[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-019":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-019","fire-111-1-water-chemical-019",111,1,19,"下列有關滅火器性能檢查之敘述，何者正確？",{"A":16,"B":17,"C":18,"D":19},"製造日期超過 5 年滅火器，應予報廢","化學泡沫滅火器應每年實施一次性能檢查","二氧化碳滅火器應每 2 年實施一次性能檢查","性能檢查完成後之滅火器瓶頸應加裝檢修環，並以顏色紅、橙、黃、綠、紫交替更換","B",null,[],false,"本題考點：滅火器的性能檢查頻率、報廢條件與檢修環顏色，依據為檢修基準滅火器章。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》滅火器之性能檢查（檢查抽樣），檢查頻率明定「依滅火器種類，化學泡沫滅火器應每年實施一次性能檢查，其餘類型滅火器應每三年實施一次性能檢查」，化學泡沫滅火器因藥劑經較長時間會產生變化，是唯一每年一次者，故選 B。\n【逐項排除】\n(A) 錯誤。同章表 1-2 備註為「製造日期超過十年或無法辨識製造日期之水滅火器、機械泡沫滅火器或乾粉滅火器，非經水壓測試合格，不得再行更換及充填藥劑，應予報廢」；門檻是十年、限於該三類，且以水壓測試不合格為條件，並非一律 5 年報廢。\n(B) 正確。化學泡沫滅火器每年實施一次性能檢查，其餘類型為每三年一次。\n(C) 錯誤。二氧化碳滅火器屬「其餘類型」，為每三年一次；表 1-2 亦以自製造年份起超過三年以上者為對象，並無 2 年之規定。\n(D) 錯誤。同章一般注意事項載明檢修環「以顏色紅、橙、黃、綠、藍交替更換」，自一百一十年度起使用紅色，後續依序為橙（111）、黃（112）、綠（113）、藍（114），並無紫色。\n【記憶點】化學泡沫「一年一次」、其餘「三年一次」；檢修環紅橙黃綠藍，自 110 年度起輪替。","滅火器的檢查分外觀檢查與性能檢查兩層，題目四個選項正好各踩一個層面。外觀檢查以目視為主：本體容器應無滅火藥劑洩漏、顯著變形、損傷及腐蝕，發現熔接部位受損、容器顯著變形、顯著腐蝕或鐵鏽剝離者應即汰換，且有此情形時得不須再施以性能檢查即可汰換；安全插梢應無脫落、壓把與護蓋應無變形且與本體緊密接合、皮管與噴嘴內部應無阻塞、壓力指示計之指示值應在綠色範圍內。性能檢查則要拆開驗藥劑，故以抽樣表控管對象。\n表 1-2 檢查試樣個數表的分類值得整理：水滅火器與強化液滅火器（加壓式、蓄壓式）以自製造年份起超過三年以上者為對象、全數檢查；化學泡沫（加壓式）以設置達一年以上者為對象、全數檢查；機械泡沫（加壓式、蓄壓式）與乾粉（加壓式、蓄壓式）為自製造年份起超過三年以上者、全數；鹵化物與二氧化碳同樣自製造年份起超過三年以上者，惟如重量及指示壓力值無異常時，其它項目可予省略；此外全部之滅火器如經外觀檢查有缺點者，均須進行性能檢查。判定上，未發現缺點者視為良好；發現缺點者應即檢修或更新，泡沫滅火藥劑應依銘板標示時間或製造商使用規範定期更換，其餘類型若滅火藥劑無固化結塊、異物、沉澱物、變色、污濁或異臭者，滅火藥劑可繼續使用。\n藥劑本身另有量與質的判定：以液面標示表示者取出前先確認有無達液面水平線，以重量表示者秤重確認，重量應在表 1-3 總重量容許範圍內（例如標示重量 1 ㎏未滿為＋100g~－80g，10 ㎏以上 20 ㎏未滿為＋700g~－400g）。新更換及充填之滅火藥劑應為經內政部登錄機構認可之產品，充填完成時噴射性能須能噴射所充填量 90% 以上，使用期限內須能噴射 80% 以上；二氧化碳滅火器所充藥劑應採一般工業用液體二氧化碳，純度 99% 以上並有相關證明文件。蓄壓式部分另定，對二氧化碳滅火器及海龍滅火器進行重量檢查時，失重超過 10％以上或壓力表示值在綠色範圍外者應予以更新。性能檢查完成後應依表 1-1 格式張貼標示，且該標示不得覆蓋、換貼或變更原新品出廠時之標示。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-018","依各類場所消防安全設備設置標準規定，總樓地板面積 100 平方公尺之何種場所應設置滅火器？ ①咖啡廳 ②幼兒園 ③陳列館 ④商場",18,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-020","電子工業廠房潔淨室設置消防安全設備，下列敘述何者正確？",20,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-017","惰性氣體滅火設備進行綜合檢查時，採低壓式者進行放射試驗時，其放射試驗所需之藥劑量，為該放射區域所設滅火藥劑量之多少以上？",17,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-021","下列有關乾粉滅火設備設置之規定，何者正確？",21,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-016","乾粉滅火設備進行性能檢查時，關於滅火藥劑量之敘述，下列何者正確？",16,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-022","有關水道連結型自動撒水設備進行綜合檢查時，其放水壓力應為多少？",22,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-019",113,"關於水帶試驗，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-019",112,"依各類場所消防安全設備設置標準規定，樓地板面積在 X 平方公尺以上之餐廳或供失智照顧型之長期照顧機構使用之場所且樓地板面積合計在 Y 平方公尺以上者，其廚房排油煙管及煙罩應設簡易自動滅火設備。則 X、Y 為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-019",110,"依各類場所消防安全設備設置標準，應設置室內消防栓設備之場所，下列規定何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-019",109,"某室內停車空間設置低發泡固定式泡沫滅火設備，每次檢修作業時，應選擇全部放射區域數多少比例以上之放射區域進行逐區放水試驗，測其放射分布及放射壓力？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-019",108,"依各類場所消防安全設備檢修及申報作業基準，有關高壓式二氧化碳滅火藥劑儲存容器之滅火藥劑量檢查方法之注意事項中，鈷 60 有效使用年限約為多少年，如已超過時，應即時連絡專業單位處理或更換？",1785129972164]