[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-035":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-035","fire-111-1-water-chemical-035",111,1,35,"二氧化碳滅火設備採全區放射，其噴頭設置規定下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"滅火藥劑儲存於溫度攝氏零下 18 度以下者之低壓式為每平方公分 9 公斤以上","滅火藥劑以常溫儲存者之高壓式為每平方公分 14 公斤以上","電信機械室採二氧化碳滅火設備全區放射，放射時間應於 3 分鐘內全部放射完畢","鍋爐房採二氧化碳滅火設備全區放射，放射時間應於 1 分鐘內全部放射完畢","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 84 條，二氧化碳滅火設備噴頭之放射壓力與全區放射方式之放射時間。\n【正解理由】第 84 條第三款規定，全區放射方式依前條核算之滅火藥劑量，應依該款表列時間內全部放射完畢，表所列設置場所為「電信機械室、總機室」者時間為 3.5 分，「其他」為 1 分。電信機械室應於 3.5 分鐘內放射完畢，選項寫 3 分鐘與條文不符，題目問何者錯誤，故選 C。\n【逐項排除】\n(A) 第 84 條第二款後段「其滅火藥劑儲存於溫度攝氏零下十八度以下者之低壓式為每平方公分九公斤以上或 0.9MPa 以上」，敘述與條文相符。\n(B) 同款前段「二氧化碳噴頭之放射壓力，其滅火藥劑以常溫儲存者之高壓式為每平方公分十四公斤以上或1.4MPa以上」，敘述正確。\n(C) 電信機械室依表列放射時間為 3.5 分，選項寫 3 分鐘，數值與條文不符，敘述錯誤，為本題應選者。\n(D) 鍋爐房非電信機械室、總機室，依表列歸入「其他」欄，放射時間 1 分，敘述正確。\n【記憶點】二氧化碳全區放射：電信機械室、總機室 3.5 分，其他 1 分；放射壓力高壓 14、低壓 9（每平方公分公斤）。","第 84 條的兩組數值分別對應「壓力」與「時間」。壓力依儲存方式而定：常溫儲存之高壓式為每平方公分十四公斤以上或1.4MPa以上；儲存於攝氏零下十八度以下者之低壓式為每平方公分九公斤以上或0.9MPa以上。兩者差異來自儲存溫度與容器內壓不同，並與第 87 條第六款「低壓式儲存容器應設置使容器內部溫度維持於攝氏零下二十度以上，攝氏零下十八度以下之自動冷凍機」互相呼應。時間部分，全區放射方式依第三款表列，電信機械室、總機室為 3.5 分、其他場所為 1 分；局部放射方式則依第五款，所核算之滅火藥劑量應於三十秒內全部放射完畢。\n電信機械室之所以在表中單獨列格，與第 83 條的藥劑量表是配套設計：該表就電信機械室、總機室訂每立方公尺防護區域所需滅火藥劑量 1.2 公斤、每平方公尺開口部所需追加滅火藥劑量 10 公斤，均為表中最高值；其他場所則依防護區域體積分為五十立方公尺未滿 1.0、五十立方公尺以上一百五十立方公尺未滿 0.9、一百五十立方公尺以上一千五百立方公尺未滿 0.8、一千五百立方公尺以上 0.75 公斤，開口部追加量一律 5 公斤，並分別訂有 50、135、1200 公斤之滅火藥劑基本需要量。藥劑量與放射時間是同一組防護思維的兩面，一起記較不易錯置。\n易混淆概念可並列第 100 條乾粉滅火設備之噴頭規定：乾粉噴頭之放射壓力在每平方公分一公斤以上或0.1MPa以上，且核算之滅火藥劑量須於三十秒內全部放射完畢，與二氧化碳的壓力與時間規定各自獨立。放射方式的分類則見第 82 條：全區放射方式須以不燃材料建造之牆、柱、樓地板或天花板等區劃間隔，且開口部設有自動關閉裝置，但能有效補充開口部洩漏量者得免設；局部放射方式視防護對象之形狀、構造、數量及性質配置噴頭；移動放射方式之皮管接頭至防護對象任一部分之水平距離在十五公尺以下。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-034","第五種滅火設備除滅火器外之其他設備，有關滅火效能值核算之規定，下列何者錯誤？",34,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-036","二氧化碳滅火設備，採用低壓式滅火藥劑儲存容器時，壓力在何範圍會發出警報？",36,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-033","二氧化碳滅火設備配管，下列設置規定何者錯誤？",33,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-037","依規定 112 年度滅火器檢查合格時，應採用那種顏色檢修環？",37,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-032","二氧化碳滅火設備屬於公共危險物品等場所的那一類滅火設備？",32,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-038","一間變壓機房採全區放射二氧化碳滅火設備，其防護區域體積 1250 立方公尺，無其它開口部，此防護區域需要多少二氧化碳藥劑量？",38,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-035",113,"惰性氣體進行高壓式全區放射綜合檢查，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-035",112,"二氧化碳滅火設備之滅火藥劑儲存容器，其設置規定下列何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-035",110,"依消防安全設備及必要檢修項目檢修基準，製造日期超過 10 年或無法辨識製造日期之何種滅火器，非經水壓測試合格，不得再行更換及充填藥劑，應予報廢？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-035",109,"廚房等大量使用火源之處所，多少樓地板面積需有一滅火效能值？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-035",108,"依各類場所消防安全設備檢修及申報作業基準，有關室內消防栓設備呼水裝置之減水警報裝置，當水量減少至多少前應發出警報？",1785129972271]