[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-112-1-alarm-evacuation-040":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-警報與避難系統消防安全設備概要-040","fire-112-1-alarm-evacuation-040",112,1,40,"依各類場所消防安全設備設置標準，醫院熱水室之場所適用選擇設置下列何種探測器？",{"A":16,"B":17,"C":18,"D":19},"熱煙複合式局限型","偵煙式局限型","火焰式局限型","定溫式局限型","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 117 條對偵煙式、熱煙複合式局限型及火焰式探測器之禁設處所。\n【正解理由】醫院熱水室屬水蒸氣會大量滯留之場所。第 117 條第一項明定偵煙式或熱煙複合式局限型探測器不得設於「塵埃、粉末或水蒸氣會大量滯留之場所」等九種處所；同條第二項第二款明定火焰式探測器不得設於「水蒸氣會大量滯留之處所」。四個選項中，熱煙複合式局限型、偵煙式局限型與火焰式三者均遭該條排除，僅屬感熱式的定溫式局限型未列於禁設範圍，故選 D。\n【逐項排除】\n(A) 熱煙複合式局限型受第 117 條第一項第一款排除，水蒸氣大量滯留會使其煙感知部誤動作，不得設於熱水室。\n(B) 偵煙式局限型與熱煙複合式同受第 117 條第一項第一款排除，水蒸氣微粒與煙粒子難以區辨，不得設置。\n(C) 火焰式受第 117 條第二項第二款排除，水蒸氣會大量滯留之處所不得設置。\n(D) 定溫式局限型屬感熱式，以周圍溫度達到標稱動作溫度而動作，不受水蒸氣干擾，未列於第 117 條之禁設範圍，為熱水室得選設者。\n【記憶點】熱水室就是水蒸氣大量滯留，偵煙式、熱煙複合式局限型與火焰式三者全退場，留下定溫式局限型。","第 117 條第一項把偵煙式或熱煙複合式局限型探測器的禁設處所列成九款：一、塵埃、粉末或水蒸氣會大量滯留之場所；二、會散發腐蝕性氣體之場所；三、廚房及其他平時煙會滯留之場所；四、顯著高溫之場所；五、排放廢氣會大量滯留之場所；六、煙會大量流入之場所；七、會結露之場所；八、設有用火設備其火焰外露之場所；九、其他對探測器機能會造成障礙之場所。第二項則規定火焰式探測器不得設於前項第二款至第四款或第六款至第八款所列處所、水蒸氣會大量滯留之處所，以及其他對探測器機能會造成障礙之處所。醫院熱水室同時具備水蒸氣大量滯留與可能結露的特性，兩項均落在禁設清單內。條文第三項並定有「前二項所列場所，依下表狀況，選擇適當探測器設置」的對照表，也就是禁設之後仍須依場所狀況挑一種能用的探測器，而不是免設。\n《消防安全設備及必要檢修項目檢修基準》火警自動警報設備一章的外觀檢查，其注意事項同樣要求「不能設置偵煙式探測器或熱煙複合式局限型探測器之場所，應依表 13-1 選設」「有發生誤報或延遲感知之虞處，應依表 13-2 選設」，並在表 13-1 的備考載明，設於紡織、木材加工場所等有火災急速擴大顧慮之場所之定溫式探測器，應儘可能使用特種且標稱動作溫度在 75℃ 以下者。\n易混淆概念：定溫式以達到標稱動作溫度才動作，差動式以單位時間內溫升率動作，補償式兼具兩者特性；熱水室這種本來就高溫多濕的空間，選定溫式可避免蒸氣造成的誤報。方向相反的是第 118 條，它規定樓梯或斜坡通道、走廊或通道、昇降機之昇降坑道或配管配線管道間、天花板等高度在十五公尺以上未滿二十公尺之場所、天花板等高度超過二十公尺之場所，以及地下層、無開口樓層及十一層以上之各樓層，應就偵煙式、熱煙複合式或火焰式探測器選擇設置——一條在講不得設，一條在講應選設，讀題時要先分清楚問的是哪一邊。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-alarm-evacuation-039","依消防安全設備及必要檢修項目檢修基準，檢查一一九火災通報裝置性能時，有關通報裝置本體檢查，下列敘述何者錯誤？",39,{"webId":33,"stem":34,"number":12,"year":35,"session":12},"fire-113-1-alarm-evacuation-001","為能有效排除火場中的濃煙，必須定期確保排煙設備之有效性，依據排煙設備檢修基準之要求，進行排煙設備的相關檢查時，下列敘述何者錯誤？",113,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-alarm-evacuation-038","有關通報試驗蓄積語音訊息之性能試驗，依據一一九火災通報裝置測試報告書判定要領，下列敘述何者錯誤？",38,{"webId":41,"stem":42,"number":43,"year":35,"session":12},"fire-113-1-alarm-evacuation-002","對於緊急電源插座距離樓地板的裝設高度範圍，下列何者正確？",2,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-alarm-evacuation-037","下列何者非各類場所消防安全設備設置標準規定應設置無線電通信輔助設備之場所？",37,{"webId":49,"stem":50,"number":51,"year":35,"session":12},"fire-113-1-alarm-evacuation-003","下列場所不得免設排煙設備？",3,[53,56,60,64,68],{"webId":54,"year":35,"stem":55,"number":13},"fire-113-1-alarm-evacuation-040","依據火警探測器認可基準，對於差動式探測器直線上升的動作試驗，自室溫狀態下以平均每分鐘 T℃直線升溫速度之水平氣流吹向時，應在 M 分鐘以內動作，下列敘述何者正確？",{"webId":57,"year":58,"stem":59,"number":13},"fire-111-1-alarm-evacuation-040",111,"光電式分離型探測器進行外觀試驗，以目視確認探測器光軸應平行牆壁距離 X 公分以上，且探測器之光軸高度應在天花板等高度 Y%以上之位置。而使用減光罩進行動作試驗，非蓄積型探測器之動作時間應在 Z 秒內。則 X、Y、Z 值，下列何者正確？",{"webId":61,"year":62,"stem":63,"number":13},"fire-110-1-alarm-evacuation-040",110,"避難器具之裝設規定，下列何者正確？",{"webId":65,"year":66,"stem":67,"number":13},"fire-109-1-alarm-evacuation-040",109,"有關火警自動警報設備受信總機周圍狀況外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"webId":69,"year":70,"stem":71,"number":13},"fire-108-1-alarm-evacuation-040",108,"依各類場所消防安全設備設置標準規定，緊急供電系統之配線的保護下列何者錯誤？",1785129963318]