[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-026":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-026","fire-111-1-water-chemical-026",111,1,26,"壓力開關高程 0 m，屋頂水箱高程 33 m，最高處撒水頭高程 30 m，加壓送水裝置利用啟動用壓力開關連動啟動。當壓力開關小於何值時，加壓送水裝置即應啟動？",{"A":16,"B":17,"C":18,"D":19},"3.3 kgf\u002Fcm2","3.8 kgf\u002Fcm2","4.5 kgf\u002Fcm2","5.0 kgf\u002Fcm2","C",null,[],false,"本題考點：啟動用水壓開關裝置的啟動壓力設定，要把最高處撒水頭的高程差換算成壓力，再加上撒水頭規定放水壓力。\n【正解理由】依《各類場所消防安全設備設置標準》第 50 條，撒水頭放水壓力應在每平方公分一公斤以上或 0.1MPa 以上；水頭十公尺換算為每平方公分一公斤，最高處撒水頭高程 30 公尺對高程 0 公尺之壓力開關而言，落差壓力為 3 kgf\u002Fcm2,加上撒水頭本身所需的 1 kgf\u002Fcm2,壓力開關處至少須維持 4 kgf\u002Fcm2,再計入壓力開關動作與配管摩擦之裕度 0.5 kgf\u002Fcm2,啟動設定值即 4.5 kgf\u002Fcm2,故選 C。該裕度之計算基準未附於候選原文，把握度標低。\n【逐項排除】\n(A) 3.3 kgf\u002Fcm2 只是屋頂水箱高程 33 公尺換算的靜水壓，未計入撒水頭所需放水壓力。\n(B) 3.8 kgf\u002Fcm2 是把屋頂水箱高程誤當成最高處撒水頭高程(3.3 加 0.5)的結果，同樣漏掉放水壓力。\n(C) 4.5 kgf\u002Fcm2 由 3 加 1 加 0.5 求得，與題目給的高程條件相符，為正解。\n(D) 5.0 kgf\u002Fcm2 無法對應題目 30 公尺或 33 公尺任一高程換算後再加計的數值。\n【記憶點】啟動壓力＝最高處撒水頭落差換算壓力＋規定放水壓力＋裕度。","單位換算是這題的骨幹：每平方公分一公斤約等於十公尺水頭，也約等於 0.1MPa,所以 30 公尺就是 3 kgf\u002Fcm2、33 公尺就是 3.3 kgf\u002Fcm2。題目同時給屋頂水箱與最高處撒水頭兩個高程，正是要考生分辨「屋頂水箱是平時使配管充滿水的來源」與「最高處撒水頭是壓力要求的臨界點」兩件不同的事。\n《設置標準》第 58 條把撒水設備的加壓送水裝置寫成三種：重力水箱必要落差為配管摩擦損失水頭加十公尺；壓力水箱必要壓力為配管摩擦損失水頭加落差再加 1 kgf\u002Fcm2,且水箱內空氣須占容積三分之一以上、壓力在使用建築物最高處之撒水頭維持規定放水水壓所需壓力以上；消防幫浦全揚程為配管摩擦損失水頭加落差再加十公尺，末項並限制撒水頭放水壓力在每平方公分十公斤以下或 1MPa 以下。三式末尾的十公尺與 1 kgf\u002Fcm2,正是第 50 條放水壓力的兩種寫法。\n同樣結構換設備就換數字：室內消防栓依第 37 條，重力水箱必要落差為消防水帶摩擦損失水頭加配管摩擦損失水頭加十七公尺，壓力水箱必要壓力為前兩項加落差再加 1.7 kgf\u002Fcm2;室外消防栓依第 42 條為加二十五公尺與加 2.5 kgf\u002Fcm2。至於壓力開關本身,《消防安全設備及必要檢修項目檢修基準》自動撒水設備之性能檢查規定，啟動用水壓開關裝置應以目視及螺絲起子確認壓力開關端子有無鬆動，並確認設定壓力值是否恰當，由操作排水閥使加壓送水裝置啟動，確認動作壓力值是否適當；判定為設定壓力值應適當，且加壓送水裝置應能依設定壓力正常啟動。設定值對不對，本身就是檢查項目。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-025","泡沫試料淨重為 200 g，還原數值如下，則 25%還原時間為何？時間（分） 0 0.5 1 1.5 2 2.5 3 還原量（ml） 0 10 20 30 40 50 60",25,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-027","自動撒水採用密閉乾式或預動式自動撒水設備，撒水頭動作後，流水檢知裝置應在幾分鐘內，使撒水頭放水？",27,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-024","十樓以下建築物之樓層供百貨商場使用，如達到設置自動撒水設備條件，使用密閉式一般反應型撒水頭時，其水源容量應符合幾個撒水頭放水 20 分鐘的撒水量？",24,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-028","依各類場所消防安全設備設置標準之規定，下列何者應設自動撒水設備？",28,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-023","簡易自動滅火設備進行性能檢查時，蓄壓式滅火藥劑儲存容器滅火藥劑量應與標示差異不超過多少？",23,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-029","變電站場所設置水霧滅火設備，放射區域 6 個分區，其消防幫浦出水量需達每分鐘 X 公升以上；且每顆水霧噴頭放水壓力均能達每平方公分 Y 公斤以上，請問前述 X、Y 為何？",29,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-026",113,"設於外浮頂式儲槽之泡沫放出口為？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-026",112,"依據各類場所消防安全設備設置標準，有關撒水頭裝置之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-026",110,"固定式泡沫滅火設備之泡沫放出口，若採用高發泡放出口，其泡沫膨脹比應選擇下列何者設置之？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-026",109,"密閉式撒水頭之自動撒水設備末端查驗閥規定，下列何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-026",108,"依各類場所消防安全設備設置標準之規定，建築物高度超過 60 公尺者，連結送水管應採用濕式，其中繼幫浦設置規定之敘述何者錯誤？",1785129972212]