[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-alarm-evacuation-027":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-警報與避難系統消防安全設備概要-027","fire-112-1-alarm-evacuation-027",112,1,27,"依各類場所消防安全設備設置標準之規定，有關緊急電源插座之設置場所與位置規定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"應設 11 層以上建築物之各樓層","應依建築技術規則應設置之緊急昇降機間","應裝設於樓梯間","每一層任何一處至插座之水平距離在 60 公尺以下","D",null,[],false,"本題考點：緊急電源插座之「應設場所」（《各類場所消防安全設備設置標準》第 29 條）與「設置位置」（同標準第 191 條）兩組規定的數值辨識。\n【正解理由】第 191 條第一款明定，緊急電源插座裝設於樓梯間或緊急昇降機間等（含各該處五公尺以內之場所）消防人員易於施行救火處，且每一層任何一處至插座之水平距離在五十公尺以下；《消防安全設備測試報告書測試方法及判定要領》緊急電源插座之外觀試驗亦載明該水平距離應在 50m 以下。D 寫成 60 公尺，已逾法定上限，故選 D。\n【逐項排除】\n(A) 正確。第 29 條第一款明定十一層以上建築物之各樓層應設緊急電源插座。\n(B) 正確。第 29 條第三款明定依建築技術規則應設置之緊急昇降機間應設之。\n(C) 正確。第 191 條第一款所定裝設處所即樓梯間或緊急昇降機間等消防人員易於施行救火處。\n(D) 錯誤。水平距離之法定值為五十公尺以下，並非六十公尺。\n【記憶點】緊急電源插座「哪裡要設」查第 29 條，「怎麼設」查第 191 條，水平距離五十公尺以下。","《設置標準》第 29 條把緊急電源插座列為消防搶救上之必要設備（見同標準第 11 條第四款），應設場所有三：十一層以上建築物之各樓層、總樓地板面積在一千平方公尺以上之地下建築物、依建築技術規則應設置之緊急昇降機間。三者的共同特徵是消防人員入室搶救時常用電源可能已被切斷，必須有可靠電源供破壞器材、照明與排煙機具使用，這也是本設備被歸入「搶救」而非「滅火」或「避難」的原因。\n第 191 條規定其細部要件，考點密集，宜整理成一組數字記憶：水平距離每一層任何一處至插座在五十公尺以下；電流供應容量為交流單相一百一十伏特（或一百二十伏特）十五安培，容量約一點五瓩以上；插座為接地型，裝設高度距樓地板一公尺以上一點五公尺以下，且一個崁裝式保護箱裝設二個；保護箱長邊二十五公分、短邊二十公分以上，鋼板厚度一點六毫米以上，箱蓋標示緊急電源插座字樣每字在二平方公分以上，並須接地；保護箱上方設紅色表示燈；應從主配電盤設專用回路，各層至少二回路以上，每一回路連接插座數在十個以下，且該專用回路不得設漏電斷路器。\n易混淆之處是「水平距離五十公尺」這個數值：同標準第 180 條第一款對連結送水管出水口也定各層任一點至出水口之水平距離在五十公尺以下，兩者條號與設備不同，須分開記。另《消防安全設備測試報告書測試方法及判定要領》緊急電源插座之外觀試驗，把上述設置規定轉寫為驗收判定（如保護箱高度 1m 以上 1.5m 以下、每一回路插座數 10 以下），命題者常在設置標準與判定要領之間交錯出題。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-alarm-evacuation-026","依各類場所消防安全設備設置標準規定，醫院在第 3 層樓可以使用下列何種避難器具？",26,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-alarm-evacuation-028","某一地下街其地下層設有瓦斯漏氣火警自動警報設備，其某一回路之檢知器數量有 40 個，依消防安全設備及必要檢修項目檢修基準使用「加瓦斯試驗器」進行加瓦斯測試，檢知器選取檢查數量為何？",28,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-alarm-evacuation-025","有關發電機設備設置場所之外觀試驗，依據緊急電源（發電機設備）測試報告書判定要領，下列敘述何者錯誤？",25,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-alarm-evacuation-029","某建築物總樓地板面積在 5 萬平方公尺以上其主要避難路徑的地方，該出口標示燈及避難方向指示燈之緊急電源容量應在 60 分鐘以上，下列場所何者不是主要避難路徑？",29,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-alarm-evacuation-024","排煙設備中以不燃材料建造的防煙壁，在某百貨公司的二樓售貨區其防煙壁自天花板下垂 X 公分以上，另臺北市的火車站前地下街（地下建築物）之地下通道，其防煙壁應自天花板下垂 Y 公分以上。X、Y 應各為多少才合規定？",24,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-alarm-evacuation-030","避難器具的固定架或支固器具使用螺栓固定時，若螺紋標稱為 M12×1.75 時，把螺栓埋入混凝土內不含灰漿部分之深度應為 X mm 以上，轉矩值應為 Y kgf-cm。X，Y 應各為多少？",30,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-027",113,"有關出口標示燈、避難方向指示燈與緊急照明燈之緊急電源規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-alarm-evacuation-027",111,"以絕緣電阻計量測 220 V 電源之火警受信總機回路絕緣電阻，下列何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-027",110,"依緊急廣播設備之揚聲器設置規定，廣播區域超過 100 平方公尺時，距揚聲器 1 公尺處所測得之音壓應為多少分貝以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-027",109,"有關緩降機支固器具之裝置，下列何者與各類場所消防安全設備設置標準之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-027",108,"依各類場所消防安全設備設置標準第 112 條，有關火警自動警報設備之火警分區劃定規定，下列何者錯誤？",1785129963184]