[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-025":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-025","fire-111-1-water-chemical-025",111,1,25,"泡沫試料淨重為 200 g，還原數值如下，則 25%還原時間為何？時間（分） 0 0.5 1 1.5 2 2.5 3 還原量（ml） 0 10 20 30 40 50 60",{"A":16,"B":17,"C":18,"D":19},"1.5 分鐘","2 分鐘","2.5 分鐘","3 分鐘","C",null,[],false,"本題考點：泡沫的 25％還原時間定義與判讀，先由試料淨重求出 25％容量值，再回到還原量記錄找出達到該量的時間。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》泡沫滅火設備綜合檢查所附發泡倍率及 25％還原時間測定方法,25％還原時間指自所採集之泡沫消泡為泡水溶液量，還原至全部泡沫水溶液量之 25％止所需之時間；測定時「將泡沫試料之淨重分為四等分，即可得所含泡水溶液量之 25％(單位 ml)」。本題試料淨重 200 g,25％容量值為 200 除以 4 等於 50 ml;對照記錄，還原量在 2.5 分時恰為 50 ml,故選 C。\n【逐項排除】\n(A) 1.5 分之還原量為 30 ml,距 25％容量值 50 ml 還差 20 ml。\n(B) 2 分之還原量為 40 ml,仍未達 50 ml。\n(C) 2.5 分之還原量恰為 50 ml,與 25％容量值相等，即為所求時間。\n(D) 3 分之還原量已達 60 ml,已越過 25％容量值，不是還原至 25％的時點。\n【記憶點】淨重除以四得 25％容量值，再回記錄找第一次達到該還原量的時間。","基準附表自己就舉了一個例子，把內插算法講得很清楚：假設泡沫試料之淨重為 180 g,25％容量值為 180÷4＝45 ml,而排液記錄為 0 分 0 ml、0.5 分 10 ml、1.0 分 20 ml、1.5 分 30 ml、2.0 分 40 ml、2.5 分 50 ml、3.0 分 60 ml,可知 45 ml 位於 2 至 2.5 分之間，再以(45－40)÷(50－40)＝1\u002F2 求得 2.25 分鐘。本題把淨重換成 200 g,25％容量值剛好落在記錄上的 50 ml,不必內插即可直接讀出 2.5 分；命題者沿用同一組排液數列、只換淨重，考的就是有沒有真的理解淨重四分之一這個換算。\n同一份附表還定義發泡倍率：發泡倍率係測量未混入空氣前之泡沫水溶液量與最終發泡量之比率，以 1400ml 除以扣除容器重量後之淨量(公克)計算；所需器具有 1400ml 容量之泡沫試料容器二個、泡沫試料採集器一個、量秤一個，以及碼表二個、泡沫試料容器台一個與 100ml 容量之透明容器四個；適用範圍為使用蛋白泡沫滅火藥劑或合成界面活性劑中之低發泡者，水成膜泡沫滅火藥劑則另以內容積 1000ml 具刻度之量筒測定。判定面，綜合檢查對固定式與移動式泡沫滅火設備都要求發泡倍率在 5 倍以上，混合比率應為設計時之稀釋容量濃度，並以糖度計法或比色計法量測。《消防安全設備測試報告書測試方法及判定要領》泡沫滅火設備綜合試驗另列判定要領：稀釋容量濃度 3％型應在 3～4％、6％型應在 6～8％;發泡倍率 5 倍以上;25％還原時間，蛋白泡沫及水成膜泡沫滅火藥劑應為 60 秒以上，合成界面活性劑泡沫滅火藥劑應為 30 秒以上。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-024","十樓以下建築物之樓層供百貨商場使用，如達到設置自動撒水設備條件，使用密閉式一般反應型撒水頭時，其水源容量應符合幾個撒水頭放水 20 分鐘的撒水量？",24,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-026","壓力開關高程 0 m，屋頂水箱高程 33 m，最高處撒水頭高程 30 m，加壓送水裝置利用啟動用壓力開關連動啟動。當壓力開關小於何值時，加壓送水裝置即應啟動？",26,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-023","簡易自動滅火設備進行性能檢查時，蓄壓式滅火藥劑儲存容器滅火藥劑量應與標示差異不超過多少？",23,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-027","自動撒水採用密閉乾式或預動式自動撒水設備，撒水頭動作後，流水檢知裝置應在幾分鐘內，使撒水頭放水？",27,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-022","有關水道連結型自動撒水設備進行綜合檢查時，其放水壓力應為多少？",22,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-028","依各類場所消防安全設備設置標準之規定，下列何者應設自動撒水設備？",28,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-025",113,"有一建築物樓高 40 m，總樓地板面積 30000 m2，其消防專用蓄水池之有效水量規定要多少立方公尺以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-025",112,"有關公共危險物品場所設置室外消防栓之規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-025",110,"自動撒水設備之水源容量規定，若使用側壁型或小區劃型撒水頭時，十層以下樓層在 X 個撒水頭、十一層以上樓層在 Y 個撒水頭繼續放水 20 分鐘之水量以上。X、Y 分別為何？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-025",109,"高架倉庫內所設置之撒水頭，其放水量每分鐘應在多少公升以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-025",108,"下列何者不屬於各類場所消防安全設備設置標準第 8 條所規定的滅火設備？",1785129972200]