[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-029":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-029","fire-111-1-water-chemical-029",111,1,29,"變電站場所設置水霧滅火設備，放射區域 6 個分區，其消防幫浦出水量需達每分鐘 X 公升以上；且每顆水霧噴頭放水壓力均能達每平方公分 Y 公斤以上，請問前述 X、Y 為何？",{"A":16,"B":17,"C":18,"D":19},"X=1200；Y=2.7","X=1200；Y=3.5","X=2000；Y=2.7","X=2000；Y=3.5","D",null,[],false,"本題考點：水霧滅火設備加壓送水裝置的出水量與出水壓力，關鍵在放射區域數量與是否用於防護電氣設備。\n【正解理由】依《各類場所消防安全設備設置標準》第 65 條第二項第一款，消防幫浦出水量每分鐘一千二百公升以上，其放射區域二個以上時為每分鐘二千公升以上；同項第二款，出水壓力應核算管系最末端一個放射區域全部水霧噴頭放水壓力均能達每平方公分二點七公斤以上或 0.27MPa 以上，但用於防護電氣設備者，應達每平方公分三點五公斤以上或 0.35MPa 以上。變電站屬電氣設備之防護，放射區域有六個,X 為 2000、Y 為 3.5,故選 D。\n【逐項排除】\n(A) X=1200 是放射區域僅一個時之出水量;Y=2.7 是未用於防護電氣設備時之放水壓力，兩者都不合本題條件。\n(B) X=1200 未反映六個放射區域應加大至每分鐘二千公升;Y=3.5 雖為電氣設備之值，整組仍錯。\n(C) X=2000 正確，但 Y=2.7 漏用但書所定電氣設備之三點五公斤。\n(D) X=2000、Y=3.5 同時符合第 65 條之出水量與但書壓力，為正解。\n【記憶點】水霧幫浦：一區 1200、二區以上 2000;放水壓力一般 2.7,防護電氣設備 3.5。","水霧滅火設備的數值分成噴頭端與幫浦端兩組。噴頭端依第 61 條：防護對象之總面積須在各水霧噴頭放水之有效防護範圍內，每一水霧噴頭之有效半徑在二點一公尺以下，配置數量依裝設之放水角度、放水量及防護區域面積核算，每平方公尺放水量供第十八條附表第三項、第四項所列場所使用者在每分鐘二十公升以上，供其他場所使用者在每分鐘十公升以上。幫浦端依第 65 條，出水量每分鐘一千二百公升以上、放射區域二個以上時每分鐘二千公升以上；出水壓力二點七公斤，防護電氣設備者三點五公斤，並須連接緊急電源。變電站這類題目的關鍵字就是電氣設備，一出現就走但書。\n另一組容易被互套的是第 212 條：公共危險物品等場所之水霧滅火設備，放射區域每一區域在一百五十平方公尺以上(防護對象之面積未滿一百五十平方公尺者以其實際面積計算),水源容量為最大放射區域全部水霧噴頭繼續放水三十分鐘之水量、放射區域每平方公尺每分鐘放水量二十公升以上，最大放射區域水霧噴頭同時放水時各噴頭放射壓力每平方公分三點五公斤以上或 0.35MPa 以上，緊急電源供電容量四十五分鐘以上。該條屬第四編，僅適用於公共危險物品或可燃性高壓氣體場所；本題變電站是一般場所，兩編數值不得互套。檢查面可對照《消防安全設備及必要檢修項目檢修基準》水霧滅火設備之性能檢查：啟動用水壓開關裝置應確認設定壓力值是否恰當，並由操作排水閥使加壓送水裝置啟動，確認動作壓力值是否適當正常。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-028","依各類場所消防安全設備設置標準之規定，下列何者應設自動撒水設備？",28,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-030","有關消防安全設備檢修完成標示附加位置，下列敘述何者錯誤？",30,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-027","自動撒水採用密閉乾式或預動式自動撒水設備，撒水頭動作後，流水檢知裝置應在幾分鐘內，使撒水頭放水？",27,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-031","應設置消防專用蓄水池之場所規定，下列何者正確？",31,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-026","壓力開關高程 0 m，屋頂水箱高程 33 m，最高處撒水頭高程 30 m，加壓送水裝置利用啟動用壓力開關連動啟動。當壓力開關小於何值時，加壓送水裝置即應啟動？",26,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-032","二氧化碳滅火設備屬於公共危險物品等場所的那一類滅火設備？",32,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-029",113,"有關流水檢知裝置之構造，依據流水檢知裝置認可基準規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-029",112,"有關泡沫滅火設備，依各類場所消防安全設備設置標準規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-029",110,"公共危險物品等場所消防設計及消防安全設備，設置第五種滅火設備者，公共危險物品每達管制量之幾倍（含未滿）應有一滅火效能值？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-029",109,"泡沫原液與水混合使用之濃度，下列何種原液之濃度為 1%？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-029",108,"有一室內停車空間，其防護區為 25 m × 16 m × 4 m，未設自動關閉裝置之開口部面積為 10 m2，擬設置全區放射式乾粉滅火設備，試問所需法定滅火藥劑量最少為多少公斤？",1785129972229]