[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-037":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-037","fire-111-1-water-chemical-037",111,1,37,"依規定 112 年度滅火器檢查合格時，應採用那種顏色檢修環？",{"A":16,"B":17,"C":18,"D":19},"橙","黃","藍","綠","B",null,[],false,"本題考點：《消防安全設備及必要檢修項目檢修基準》第一章滅火器之一般注意事項，滅火器性能檢查後檢修環顏色與年度之對應。\n【正解理由】該章一般注意事項明定，性能檢查完成後之滅火器應於瓶頸加裝檢修環，檢修環上應標註年份，並「以顏色紅、橙、黃、綠、藍交替更換，自一百一十年度起開始使用紅色檢修環，後續依年度別依序採用橙色（一百一十一年度）、黃色（一百一十二年度）、綠色（一百一十三年度）、藍色（一百一十四年度）之檢修環，依此類推」。一百一十二年度對應黃色，故選 B。\n【逐項排除】\n(A) 橙色依前開規定對應一百一十一年度，與題目所問之一百一十二年度不符。\n(B) 黃色即該基準所定一百一十二年度使用之檢修環顏色，與題目年度相符，為本題答案。\n(C) 藍色對應一百一十四年度，為紅橙黃綠藍五色循環之末色。\n(D) 綠色對應一百一十三年度，較題目所問年度晚一年。\n【記憶點】紅橙黃綠藍五色循環，一百一十年度為紅，年度每加一即往後移一色，一百一十五年度再回紅色。","檢修環制度的用意，在於讓人從外觀即可辨識滅火器上一次性能檢查的年度。《消防安全設備及必要檢修項目檢修基準》第一章滅火器之一般注意事項就此定有完整規格：性能檢查完成後之滅火器應依表 1-1 格式張貼標示，且該標示不得覆蓋、換貼或變更原新品出廠時之標示；檢修環加裝於滅火器瓶頸，環上應標註年份，材質以一體成型之硬質無縫塑膠、壓克力或鐵環製作，尺寸以非經拆卸滅火器無法取出，或直接以內徑不得大於滅火器瓶口 1mm 之方式辦理。顏色則以紅、橙、黃、綠、藍交替更換，自一百一十年度起使用紅色，依序為橙色（一百一十一年度）、黃色（一百一十二年度）、綠色（一百一十三年度）、藍色（一百一十四年度），之後循環類推。推算訣竅是先把一百一十年記成紅，再以五色為一輪往後推算。\n配套的標示內容同樣是命題來源：表 1-1 應載明滅火器設置場所名稱、場所地址、廠商名稱、廠商證書號碼、消防專技人員姓名與證書字號、品名（乾粉、水、二氧化碳、機械泡沫、強化液、鹵化物滅火器）、規格（5 型、10 型、20 型或其他）、製造日期、流水編號、性能檢查日期、檢查情形（檢查合格無需更換藥劑、更換藥劑後合格、水壓測試合格——限十年以上或無法辨識日期之滅火器）及下次性能檢查日期。\n外觀檢查就標示部分之判定方法為：應無超過有效使用期限、應依規定張貼標示銘牌；其注意事項並載明已超過有效使用期限或未附銘牌者，得不須再施以性能檢查即可予更換新品，滅火器並應於其設置場所之明顯處所標明「滅火器」字樣。另一組常考數值出自同章性能檢查：對二氧化碳滅火器及海龍滅火器進行重量檢查時，如失重超過 10％以上或壓力表示值在綠色範圍外時，應予以更新；一般注意事項亦定，滅火器自原設置位置移開時應暫時以其他滅火器替代之，確保防護不中斷。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-036","二氧化碳滅火設備，採用低壓式滅火藥劑儲存容器時，壓力在何範圍會發出警報？",36,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-038","一間變壓機房採全區放射二氧化碳滅火設備，其防護區域體積 1250 立方公尺，無其它開口部，此防護區域需要多少二氧化碳藥劑量？",38,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-035","二氧化碳滅火設備採全區放射，其噴頭設置規定下列何者錯誤？",35,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-039","可燃性高壓氣體儲存場所任一點至滅火器之步行距離在 X 公尺以下，並不得妨礙出入作業；每具滅火器對普通火災具有 Y 個以上之滅火效能值，請問前述 X、Y 為何？",39,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-034","第五種滅火設備除滅火器外之其他設備，有關滅火效能值核算之規定，下列何者錯誤？",34,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-040","二氧化碳滅火設備採全區放射方式，採用高壓系統在進行綜合檢查時，以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之 X%核算，每公斤核算空氣量或氮氣量 Y（公升），請問前述 X、Y 為何？",40,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-037",113,"加壓式乾粉滅火設備應設壓力調整裝置，可調整壓力至多少 Mpa 以下？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-037",112,"固定式泡沫滅火設備（低發泡）進行綜合檢查作業時，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-037",110,"依消防安全設備及必要檢修項目檢修基準，水道連結型自動撒水設備之末端查驗閥或連結之水龍頭等日常生活用水設施配置的壓力表，其放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。X、Y 分別為何？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-037",109,"連結送水管之配管設置規定，應能承受送水設計壓力 1.5 倍以上之水壓，且能持續多少時間才合格？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-037",108,"進行滅火器之檢查時，有關一般注意事項，下列何者錯誤？",1785129972284]