[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-030":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-030","fire-111-1-water-chemical-030",111,1,30,"有關消防安全設備檢修完成標示附加位置，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"室內消防栓設備：加壓送水裝置控制盤盤面及消防栓箱箱面","自動撒水設備：加壓送水裝置控制盤盤面及制水閥本體","簡易自動滅火設備：手動啟動裝置操作部","水霧滅火設備：加壓送水裝置控制盤盤面及制水閥本體","C",null,[],false,"本題考點：消防安全設備檢修完成標示的附加位置，要判斷哪一個設備被配上了不該有的部位。\n【正解理由】檢修完成標示的附加位置是依各設備的操作核心部位逐項列明:A、B、D 所述的「加壓送水裝置控制盤盤面」再搭配「消防栓箱箱面」或「制水閥本體」,都是水系統設備平時可直接目視確認的部位，與規定一致；簡易自動滅火設備的標示部位並非手動啟動裝置操作部,C 的配對與規定不符，本題問的是何者錯誤，故選 C。該附加位置規定之原文未附於候選條文，把握度標低。\n【逐項排除】\n(A) 室內消防栓設備以加壓送水裝置控制盤盤面及消防栓箱箱面為標示部位，兩處都是使用與檢查時必然接觸之處，敘述正確。\n(B) 自動撒水設備以加壓送水裝置控制盤盤面及制水閥本體為標示部位，與該設備以控制盤及制水閥為操作核心相符，敘述正確。\n(C) 手動啟動裝置操作部依《消防安全設備測試報告書測試方法及判定要領》簡易自動滅火設備之外觀試驗，是應設於距樓地板面高度 0.8m 以上 1.5m 以下並標示「手動啟動裝置」字樣的部位，屬設置高度與設備表示之規定，不是檢修完成標示的附加位置，為本題應選者。\n(D) 水霧滅火設備與自動撒水設備同屬以加壓送水裝置及制水閥運作之水系統，標示部位相同，敘述正確。\n【記憶點】水系統看控制盤盤面加箱面或制水閥本體；簡易自動滅火設備不以手動啟動裝置操作部為標示部位。","簡易自動滅火設備在法規體系裡自成一類。《設置標準》第 8 條把滅火設備列為滅火器與消防砂、室內消防栓設備、室外消防栓設備、自動撒水設備、水霧滅火設備、泡沫滅火設備、二氧化碳滅火設備、乾粉滅火設備、簡易自動滅火設備共九種；其中水系統各設備靠加壓送水裝置與閥類運作，這正是檢修完成標示多落在控制盤盤面與制水閥本體的原因。簡易自動滅火設備則依第 111-1 條設於廚房煙罩與排油煙管，由感知元件、噴頭、儲存鋼瓶及加壓用氣體鋼瓶構成，並無加壓送水裝置與制水閥，標示部位自然另有安排；該條並要求排油煙管內風速超過每秒五公尺者，應在警戒長度外側設置放出藥劑之啟動裝置及連動閉鎖閘門，警戒長度指煙罩與排油煙管接合處往內五公尺。\n檢查重點可對照《消防安全設備及必要檢修項目檢修基準》簡易自動滅火設備之外觀檢查：儲存容器與固定架應無變形、損傷、明顯腐蝕、生銹或塗裝剝離，周圍溫度在 40℃ 以下，壓力表指針應在綠色指示範圍內，標示應無損傷、脫落、污損；性能檢查則以台秤測定藥劑量，應與標示差異不超過 3%。《消防安全設備測試報告書測試方法及判定要領》之外觀試驗另定：凡煎炒、滷煮、油炸、烤肉等會生成油煙的爐具及其上方油煙罩、風管應實施保護，不同居室之油煙罩不得合併由同一套控制裝置保護，控制裝置應設在油煙罩附近、不直接受爐火熱源波及且環境溫度 49℃ 以下之場所，本體應標示「廚房簡易自動滅火裝置」字樣，緊急電源應為發電機設備或蓄電池設備且容量能使該設備有效動作一小時。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-029","變電站場所設置水霧滅火設備，放射區域 6 個分區，其消防幫浦出水量需達每分鐘 X 公升以上；且每顆水霧噴頭放水壓力均能達每平方公分 Y 公斤以上，請問前述 X、Y 為何？",29,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-031","應設置消防專用蓄水池之場所規定，下列何者正確？",31,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-028","依各類場所消防安全設備設置標準之規定，下列何者應設自動撒水設備？",28,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-032","二氧化碳滅火設備屬於公共危險物品等場所的那一類滅火設備？",32,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-027","自動撒水採用密閉乾式或預動式自動撒水設備，撒水頭動作後，流水檢知裝置應在幾分鐘內，使撒水頭放水？",27,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-033","二氧化碳滅火設備配管，下列設置規定何者錯誤？",33,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-030",113,"鹵化烴滅火設備全區放射綜合檢查時，檢查方法、判定方法及注意事項，下列何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-030",112,"消防幫浦之防止水溫上升用排放裝置，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-030",110,"公共危險物品等場所消防設計及消防安全設備，其他滅火困難場所，應設置第幾種滅火設備？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-030",109,"泡沫滅火設備計算之水溶液量，應加算充滿配管所需之泡沫水溶液量，且應加算總泡沫水溶液量之百分之多少？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-030",108,"依滅火器設置規定，下列何者錯誤？",1785129972238]