[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-112-1-alarm-evacuation-001":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":26,"sameNumber":52,"hasEssay":25},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":12,"stem":13,"options":14,"answer":19,"answerNote":20,"images":21,"imagesPending":22,"lawTimestamp":11,"explanation":23,"explanationDeep":24,"freq":12,"indexable":25},"fire-112-1-警報與避難系統消防安全設備概要-001","fire-112-1-alarm-evacuation-001",112,1,"依據配線檢修基準性能檢查之檢查方法，有關高壓回路電源回路間及電源回路與大地間之絕緣電阻值測定，下列敘述何者錯誤？",{"A":15,"B":16,"C":17,"D":18},"使用 5 百伏特之絕緣電阻計測量","使用 1 千伏特之絕緣電阻計測量","使用 2 千伏特之絕緣電阻計測量","使用 5 千伏特之絕緣電阻計測量","A",null,[],false,"本題考點：配線性能檢查中，高壓回路絕緣電阻值測定所使用之絕緣電阻計電壓。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第二十七章配線二、性能檢查之檢查方法，高壓回路電源回路間及電源回路與大地間之絕緣電阻值測定，使用 1,000 伏特、2,000 伏特或 5,000 伏特之絕緣電阻計測量；500 伏特不在該三種之列，故選 A。\n【逐項排除】\n(A) 錯誤。同一節另定低壓回路開關器或斷路器之每一分岐回路，其配線間及配線與大地間之絕緣電阻值測定使用 500 伏特以下之絕緣電阻計，該電壓屬低壓回路之用，不是高壓回路所列電壓。\n(B) 正確。1,000 伏特為高壓回路測定所列三種電壓之一。\n(C) 正確。2,000 伏特為高壓回路測定所列三種電壓之一。\n(D) 正確。5,000 伏特為高壓回路測定所列三種電壓之一。\n【記憶點】高壓回路記「一千、二千、五千」三選一，五百伏特以下留給低壓分岐回路。","測完電壓還要對判定值，第二十七章的表 27-3 是配線絕緣阻抗試驗合格判定表，逐列為：300V 以下者，對地電壓應為 150V 以下時為 0.1MΩ、其他情形為 0.2MΩ；超過 300V 者為 0.4MΩ；3,000V 高壓電路為 3MΩ；6,000V 高壓電路為 6MΩ。測定值應符合表列數值以上。檢查前須先切斷電壓電路之電源，以電壓計或電流計確認已無充電情形，且使用因絕緣阻抗試驗會有妨礙之虞的電子零件回路，以及配線相互間難以測定之回路，得省略之。\n不同設備的設置條文各自規定測定用電壓，這是本科最容易張冠李戴的一組數字，要連條號一起記：火警自動警報設備依第一百二十七條第四款，電源回路及探測器回路均以直流二百五十伏特額定之絕緣電阻計測定，對地電壓一百五十伏特以下者在 0.1MΩ 以上、超過一百五十伏特者在 0.2MΩ 以上，探測器回路每一火警分區在 0.1MΩ 以上；緊急廣播設備依第一百三十九條第一款同為直流二百五十伏特額定；瓦斯漏氣火警自動警報設備依第一百四十四條第一款則是直流五百伏特額定。另第一百三十一條第三款規定火警警鈴之電鈴絕緣電阻以直流二百五十伏特額定之絕緣電阻計測定，在二十 MΩ 以上。\n驗收面則見《消防安全設備測試報告書測試方法及判定要領》第二十二章配線乙、性能試驗：低壓回路做絕緣阻抗試驗，判定值同樣是 300V 以下 0.1MΩ 或 0.2MΩ、超過 300V 者 0.4MΩ；高壓回路做的是絕緣耐力試驗，依用戶用電設備裝置規則等法令規定之試驗電壓連續十分鐘施加於電路和大地之間，判定為高壓回路應可連續承受 10 分鐘。至於配線本身的耐燃、耐熱保護區分，則依第二百三十五條與第二百三十六條辦理。",true,[27,32,36,40,44,48],{"webId":28,"stem":29,"number":30,"year":31,"session":12},"fire-111-1-alarm-evacuation-040","光電式分離型探測器進行外觀試驗，以目視確認探測器光軸應平行牆壁距離 X 公分以上，且探測器之光軸高度應在天花板等高度 Y%以上之位置。而使用減光罩進行動作試驗，非蓄積型探測器之動作時間應在 Z 秒內。則 X、Y、Z 值，下列何者正確？",40,111,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-alarm-evacuation-002","依據緊急電源插座檢修基準，有關性能檢查之判定方法，下列敘述何者錯誤？",2,{"webId":37,"stem":38,"number":39,"year":31,"session":12},"fire-111-1-alarm-evacuation-039","民國 84 年取得使用執照之大樓，測試其火警地區音響裝置之音壓何者正確？",39,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-alarm-evacuation-003","依據標示設備檢修基準，下列何者非性能檢查之檢查項目？",3,{"webId":45,"stem":46,"number":47,"year":31,"session":12},"fire-111-1-alarm-evacuation-038","依消防安全設備及必要檢修項目檢修基準，針對緩降機之下降空間進行外觀檢查時，確認有無妨礙下降之物品，及有無確保下降必要之空間，下列何者錯誤？",38,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-alarm-evacuation-004","依據一一九火災通報裝置檢修基準之性能檢查，下列何者非預備電源檢查方法之項目？",4,[53,57,60,64,68],{"webId":54,"year":55,"stem":56,"number":12},"fire-113-1-alarm-evacuation-001",113,"為能有效排除火場中的濃煙，必須定期確保排煙設備之有效性，依據排煙設備檢修基準之要求，進行排煙設備的相關檢查時，下列敘述何者錯誤？",{"webId":58,"year":31,"stem":59,"number":12},"fire-111-1-alarm-evacuation-001","依各類場所消防安全設備設置標準規定，公共危險物品室內儲存場所總樓地板面積在多少平方公尺以上者，應設置火警自動警報設備？",{"webId":61,"year":62,"stem":63,"number":12},"fire-110-1-alarm-evacuation-001",110,"下列有關建築物火警分區之劃定，何者符合各類場所消防安全設備設置標準的規定？",{"webId":65,"year":66,"stem":67,"number":12},"fire-109-1-alarm-evacuation-001",109,"常開式之火警探測器信號回路，加設終端電阻之目的為何？",{"webId":69,"year":70,"stem":71,"number":12},"fire-108-1-alarm-evacuation-001",108,"某一新建建築物地面六層、地下二層，用途為辦公室，每層樓地板面積為 400 平方公尺，設置火警自動警報系統，假設 1 樓發生火警時，依各類場所消防安全設備設置標準規定，其鳴動方式為何？",1785129962917]