[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-alarm-evacuation-029":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-警報與避難系統消防安全設備概要-029","fire-112-1-alarm-evacuation-029",112,1,29,"某建築物總樓地板面積在 5 萬平方公尺以上其主要避難路徑的地方，該出口標示燈及避難方向指示燈之緊急電源容量應在 60 分鐘以上，下列場所何者不是主要避難路徑？",{"A":16,"B":17,"C":18,"D":19},"通往戶外之出入口","通往直通樓梯之出入口","通往戶外之出入口的走廊或通道","通往直通樓梯的走廊或通道","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 155 條所定「主要避難路徑」之範圍，以及緊急電源容量六十分鐘之適用。\n【正解理由】第 155 條第一項但書規定，總樓地板面積在五萬平方公尺以上等場所之主要避難路徑，出口標示燈及避難方向指示燈之緊急電源容量應在六十分鐘以上；同條第二項逐款界定主要避難路徑為：一、通往戶外之出入口；二、通往直通樓梯之出入口；三、通往第一款出入口之走廊或通道；四、直通樓梯。第三款之走廊或通道只承接第一款，未及於第二款，故選 D。\n【逐項排除】\n(A) 屬主要避難路徑，即第二項第一款之通往戶外之出入口。\n(B) 屬主要避難路徑，即第二項第二款之通往直通樓梯之出入口。\n(C) 屬主要避難路徑，即第二項第三款之通往第一款出入口之走廊或通道。\n(D) 不屬主要避難路徑。第三款所連結者僅第一款，通往直通樓梯之走廊或通道未列入該項四款之中。\n【記憶點】走廊只跟著「通往戶外」那一款走，直通樓梯本身入列、其走廊不入列。","第 155 條的本文與但書要分開記：一般情形下，出口標示燈及避難方向指示燈之緊急電源使用蓄電池設備，容量能有效動作二十分鐘以上即可；但設於下列場所之主要避難路徑者，容量應在六十分鐘以上，並得採蓄電池設備及緊急發電機併設方式——總樓地板面積在五萬平方公尺以上、高層建築物其總樓地板面積在三萬平方公尺以上、地下建築物其總樓地板面積在一千平方公尺以上。三個門檻各自對應不同建築型態，避難所需時間隨規模與縱深拉長，這是把二十分鐘提高為六十分鐘的理由，也是允許併設發電機以免蓄電池體積過大的原因。\n主要避難路徑的四款其實是把「人往外走」的動線拆開：走廊或通道（第三款）、通往戶外之出入口（第一款），另一路則是直通樓梯（第四款）與通往直通樓梯之出入口（第二款）。設有排煙室者，第一、二款均以該室之出入口為準。\n與之對照的是同標準第 146-3 條的設置位置：出口標示燈設於通往戶外之出入口、通往直通樓梯之出入口、通往前二款出入口由室內往走廊或通道之出入口，以及通往第一款及第二款出入口走廊或通道上所設跨防火區劃之防火門；避難方向指示燈則裝設於走廊、樓梯及通道，並優先設於轉彎處。第 146-3 條管「哪裡要設燈」，第 155 條管「哪一段路徑的電源要撐六十分鐘」，兩條款次結構相似而範圍不同，是本題型的主要陷阱。另第 146-5 條定有出口標示燈標示面光度在二十燭光以上、避難方向指示燈在二十五燭光以上，常與電源容量同題出現。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-alarm-evacuation-028","某一地下街其地下層設有瓦斯漏氣火警自動警報設備，其某一回路之檢知器數量有 40 個，依消防安全設備及必要檢修項目檢修基準使用「加瓦斯試驗器」進行加瓦斯測試，檢知器選取檢查數量為何？",28,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-alarm-evacuation-030","避難器具的固定架或支固器具使用螺栓固定時，若螺紋標稱為 M12×1.75 時，把螺栓埋入混凝土內不含灰漿部分之深度應為 X mm 以上，轉矩值應為 Y kgf-cm。X，Y 應各為多少？",30,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-alarm-evacuation-027","依各類場所消防安全設備設置標準之規定，有關緊急電源插座之設置場所與位置規定，下列敘述何者錯誤？",27,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-alarm-evacuation-031","依消防安全設備及必要檢修項目檢修基準，執行緊急廣播設備性能檢查時，對啟動裝置狀態於檢查後判定方法，下列敘述何者錯誤？",31,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-alarm-evacuation-026","依各類場所消防安全設備設置標準規定，醫院在第 3 層樓可以使用下列何種避難器具？",26,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-alarm-evacuation-032","依消防機關受理消防安全設備檢修申報及複查注意事項複查作業中專業性複查，依消防安全設備及必要檢修項目檢修基準視轄區狀況，進行重點抽測，其必要抽測項目下列何者正確？",32,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-029",113,"有關特別安全梯與緊急昇降機間排煙室兼用時，其排煙設備採機械排煙、自然進風方式，則排煙機之排煙量應在 X m3\u002Fsec 以上；直接面向戶外之進風口開口面積應在 Y m2 以上則 X、Y 各為多少？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-alarm-evacuation-029",111,"緩降機為顧及使用之安全，裝置時應考慮之位置下列何者為佳？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-029",110,"有關瓦斯漏氣檢知器之設置，當瓦斯對空氣之比重小於 1 時，應設於距瓦斯燃燒器具水平距離 A 公尺以內；當瓦斯對空氣之比重大於 1 時，應設於距瓦斯燃燒器具水平距離 B 公尺以內，其中 A 及 B 分別為：",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-029",109,"有關瓦斯漏氣火警自動警報設備檢知器外觀檢查選取之檢查數量，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-029",108,"消防安全設備測試報告書測試方法及判定要領中規定，火警自動警報設備外觀試驗，其定溫式感知線型探測器之判定要領中，下列何者正確？",1785129963209]