[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-112-1-fire-law-032":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":51,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-消防法規概要-032","fire-112-1-fire-law-032",112,1,32,"依消防幫浦加壓送水裝置等及配管摩擦損失計算基準之規定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"幫浦本體必須能耐最高水壓之 1.5 倍以上，且加壓 3 分鐘後，各部位仍無洩漏現象才算合格","電動機在額定輸出連續運轉 8 小時後，不得發生異狀，且在超過額定輸出之 10%輸出力運轉 1 小時，仍不致發生障礙，引起過熱現象","防止水溫上升用之排放管應使用口徑 15 mm 以上者","加壓送水裝置所用壓力表及連成表應使用精度在 1.0 級以上品質者，或具有同等以上強度及性能者","D",null,[],false,"本題考點：《消防幫浦加壓送水裝置等及配管摩擦損失計算基準》對幫浦本體耐壓、電動機機能、防止水溫上升用排放管口徑與壓力表精度的規定，四個選項各出自一個「點」。\n【正解理由】依該基準第 22 點，「加壓送水裝置所用壓力表及連成表應使用精度在 1.5 級以上品質者，或具有同等以上強度及性能者」。本項寫成精度 1.0 級，與該點明定的 1.5 級不符，敘述錯誤，故選 D。\n【逐項排除】\n(A) 與第 6 點「幫浦本體必須能耐最高水壓之 1.5 倍以上，且加壓 3 分鐘後，各部位仍無洩漏現象才算合格」相符。\n(B) 與第 10 點第二款「電動機在額定輸出連續運轉八小時後，不得發生異狀，且在超過額定輸出之 10％輸出力運轉一小時，仍不致發生障礙，引起過熱現象」相符。\n(C) 與第 17 點第四款「防止水溫上升用之排放管應使用口徑 15mm 以上者」相符。\n(D) 壓力表及連成表的精度應在 1.5 級以上，非 1.0 級，為本題應選者。\n【記憶點】本基準的兩個 1.5：幫浦本體耐最高水壓 1.5 倍（加壓 3 分鐘不洩漏），壓力表與連成表精度 1.5 級以上。","本基準是《各類場所消防安全設備設置標準》第 234 條的配套技術規範——該條明定依本標準設置之室內消防栓、室外消防栓、自動撒水、水霧滅火、泡沫滅火、冷卻撒水、射水設備及連結送水管等設備，其消防幫浦、電動機、附屬裝置及配管摩擦損失計算，由中央消防機關另定之。因為體例是「點」而不是「條」，引用時要寫「第 N 點」。第 2 點先定義加壓送水裝置等的組成：由幫浦、電動機之加壓送水裝置及控制盤、呼水裝置、防止水溫上升用排放裝置、幫浦性能試驗裝置、啟動用水壓開關裝置、底閥等附屬裝置或附屬機器所構成。\n本題四項各出自一個點，數值都是常考處。第 6 點是耐壓：幫浦本體能耐最高水壓 1.5 倍以上、加壓 3 分鐘後各部位無洩漏，括號並說明最高揚水壓力指在全閉揚程換算為水頭壓力再加上最高之押入壓力之總和。第 10 點是電動機機能：幫浦在額定負荷狀態下應能順利啟動，電動機在額定輸出連續運轉八小時後不得發生異狀，超過額定輸出 10％輸出力運轉一小時仍不致發生障礙、引起過熱。第 17 點是防止水溫上升用排放裝置的五款，除口徑 15mm 以上外，還規定設呼水槽時排放管應從呼水管逆止閥之靠幫浦側連結、中途應設限流孔，未設呼水槽時從幫浦出水側逆止閥之一次側連接，配管中途須裝設控制閥，並給出排放水量 q＝Ls×C／（60×Δt）的算式，C 為每小時千瓦八百六十千卡、Δt 為水溫上昇限度攝氏三十度時每一公升水的吸收熱量。第 22 點則是量測器精度：壓力表及連成表精度 1.5 級以上。\n「1.5」在不同法源各有不同身分，宜並列辨識：本基準第 6 點的 1.5 是耐壓倍數、第 22 點的 1.5 是儀表精度等級；《設置標準》第 181 條規定連結送水管配管應能承受送水設計壓力 1.5 倍以上之水壓且持續三十分鐘。看到 1.5 先問它是倍數、等級還是分數。",true,[28,32,35,39,43,47],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-fire-law-031","依消防安全設備及必要檢修項目檢修基準之規定，某一場所 2.5 英吋室外消防栓之瞄子口徑 19 mm，現場測得瞄子壓力為 4（kgf\u002Fcm2），其放水量計算式 Q=0.653D2 P ，試問室外消防栓瞄子放水量 Q 為多少（l\u002Fmin）？",31,{"webId":33,"stem":14,"number":34,"year":11,"session":12},"fire-112-1-fire-law-033",33,{"webId":36,"stem":37,"number":38,"year":11,"session":12},"fire-112-1-fire-law-030","依消防安全設備及必要檢修項目檢修基準之規定，有關惰性氣體滅火設備之綜合檢查，下列敘述何者正確？",30,{"webId":40,"stem":41,"number":42,"year":11,"session":12},"fire-112-1-fire-law-034","避難器具支固器具以直接裝置在建築物主要構造部之施工方法，下列敘述何者正確？",34,{"webId":44,"stem":45,"number":46,"year":11,"session":12},"fire-112-1-fire-law-029","依消防安全設備及必要檢修項目檢修基準之規定，使用加瓦斯試驗器對瓦斯漏氣火警自動警報設備的檢知器進行加瓦斯測試，若某一回路之檢知器數量為 24 個，有關該回路應選取之檢知器檢查數量，下列敘述何者正確？",29,{"webId":48,"stem":49,"number":50,"year":11,"session":12},"fire-112-1-fire-law-035","下列何者非屬高層建築物消防安全設備竣工查驗時應檢附之資料？",35,[52,56,60,64,68],{"webId":53,"year":54,"stem":55,"number":13},"fire-114-1-fire-law-032",114,"依可燃性高壓氣體場所標示板規格及設置要點規定，下列敘述何者錯誤？",{"webId":57,"year":58,"stem":59,"number":13},"fire-113-1-fire-law-032",113,"依建築技術規則建築設計施工編規定，有關耐燃合板、耐燃纖維板、耐燃塑膠板及石膏板等耐燃材料，係指耐燃幾級之材料？",{"webId":61,"year":62,"stem":63,"number":13},"fire-111-1-fire-law-032",111,"供某住宿式長期照顧機構使用之五層樓建築物，各樓層若符合下列何者之規定，得免設避難器具？",{"webId":65,"year":66,"stem":67,"number":13},"fire-110-1-fire-law-032",110,"裝置避難器具之固定部（係指裝設避難器具之樑、柱、樓板等堅固構造或經補強之部分）直接裝置在建築物主要構造部之施工方法，若以金屬膨脹錨定螺栓之施工方法，金屬膨脹錨定螺栓間之間隔，應為埋入深度之幾倍以上？",{"webId":69,"year":70,"stem":71,"number":13},"fire-109-1-fire-law-032",109,"依各類場所消防安全設備檢修及申報作業基準，有關滅火器外觀檢查之規定，滅火器本體上端與樓地板面之距離，18 公斤以上者不得超過 a 公尺，未滿 18 公斤者不得超過 b 公尺。a、b 值各為下列何者？",1785129969276]