[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-111-1-water-chemical-038":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-038","fire-111-1-water-chemical-038",111,1,38,"一間變壓機房採全區放射二氧化碳滅火設備，其防護區域體積 1250 立方公尺，無其它開口部，此防護區域需要多少二氧化碳藥劑量？",{"A":16,"B":17,"C":18,"D":19},"800 kg","900 kg","1000 kg","1050 kg","C",null,[],false,"本題考點：全區放射方式二氧化碳滅火設備之滅火藥劑量計算，依防護區域體積級距套用單位體積藥劑量。\n【正解理由】依《各類場所消防安全設備設置標準》關於全區放射方式二氧化碳滅火設備之規定，一般防護區域按體積級距適用每立方公尺藥劑量，依序為 1.00、0.90、0.80、0.75 公斤，切點為 50、150、1,500 立方公尺。本題體積 1,250 立方公尺落在 150 以上未達 1,500 之級距，適用 0.80 公斤／立方公尺，且無開口部無須追加，計得 1,000 公斤，故選 C。\n【逐項排除】\n(A) 800 kg 相當於 0.64 公斤／立方公尺，級距表並無此係數，數值偏低。\n(B) 900 kg 係誤用 0.72 係數或誤判體積級距所致，與級距表不符。\n(C) 1,000 kg 由 1,250 × 0.80 求得，級距正確且無開口部追加量，為正解。\n(D) 1,050 kg 相當於 0.84 公斤／立方公尺，係額外加計並不存在的開口部補償量。\n【演算步驟】公式：W＝V × g ＋ 開口部面積追加量。代入 V＝1,250 m³ → g＝0.80 kg\u002Fm³；開口部 0 m² → W＝1,250 m³ × 0.80 kg\u002Fm³ ＝ 1,000 kg。\n【記憶點】二氧化碳全區藥劑量背「1.00／0.90／0.80／0.75」，體積一千多用 0.8，乘完再看開口部。","二氧化碳滅火設備的藥劑量設計，原理是以窒息作用為主、冷卻作用為輔，必須在防護區域內建立並維持足以使燃燒中止的氧濃度稀釋比例。一般可燃物約需將氧濃度由 21% 降至 15% 以下，換算所需的二氧化碳體積濃度約三成上下；由於二氧化碳在標準狀態下的密度約 1.98 公斤／立方公尺，換算後每立方公尺防護空間所需質量便落在 0.75 至 1.0 公斤這個量級，這就是級距表數值的由來。體積愈大者單位藥劑量愈低，是因為大空間的邊界散失比例相對較小，且大型鋼瓶組的放射效率較高，故容許適度遞減。\n\n級距表可整理成記憶序列：未達 50 立方公尺用 1.00、50 以上未達 150 用 0.90、150 以上未達 1,500 用 0.80、1,500 以上用 0.75，四個數字呈遞減且間隔規律，只要記住「五十、一百五、一千五」三個切點即可。另須注意各級距尚訂有最低藥劑量下限，體積偏小時若乘積低於下限，應改採下限值，這是計算題常設的第二層陷阱。開口部部分，未設自動關閉裝置之開口，須按其面積追加藥劑量；本題明示無其他開口部，故追加項為零，若題目改為「有 2 平方公尺開口且無自動關閉裝置」，就必須加計追加量再作答。\n\n特殊場所另有專屬的單位藥劑量，例如電信機械室、總機室等以電子設備為主的空間，因設備間隙多、需較高濃度且要求不留殘渣，所適用之係數與一般場所不同；油類、可燃性液體等 B 類火災則另依設計濃度換算。作答時第一步永遠是確認題目屬於一般防護區域或特殊場所，本題所稱變壓機房若題幹未指明適用特殊係數，即依一般級距處理。\n\n易混淆概念對照：全區放射須以整個防護區域為對象並要求區劃完整，局部放射則針對特定設備或油面計算，公式與係數完全不同；移動式則以每一具瞄子之藥劑量計。另二氧化碳、乾粉、海龍替代藥劑的單位藥劑量與設計濃度各自獨立，數字不可互借。\n\n相關考點連結：同一主題常延伸考放射時間、選擇閥與音響警報裝置、防護區域之自動關閉裝置及緊急停止按鈕等安全措施規定。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-037","依規定 112 年度滅火器檢查合格時，應採用那種顏色檢修環？",37,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-039","可燃性高壓氣體儲存場所任一點至滅火器之步行距離在 X 公尺以下，並不得妨礙出入作業；每具滅火器對普通火災具有 Y 個以上之滅火效能值，請問前述 X、Y 為何？",39,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-036","二氧化碳滅火設備，採用低壓式滅火藥劑儲存容器時，壓力在何範圍會發出警報？",36,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-040","二氧化碳滅火設備採全區放射方式，採用高壓系統在進行綜合檢查時，以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之 X%核算，每公斤核算空氣量或氮氣量 Y（公升），請問前述 X、Y 為何？",40,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-035","二氧化碳滅火設備採全區放射，其噴頭設置規定下列何者錯誤？",35,{"webId":49,"stem":50,"number":12,"year":51,"session":12},"fire-112-1-water-chemical-001","某一新建建築物設有室內消防栓設備，其加壓送水裝置全閉揚程為 60 公尺，今於上午 9 時施作消防立管管系加壓試驗，試驗壓力應大於 X kgf\u002Fcm2 以上之水壓，且須持續維持試驗壓力至 Y 時止均無漏水現象方為合格。其中 X 與 Y 分別為多少？",112,[53,57,60,64,68],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-038",113,"依各類場所消防安全設備設置標準之規定，下列何場所得免設滅火器？",{"webId":58,"year":51,"stem":59,"number":13},"fire-112-1-water-chemical-038","依各類場所消防安全設備設置標準規定，消防專用蓄水池之設置，下列敘述何者錯誤？",{"webId":61,"year":62,"stem":63,"number":13},"fire-110-1-water-chemical-038",110,"依消防安全設備及必要檢修項目檢修基準，海龍滅火設備全區放射方式檢查方法，若以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之多少%核算？",{"webId":65,"year":66,"stem":67,"number":13},"fire-109-1-water-chemical-038",109,"消防專用蓄水池之設置規定，下列何者正確？",{"webId":69,"year":70,"stem":71,"number":13},"fire-108-1-water-chemical-038",108,"依各類場所消防安全設備檢修及申報作業基準，有關乾粉滅火藥劑判定方法，乾粉藥劑不得有雜質、變質、固化等情形，且以手輕握搓揉，並自地面上高度多少公分處使其落下，應呈粉狀？",1785129972288]