[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-alarm-evacuation-007":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-警報與避難系統消防安全設備概要-007","fire-112-1-alarm-evacuation-007",112,1,7,"有關揚聲器設置場所之外觀試驗判定要領，依據緊急廣播設備測試報告書，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"應設置在無障礙物妨礙音響效果之場所","揚聲器設置在樓梯或斜坡通道以外之場所時，應設置在各廣播區域，且從該廣播區域任一點至揚聲器之水平距離在 10 公尺以內範圍","揚聲器設置在樓梯或斜坡通道時，至少每 15 公尺之垂直距離，應設 1 個以上 L 級者","揚聲器設置在樓梯或斜坡通道以外之場所時，如設於 50 平方公尺以上 100 平方公尺以下之廣播區域者，應為 S 級","D",null,[],false,"本題考點：緊急廣播設備揚聲器設置場所之外觀試驗判定要領，核心是廣播區域面積與揚聲器級別的對應。\n【正解理由】依《消防安全設備測試報告書測試方法及判定要領》緊急廣播設備之外觀試驗，揚聲器設置在樓梯或斜坡通道以外之場所時，設於超過 100 平方公尺之廣播區域者應為 Ｌ 級；設於 50 平方公尺以上 100 平方公尺以下之廣播區域者，應為 Ｌ 級或 Ｍ 級；設於 50 平方公尺以下之廣播區域者，應為 Ｌ 級、Ｍ 級或 Ｓ 級。《設置標準》第 133 條第二款分級相同，惟其用語為「超過五十平方公尺」。選項所述 50 平方公尺以上 100 平方公尺以下之廣播區域「應為 Ｓ 級」，與判定要領所列級別不符，故選 D。\n【逐項排除】\n(A) 正確：判定要領明定揚聲器應設置在無障礙物妨礙音響效果之場所。\n(B) 正確：設置在樓梯或斜坡通道以外之場所時，應設置在各廣播區域，且從該廣播區域任一點至揚聲器之水平距離在 10 公尺以內。\n(C) 正確：設置在樓梯或斜坡通道時，至少每 15 公尺之垂直距離，應設 1 個以上 Ｌ 級者。\n(D) 錯誤：50 平方公尺以上 100 平方公尺以下之廣播區域應為 Ｌ 級或 Ｍ 級；Ｓ 級只用於 50 平方公尺以下之區域。\n【記憶點】面積切三段：超過 100 平方公尺只准 Ｌ 級，50 至 100 平方公尺為 Ｌ 或 Ｍ 級，50 平方公尺以下 Ｌ、Ｍ、Ｓ 級皆可。","Ｌ、Ｍ、Ｓ 三級的分野在音壓。《各類場所消防安全設備設置標準》第 133 條第一款表定：距揚聲器一公尺處所測得之音壓，Ｌ 級 92 分貝以上、Ｍ 級 87 分貝以上 92 分貝未滿、Ｓ 級 84 分貝以上 87 分貝未滿。級別與廣播區域面積的對應規則，即建立在這組音壓級距之上。同條第二款第四目定水平距離十公尺以下之原則，並附但書：居室樓地板面積在六平方公尺或由居室通往地面之主要走廊及通道樓地板面積在六平方公尺以下，其他非居室部分樓地板面積在三十平方公尺以下，且該區域與相鄰接區域揚聲器之水平距離相距八公尺以下時，得免設。同條第三款另給一條路：樓梯或斜坡通道以外之場所，廣播區域內距樓地板面一公尺處依 Ｐ＝ｐ＋10log10（Ｑ／4πr²＋4（1－α）／Ｓα）求得之音壓在七十五分貝以上者，或廣播區域殘響時間在三秒以上時距離在該款所列公式求得值以下者，不受前款第四目水平距離之限制，這也是計算題的出處。廣播分區看第 134 條：每一廣播分區不得超過一樓層；室內安全梯或特別安全梯應垂直距離每四十五公尺單獨設定一廣播分區，其地下層部分另設定一廣播分區。啟動裝置依第 136 條：各樓層任一點至啟動裝置之步行距離在五十公尺以下，設在距樓地板高度零點八公尺以上一點五公尺以下範圍內，第十一層以上之各樓層、地下第三層以下之各樓層或地下建築物應使用緊急電話方式啟動。同一組數值在設置（設置標準）、竣工查驗（測試報告書測試方法及判定要領）與定期檢修（《消防安全設備及必要檢修項目檢修基準》緊急廣播設備之綜合檢查，距揚聲器一公尺處以噪音計 Ａ 特性量測音壓）三個階段反覆出現，是本科高頻考點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-alarm-evacuation-006","有關室內排煙綜合試驗之排煙風量測試，依據排煙設備測試報告書判定要領，下列敘述何者錯誤？",6,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-alarm-evacuation-008","有關警報裝置設置場所之外觀試驗判定要領，依據瓦斯漏氣火警自動警報設備測試報告書，下列敘述何者錯誤？",8,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-alarm-evacuation-005","有關瓦斯漏氣檢知器一回路設置數量，依據瓦斯漏氣火警自動警報設備檢修基準之性能檢查，有關撰取檢查數量，下列敘述何者正確？",5,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-alarm-evacuation-009","依據緊急廣播設備用揚聲器認可基準，有關頻率特性試驗，下列敘述何者錯誤？",9,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-alarm-evacuation-004","依據一一九火災通報裝置檢修基準之性能檢查，下列何者非預備電源檢查方法之項目？",4,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-alarm-evacuation-010","依據緊急照明設備檢修基準性能檢查之判定方法，有關檢查緊急電源容量能否持續 30 分鐘之檢查數量，下列敘述何者正確？",10,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-007",113,"醫療機構中的 3 樓，經容納病床數量、從業員工與相關區域之樓地板面積等相關條件評估後，其收容人數為 550 人，該樓層在無減設、免設考量下，至少應設多少具避難器具？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-alarm-evacuation-007",111,"依消防安全設備及必要檢修項目檢修基準，差動式分布型空氣管式之火災動作或動作持續試驗，不動作或測定之時間超過範圍時，應即確認空氣管與旋塞台之連接部位是否栓緊，且應進行何種試驗？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-007",110,"下列何種火警探測器在認可作業中須進行粉塵試驗？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-007",109,"除火焰式探測器外，一般局限型探測器裝設時，依各類場所消防安全設備設置標準之規定，不得傾斜幾度以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-007",108,"有關無線電通信輔助設備設置規定，下列何者正確？",1785129962971]