[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-alarm-evacuation-011":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-警報與避難系統消防安全設備概要-011","fire-112-1-alarm-evacuation-011",112,1,11,"依據火警探測器認可基準之構造及材質規定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"局限型之離子式及光電式探測器與平面位置有 45 度傾斜時，差動式者有 5 度傾斜時，仍不致有功能異狀","探測器之底座視為探測器的一部位，且可與本體連結試驗 1 千次後，內部接觸彈片不得發生異狀及功能失效","離子式探測器之輻射量應低於 1 百微居里（µCi），且不得對人體有危害","不得因氣流方向改變而影響探測功能","C",null,[],false,"本題考點：《火警探測器認可基準》關於探測器構造及材質之規定，被改動的是離子式探測器輻射量的數值。\n【正解理由】依題目所據之《火警探測器認可基準》構造及材質規定，離子式探測器所使用之放射線源，其輻射量須低於該基準所定之上限，且不得對人體有危害。該基準之逐字數值應以中央主管機關公告內容為準，本文不代為引述，惟選項所載「1 百微居里（µCi）」之輻射量上限與該基準所定之數值不符，其餘三個選項則為該基準構造及材質規定所明定之事項，故選 C。\n【逐項排除】\n(A) 與該基準相符：局限型之離子式及光電式探測器與平面位置有 45 度傾斜時，差動式者有 5 度傾斜時，仍不致有功能異狀；《各類場所消防安全設備設置標準》第 115 條第五款亦定局限型探測器之裝置不得傾斜四十五度以上，但火焰式探測器不在此限。\n(B) 與該基準相符：探測器之底座視為探測器的一部位，且可與本體連結試驗 1 千次後，內部接觸彈片不得發生異狀及功能失效。\n(C) 錯誤：離子式探測器之輻射量上限並非 1 百微居里，該數值與認可基準所定之輻射量規定不符。\n(D) 與該基準相符：探測器不得因氣流方向改變而影響探測功能。\n【記憶點】離子式靠微量放射線源使空氣離子化，認可基準對輻射量定有上限並要求不得危害人體；本題四個選項只有這個數字被動過。","本題所據之《火警探測器認可基準》為中央主管機關公告之認可基準，其輻射量上限的逐字數值應以公告版本為準；以下改以《各類場所消防安全設備設置標準》與檢修基準查得的規定補足周邊考點。離子式與光電式的原理對照是必考：離子式局限型以放射線源使偵測室內空氣離子化形成微弱電流，煙粒子進入後電流變化即動作；光電式局限型則以煙粒子對光的散射或遮蔽造成受光量變化而動作。裝置面的規定在《各類場所消防安全設備設置標準》第 115 條：天花板上設有出風口時，除火焰式、差動式分布型及光電式分離型探測器外，應距離該出風口一點五公尺以上；牆上設有出風口時應距離一點五公尺以上，但該出風口距天花板在一公尺以上時不在此限；天花板設排氣口或回風口時，偵煙式探測器應裝置於排氣口或回風口周圍一公尺範圍內；局限型探測器以裝置在探測區域中心附近為原則，且不得傾斜四十五度以上。探測區域依第 119 條，指裝置面之四周以淨高四十公分以上之樑或類似構造體區劃包圍者，但差動式分布型及偵煙式探測器之裝置面四周淨高應為六十公分以上。偵煙式（光電式分離型除外）依第 122 條，探測器下端裝設在裝置面下方六十公分範圍內、距離牆壁或樑六十公分以上，有效探測範圍在裝置面高度未滿四公尺時，一種或二種為 150 平方公尺、三種為 50 平方公尺；四公尺以上未滿二十公尺時，一種或二種為 75 平方公尺。動作時間則見《消防安全設備及必要檢修項目檢修基準》火警自動警報設備之性能檢查：離子式局限型與光電式局限型，一種 30 秒、二種 60 秒、三種 90 秒；定溫式局限型特種 40 秒、一種 60 秒、二種 120 秒；差動式局限型與補償式局限型，一種及二種均為 30 秒。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-alarm-evacuation-010","依據緊急照明設備檢修基準性能檢查之判定方法，有關檢查緊急電源容量能否持續 30 分鐘之檢查數量，下列敘述何者正確？",10,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-alarm-evacuation-012","有關出口標示燈及避難方向指示燈，在沒有不易看清或識別該燈情形的條件，依據各類場所消防安全設備設置標準，下列有效範圍何者錯誤？",12,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-alarm-evacuation-009","依據緊急廣播設備用揚聲器認可基準，有關頻率特性試驗，下列敘述何者錯誤？",9,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-alarm-evacuation-013","有關避難器具設置規定，依據各類場所消防安全設備設置標準，下列何種避難器具不能裝置在使用場所之樑？",13,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-alarm-evacuation-008","有關警報裝置設置場所之外觀試驗判定要領，依據瓦斯漏氣火警自動警報設備測試報告書，下列敘述何者錯誤？",8,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-alarm-evacuation-014","依各類場所消防安全設備設置標準規定，火警自動警報設備應採分區鳴動，下列敘述何者錯誤？",14,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-011",113,"某一場所設有一 A 級出口標示燈，其縱向尺度為 0.8 公尺，且未顯示避難方向符號者，請問其步行距離應為多少公尺？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-alarm-evacuation-011",111,"依各類場所消防安全設備設置標準規定，下列場所何者未強制要求設置 119 火災通報裝置？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-011",110,"特別安全梯間與緊急昇降機間兼用之排煙室，如設置排煙管道及進風管道，下列何者在綜合試驗中應判定合格？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-011",109,"避難器具設置數量需衡酌場所之收容人數，依各類場所消防安全設備設置標準規定，百貨商場供飲食或休息用場所之收容人數計算，應以該部分樓地板面積除多少？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-011",108,"為提升火災發生時之通報效率，並避免延誤報案致生重大火災事故，各類場所消防安全設備設置標準於 107 年 10 月 17 日增列下列那一種設備種類？",1785129963016]