[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-alarm-evacuation-025":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-警報與避難系統消防安全設備概要-025","fire-112-1-alarm-evacuation-025",112,1,25,"有關發電機設備設置場所之外觀試驗，依據緊急電源（發電機設備）測試報告書判定要領，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"發電裝置．控制裝置應包括有高水溫、低油壓、超轉速保護等裝置","引擎排氣管與固定設備連接處應裝設防震軟管，並加裝消音器","油箱容量應可供滿載運轉 1 小時之油量","控制盤上應有電壓、電流、頻率表、冷卻水溫度計、潤滑油壓力計及其他必要儀器等","C",null,[],false,"本題考點：緊急電源（發電機設備）外觀試驗之判定要領，關鍵在油箱容量所對應之滿載運轉時數。\n【正解理由】依《消防安全設備測試報告書測試方法及判定要領》第二十章緊急電源（發電機設備）甲、外觀試驗，油箱一項之判定要領明定「容量應可供滿載運轉二小時之油量」，並要求使用鋼板材、標示油箱容量、附裝油面計、進油閥、回油閥。本題問敘述錯誤者，油箱容量之判定時數為二小時。故選 C。\n【逐項排除】\n(A) 同章外觀試驗「發電裝置．控制裝置」之判定要領明定，發電裝置．控制裝置應包括有高水溫、低油壓、超轉速保護等裝置，敘述正確。\n(B) 同章「引擎排氣管與固定設備連接處有無裝設防震軟管」之判定要領明定，連接處應裝設防震軟管並加裝消音器，排氣管並應施以隔熱裝置，敘述正確。\n(C) 油箱容量之判定要領為可供滿載運轉二小時之油量，本項寫 1 小時，敘述錯誤，為本題所問者。\n(D) 同章「控制盤」之判定要領明定，控制盤上應有電壓、電流、頻率表、冷卻水溫度計、潤滑油壓力計及其他必要儀器等，敘述正確。\n【記憶點】發電機設備外觀試驗，油箱要能撐滿載運轉二小時。","油箱容量之所以訂在滿載運轉二小時，是因為緊急發電機要撐的不只是單一設備的法定動作時間，而是整棟建築在停電後、消防人員搶救期間的整體供電需求，因此驗收端給的是一個涵蓋各設備動作時間的共同油量門檻。把它和各設備的緊急電源時數分開記，是這一題不失分的關鍵。\n同章外觀試驗還有幾個常考項目：結線．接續應確實且無鬆脫；電源切換裝置以後之緊急用配電盤部分應有回路標示，開關器上應有其為消防安全設備等用之標示；應採取防止因地震而產生變形、損傷等之耐震措施；配線應符合屋內線路裝置規則等相關法令之設置規定；引擎運轉部應設有安全護網裝置，四周不得有影響通風之遮蔽物；控制盤除各式儀表外，應有自動手動啟動裝置及自動停機之保護裝置。\n設置端的規定則在《各類場所消防安全設備設置標準》第 237 條：緊急電源使用符合 CNS 一○二○四規定之發電機設備、一○二○五規定之蓄電池設備或具有相同效果之設備，其容量之計算由中央消防機關另定之；緊急電源裝置切換開關，於常用電源切斷時自動切換供應電源至緊急用電器具，並於常用電源恢復時自動恢復由常用電源供應；發電機裝設適當開關或連鎖機件，以防止向正常供電線路逆向電力；裝設發電機及蓄電池之處所為防火構造，但設於屋外且有防水措施者不在此限；蓄電池設備充電電源之配線設專用回路，其開關上應有明顯之標示。\n各設備緊急電源時數也宜整理並列：第 38 條室內消防栓設備之緊急電源供電容量三十分鐘以上；第 128 條火警自動警報設備之緊急電源使用蓄電池設備，容量能有效動作十分鐘以上；第 177 條緊急照明設備之蓄電池設備持續動作三十分鐘以上；第 188 條第九款排煙設備三十分鐘以上；第 192-1 條防災監控系統綜合操作裝置二小時以上。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-alarm-evacuation-024","排煙設備中以不燃材料建造的防煙壁，在某百貨公司的二樓售貨區其防煙壁自天花板下垂 X 公分以上，另臺北市的火車站前地下街（地下建築物）之地下通道，其防煙壁應自天花板下垂 Y 公分以上。X、Y 應各為多少才合規定？",24,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-alarm-evacuation-026","依各類場所消防安全設備設置標準規定，醫院在第 3 層樓可以使用下列何種避難器具？",26,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-alarm-evacuation-023","有關特別安全梯或緊急昇降機間排煙室之排煙設備，當設置直接面向戶外之窗戶時，下列敘述何者錯誤？",23,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-alarm-evacuation-027","依各類場所消防安全設備設置標準之規定，有關緊急電源插座之設置場所與位置規定，下列敘述何者錯誤？",27,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-alarm-evacuation-022","有關感熱型探測器定溫式（非再用型）性能檢查之選取檢查數量，依據火警自動警報設備檢修基準，下列敘述何者錯誤？",22,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-alarm-evacuation-028","某一地下街其地下層設有瓦斯漏氣火警自動警報設備，其某一回路之檢知器數量有 40 個，依消防安全設備及必要檢修項目檢修基準使用「加瓦斯試驗器」進行加瓦斯測試，檢知器選取檢查數量為何？",28,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-025",113,"依各類場所消防安全設備設置標準之規定，有關緊急電源插座之設置規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-alarm-evacuation-025",111,"依 119 火災通報裝置認可基準規定，當常用電源停電，持續 X 分鐘待機狀態後，需保有 Y 分鐘以上可進行火災通報之電源容量；通話功能及回鈴應答試驗於 Z 秒內未收到回鈴信號，應可重複進行撥號。則 X、Y、Z 為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-025",110,"下列有關火警受信總機之裝置規定，何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-025",109,"有關火焰式探測器之設置，下列何者與各類場所消防安全設備設置標準之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-025",108,"依各類場所消防安全設備設置標準規定，火警自動警報設備之火警發信機（非定址式）與 P 型受信總機，其配線為何種配線？",1785129963159]