽臺或排煙室為中介空間，敘述正確。\n(C) 直通樓梯：第 96 條把它當成應「改為室內或室外之安全梯或特別安全梯」的對象（通達三層以上五層以下者至少一座為安全梯），可見它是上位概念，本身不以陽臺或排煙室為要件。\n(D) 剪刀梯：指兩座樓梯交叉配置於同一樓梯間者，《各類場所消防安全設備設置標準》第 158 條第一款第二目即以「剪刀式樓梯視為一座」計算不同避難方向之安全梯座數，與進入方式無關。\n【記憶點】特別安全梯的辨識點只有一個：室內與樓梯間之間夾了陽臺或排煙室。","《建築技術規則建築設計施工編》第 97 條把安全梯分成三型，各自的構造要求就是考試的取分點。室內安全梯：梯間四周牆壁（外牆依前章規定）須具一小時以上防火時效，天花板及牆面裝修以耐燃一級材料為限，出入口防火門須具一小時以上防火時效、半小時以上阻熱性及遮煙性能且不得設門檻、寬度不得小於九十公分，梯間應設緊急電源之照明設備，採光用向外窗戶或開口須與同幢建築物其他窗戶或開口相距九十公分以上。戶外安全梯：梯間四周牆壁具一小時以上防火時效，安全梯與建築物任一開口間距離除防火門外不得小於二公尺（開口面積一平方公尺以內並裝具半小時以上防火時效之防火設備者除外），對外開口面積應在二平方公尺以上。特別安全梯：樓梯間及排煙室四周牆壁具一小時以上防火時效、裝修為耐燃一級材料，管道間維修孔不得開向樓梯間；樓梯間與排煙室或陽臺之間所開設之窗戶應為固定窗；建築物達十五層以上或地下三層以下者，供 A-1、B-1、B-2、B-3、D-1 或 D-2 組使用時，樓梯間與排煙室（或陽臺）之面積不得小於各該層居室樓地板面積百分之五，其他使用不得小於百分之三。第 97 條末並規定安全梯於避難層之出入口應裝設具一小時防火時效之防火門，且各棟至少一座安全梯於各樓層僅設一處出入口且不得直接連接居室。\n排煙室不是空殼子，它有自己的設備規定：《設置標準》第 28 條第五款把「依建築技術規則應設置之特別安全梯或緊急昇降機間」列為應設排煙設備之場所；第 189 條給了兩條選擇路徑——設直接面向戶外之窗戶者，有效開口面積須位於天花板高度二分之一以上範圍內且在二平方公尺以上（與緊急昇降機間兼用時為三平方公尺以上）；設排煙、進風風管者，排煙口位於天花板高度二分之一以上範圍、進風口位於二分之一以下範圍，排煙機與進風機之排煙量、進風量在每秒四立方公尺（兼用時每秒六立方公尺）以上，且須連接緊急電源供其有效動作三十分鐘以上。\n易混淆對照：排煙室依第 49 條第二款屬得免裝撒水頭之處所；緊急昇降機間則依第 29 條第三款應設緊急電源插座。名稱相近但規範的設備各不相同，作題時先看問的是「梯的構造」還是「間的設備」。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-fire-law-035","下列何者非屬高層建築物消防安全設備竣工查驗時應檢附之資料？",35,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-fire-law-037","依建築技術規則建築設計施工編之規定，有關建築技術用語之定義，下列敘述何者正確？",37,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-fire-law-034","避難器具支固器具以直接裝置在建築物主要構造部之施工方法，下列敘述何者正確？",34,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-fire-law-038","依建築技術規則建築設計施工編之規定，下列何者屬耐燃二級裝修材料？",38,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-fire-law-033","依消防幫浦加壓送水裝置等及配管摩擦損失計算基準之規定，下列敘述何者錯誤？",33,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-fire-law-039","依建築技術規則建築設計施工編及各類場所消防安全設備設置標準對無窗戶居室之定義及規定，下列敘述何者錯誤？",39,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-036",114,"消防設備人員執行消防安全設備之測試業務，製作測試報告書是由消防安全設備測試人員依滅火設備、警報設備、避難逃生設備、消防搶救上之必要設備及其他經中央主管機關認定之消防安全設備等依序製表，並確認各項消防安全設備之試驗符合規定。下列何者非屬應實施之試驗？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-036",113,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定，有關第一類公共危險物品的儲存及處理，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-fire-law-036",111,"受託辦理檢修之檢修機構應依相關規定檢修完成消防安全設備後，依照消防安全設備檢修及申報辦法規定，應附加檢修完成標示檢修機構專業樣式以何種顏色為底？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-law-036",110,"依建築技術規則建築設計施工編規定，夾層係指夾於樓地板與天花板間之樓層；同一樓層內夾層面積之和，超過多少平方公尺，視為另一樓層？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-036",109,"依避難器具支固器具及固定部之結構、強度計算及施工方法之規定，裝置避難器具固定部材料，使用直徑 1 公分錨定螺栓，設定試驗荷重 500 公斤力（kgf）時，則鎖緊扭力應為多少公斤力\u002F公分（kgf\u002Fcm）？",1785129969298]