[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-fire-law-021":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-消防法規概要-021","fire-112-1-fire-law-021",112,1,21,"依各類場所消防安全設備設置標準，滅火設備之室內消防栓設備、室外消防栓設備、泡沫滅火設備，及防火牆及防火水幕設置基準之防火水幕設備之水源容量規定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"二支室內消防栓至少放水 20 分鐘，顯著滅火困難場所五支室內消防栓繼續放水 30 分鐘之水量","二具室外消防栓放水至少 30 分鐘","防火水幕設備之水源容量在儲槽容量未達 1 萬公秉者，不得小於防護該儲槽連續放水 120 分鐘之水量","泡沫滅火設備之最大一個泡沫放射區域，能繼續放射 30 分鐘以上","D",null,[],false,"本題考點：室內消防栓、室外消防栓、防火水幕與泡沫滅火設備水源容量之放水時間，分屬《設置標準》第二編、第四編與《防火牆及防火水幕設置基準》。\n【正解理由】依《各類場所消防安全設備設置標準》第 76 條第一款，泡沫滅火設備使用泡沫頭時，依第 72 條核算之最低放射量在最大一個泡沫放射區域，應能繼續放射二十分鐘以上；選項所述三十分鐘與該款不符，為敘述錯誤者，故選 D。\n【逐項排除】\n(A) 第 36 條規定室內消防栓水源容量應在最多樓層全部消防栓繼續放水二十分鐘之水量以上，超過二支時以二支計算；第 209 條第五款規定公共危險物品等場所之顯著滅火困難場所為繼續放水三十分鐘，超過五支以五支計算，敘述與兩條相符。\n(B) 第 41 條規定室外消防栓設備水源容量應在二具室外消防栓同時放水三十分鐘之水量以上，敘述正確。\n(C) 《防火牆及防火水幕設置基準》第 10 點第一款規定儲槽容量未達一萬公秉者，不得小於連續放水一百二十分鐘之水量，敘述正確。\n(D) 第 76 條第一款泡沫頭為最大一個泡沫放射區域繼續放射二十分鐘以上，同條第三款移動式泡沫為二具泡沫瞄子同時放水十五分鐘，均無三十分鐘，為本題應選者。\n【記憶點】一般場所泡沫頭 20 分鐘（第 76 條第一款）、移動式泡沫 15 分鐘（同條第三款）、室外消防栓 30 分鐘（第 41 條）、防火水幕未達一萬公秉 120 分鐘（基準第 10 點）。","水源容量題的解法是先確認三個變數：這是哪一編、哪一種設備、用哪一種放射方式。一般場所走第二編。第 36 條室內消防栓為最多樓層全部消防栓繼續放水二十分鐘，超過二支以二支計算，且消防用水與普通用水合併使用者應確保水源容量在有效水量範圍內。第 41 條室外消防栓為二具同時放水三十分鐘。第 57 條自動撒水設備依撒水頭型式與場所查表個數並繼續放水二十分鐘：十一樓以上建築物與地下建築物為快速反應型十二個、一般反應型十五個；十樓以下建築物之地下層與供第 12 條第一款第四目使用者同為十二個與十五個，其他為八個與十個；高架儲存倉庫儲存棉花、塑膠、木製品、紡織品等易燃物品為二十四個與三十個，儲存其他物品為十六個與二十個。第 76 條泡沫滅火設備使用泡沫頭時為最大一個泡沫放射區域繼續放射二十分鐘，使用高發泡放出口全區放射時依膨脹比查冠泡體積每立方公尺之泡沫水溶液量（第一種零點零四、第二種零點零一三、第三種零點零零八立方公尺），移動式為二具泡沫瞄子同時放水十五分鐘；同條第二項並要求加算充滿配管所需之泡沫水溶液量及總量之百分之二十。\n公共危險物品等場所走第四編，同名設備的數字整組不同：第 209 條室內消防栓為繼續放水三十分鐘、超過五支以五支計算，各瞄子放水壓力每平方公分三點五公斤以上、放水量每分鐘二百六十公升以上；第 210 條室外消防栓為三十分鐘、超過四支以四支計算，放水量每分鐘四百五十公升以上；第 211 條自動撒水設備為三十個撒水頭繼續放水三十分鐘，使用密閉乾式或預動式流水檢知裝置時撒水頭數追加十個；第 212 條水霧為最大放射區域全部水霧噴頭繼續放水三十分鐘，放射區域每平方公尺每分鐘放水量二十公升以上；第 220 條泡沫則為泡沫頭放射十分鐘、移動式四具瞄子三十分鐘、泡沫射水槍二具三十分鐘。第 209 至 212 條的緊急電源供電容量並統一為有效動作四十五分鐘以上。\n把兩編並排看最能看出命題手法：同樣一句「泡沫頭最大一個放射區域」，第 76 條第一款是二十分鐘、第 220 條第一款是十分鐘，選項若寫三十分鐘，兩編都對不上，這正是本題的破題點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-fire-law-020","依各類場所消防安全設備設置標準之規定，有關避難器具之敘述，下列何者正確？",20,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-fire-law-022","依各類場所消防安全設備設置標準應設置排煙設備之規定，下列敘述何者錯誤？",22,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-fire-law-019","依各類場所消防安全設備設置標準之規定，各類場所於增建、改建或變更用途時，下列何項消防安全設備適用增建、改建或變更用途前之標準？",19,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-fire-law-023","室外儲槽儲存閃火點在攝氏 70 度以下的第四類公共危險物品之顯著滅火困難場所，其依規定設置之冷卻撒水設備，下列敘述何者正確？",23,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-fire-law-018","依各類場所消防安全設備設置標準之規定，下列何類場所非屬應設置一一九火災通報裝置之場所？",18,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-fire-law-024","某一消防設備士受託辦理一家辦公大樓消防安全設備檢修，該大樓依規定設置之全部緩降機經消防設備士執行下降檢查，測量每具緩降機之下降距離及下降時間，經計算出之平均下降速度全部符合規定，其緩降機之下降距離及下降時間，下列敘述何者正確？",24,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-021",114,"某工廠現有建築物及儲存場所之中度危險工作場所樓地板面積合計 2,000 平方公尺，該工廠將擴廠增建一棟一樓層之低度危險工作場所，該增建場所之建築物及儲存場所樓地板面積合計在多少平方公尺以上時，應設置室外消防栓設備？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-021",113,"有關消防設備人員執行業務，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-fire-law-021",111,"依建築技術規則建築設計施工編所訂之建築技術用語，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-law-021",110,"依各類場所消防安全設備設置標準規定，有關應設置自動撒水設備之場所，其撒水頭之位置規定，下列敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-021",109,"依各類場所消防安全設備設置標準，有關使用密閉式撒水頭自動撒水設備末端查驗閥之規定，下列敘述何者正確？",1785129969202]