[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-alarm-evacuation-021":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-警報與避難系統消防安全設備概要-021","fire-112-1-alarm-evacuation-021",112,1,21,"依各類場所消防安全設備設置標準之規定，裝設於樓梯 L 級揚聲器，距揚聲器 1 公尺處所測得之音壓規定，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"84 分貝以上 87 分貝未滿","87 分貝以上 92 分貝未滿","90 分貝以上 92 分貝未滿","92 分貝以上","D",null,[],false,"本題考點：緊急廣播設備揚聲器之音壓分級，以及設於樓梯者所應採用之揚聲器級別。\n【正解理由】依《各類場所消防安全設備設置標準》第 133 條第一款之音壓表，距揚聲器一公尺處所測得之音壓，Ｌ級為 92 分貝以上；同條第二款第五目並明定設於樓梯或斜坡通道時，至少垂直距離每十五公尺設一個Ｌ級揚聲器，題幹裝設於樓梯者即為Ｌ級揚聲器，其音壓適用 92 分貝以上。故選 D。\n【逐項排除】\n(A) 84 分貝以上 87 分貝未滿，為同表Ｓ級揚聲器之音壓規定，非Ｌ級。\n(B) 87 分貝以上 92 分貝未滿，為同表Ｍ級揚聲器之音壓規定，非Ｌ級。\n(C) 90 分貝以上 92 分貝未滿並非該音壓表所列之任一級距；90 分貝出現在第 131 條第二款之火警警鈴音壓規定（在規定電壓下離開火警警鈴一百公分處測得），與揚聲器分級無關。\n(D) Ｌ級揚聲器音壓 92 分貝以上，與第 133 條第一款音壓表逐字相符，敘述正確。\n【記憶點】揚聲器音壓Ｓ級 84 至 87 分貝、Ｍ級 87 至 92 分貝、Ｌ級 92 分貝以上；樓梯與斜坡通道每垂直十五公尺設一個Ｌ級。","音壓分級與廣播區域面積是綁在一起的一組規定。第 133 條第二款規定：廣播區域超過一百平方公尺時設Ｌ級揚聲器；超過五十平方公尺一百平方公尺以下時設Ｌ級或Ｍ級；在五十平方公尺以下時設Ｌ級、Ｍ級或Ｓ級。也就是說級數愈高音壓愈大、可涵蓋的區域愈大，Ｌ級在任何區域都能用，Ｓ級只能用在小區域。樓梯與斜坡通道是垂直貫穿多樓層的空間，煙與聲音都會沿著它流動，因此第二款第五目直接指定至少垂直距離每十五公尺設一個Ｌ級揚聲器，本題只要抓住「樓梯即Ｌ級」就能定位到 92 分貝以上。\n配置面另有兩項常考規定。同款第四目要求從各廣播區域內任一點至揚聲器之水平距離在十公尺以下；但居室樓地板面積在六平方公尺或由居室通往地面之主要走廊及通道樓地板面積在六平方公尺以下、其他非居室部分樓地板面積在三十平方公尺以下，且該區域與相鄰接區域揚聲器之水平距離相距八公尺以下時，得免設。這是本條唯一的免設但書，抄漏但書就會把免設條件記成無條件。\n第三款則給了樓梯或斜坡通道以外場所的替代驗證途徑：廣播區域內距樓地板面一公尺處，依條文所列公式（以揚聲器音響功率、指向係數、受音點至揚聲器距離、廣播區域平均吸音率與牆壁樓地板天花板面積合計計算）求得之音壓在七十五分貝以上者，不受前款第四目十公尺之限制；廣播區域之殘響時間在三秒以上時，另依條文所列公式計算受音點至揚聲器之距離上限。\n可一併記的鄰近條文：第 22 條規定依第 19 條或第 21 條設有火警自動警報或瓦斯漏氣火警自動警報設備之建築物，應設置緊急廣播設備；第 131 條第二項並規定依該章第三節設有緊急廣播設備時，得免設火警警鈴。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-alarm-evacuation-020","依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",20,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-alarm-evacuation-022","有關感熱型探測器定溫式（非再用型）性能檢查之選取檢查數量，依據火警自動警報設備檢修基準，下列敘述何者錯誤？",22,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-alarm-evacuation-019","消防安全設備及必要檢修項目檢修基準的火警自動警報設備的探測器性能檢查中，使用火焰探測器用動作試驗器，在確認火焰探測器之動作及火警分區之表示是否正常時，火焰探測器之動作時間應在幾秒內動作？",19,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-alarm-evacuation-023","有關特別安全梯或緊急昇降機間排煙室之排煙設備，當設置直接面向戶外之窗戶時，下列敘述何者錯誤？",23,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-alarm-evacuation-018","消防安全設備及必要檢修項目檢修基準的緊急照明設備於性能檢查時，判定方法下列敘述何者正確？",18,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-alarm-evacuation-024","排煙設備中以不燃材料建造的防煙壁，在某百貨公司的二樓售貨區其防煙壁自天花板下垂 X 公分以上，另臺北市的火車站前地下街（地下建築物）之地下通道，其防煙壁應自天花板下垂 Y 公分以上。X、Y 應各為多少才合規定？",24,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-021",113,"一棟防火構造建築物，其中展覽室長 20 公尺、寬 20 公尺、高 6 公尺，天花板具有一個 50 公分的樑，將其平均分為兩個區域，試問使用補償式局限型一種探測器時，最少應設置幾顆探測器於該區域當中？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-alarm-evacuation-021",111,"依各類場所消防安全設備設置標準規定，下列有關出口標示燈及避難方向指示燈之敘述，何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-021",110,"下列有關免設火警探測器之場所，何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-021",109,"有關應設置火警自動警報設備之場所，下列何者與各類場所消防安全設備設置標準之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-021",108,"依各類場所消防安全設備設置標準規定，下列危險物品場所何者不須設置火警自動警報設備？",1785129963120]