[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-017":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-017","fire-111-1-water-chemical-017",111,1,17,"惰性氣體滅火設備進行綜合檢查時，採低壓式者進行放射試驗時，其放射試驗所需之藥劑量，為該放射區域所設滅火藥劑量之多少以上？",{"A":16,"B":17,"C":18,"D":19},"5%","10%","15%","20%","B",null,[],false,"本題考點：惰性氣體滅火設備綜合檢查中，低壓式進行放射試驗所需藥劑量占該放射區域所設滅火藥劑量的比例。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》惰性氣體滅火設備之綜合檢查，全區放射方式「低壓式者」規定：「應進行放射試驗，其放射試驗所需之藥劑量，為該放射區域所設滅火藥劑量之 10％以上，或使用 40 公升氮氣 5 瓶以上作為替代藥劑放射」，故選 B。\n【逐項排除】\n(A) 錯誤。5% 不是該項所定之比例。同段出現的「5」是替代放射用的「40 公升氮氣 5 瓶以上」，以及高壓式「每次試驗最多放出 5 支」，兩者都不是藥劑量百分比。\n(B) 正確。低壓式放射試驗之藥劑量為該放射區域所設滅火藥劑量之 10％以上。\n(C) 錯誤。15% 於該章綜合檢查之核算與判定規定中查無依據。\n(D) 錯誤。20% 同樣不是本項比例；該章性能檢查另定滅火藥劑量之測定結果與重量表或圖面明細表核對「其差值應在充填值 10％以下」，仍是 10 這個數字。\n【記憶點】惰性氣體綜合檢查放射試驗：低壓式取所設滅火藥劑量 10％以上，或以 40 公升氮氣 5 瓶以上替代。","綜合檢查是把設備當成一個系統整體啟動一次，因此不可能把藥劑全部放光，規定改以「按比例取樣放射」設計。同章高壓式者的作法是以空氣或氮氣進行放射試驗，所需空氣量或氮氣量就放射區域應設滅火藥劑量之 10％核算，每公斤再依表列公升數比例換算：二氧化碳 55 公升、氮氣 100 公升、IG-55 100 公升、IG-541 100 公升，且每次試驗最多放出 5 支。低壓式因藥劑以低溫液態大量儲存，改為直接取所設滅火藥劑量之 10％以上放射，或以 40 公升氮氣 5 瓶以上替代。兩者比例一致，差別只在放什麼、怎麼換算。\n同樣的 10％也出現在鄰近各章：鹵化烴滅火設備之綜合檢查以空氣或氮氣進行放射試驗，就放射區域應設滅火藥劑量之 10％核算，每公斤依表列 HFC-23 為 34 公升、HFC-227ea 為 14 公升，每次試驗最多放出 5 支；乾粉滅火設備之綜合檢查，加壓式者所需試驗用氣體量為該放射區域應設加壓用氣體之 10％以上（小數點以下有尾數時進一），蓄壓式者為應設蓄壓用氣體量之 10％以上；簡易自動滅火設備之綜合檢查亦同。惰性氣體與鹵化烴另有抽樣分配表，依系統設置數量在十年週期內分配抽測套數，設置數量超過 21 套者依比例類推分配；抽測之系統放射區域在二區以上時，應至少擇一放射區域實施放射試驗，並於滅火藥劑儲存容器標示放射日期。\n判定方法為六項：警報裝置應確實鳴響、遲延裝置應確實動作、開口部等之自動關閉裝置應能正常動作且換氣裝置須確實停止、指定防護區劃之啟動裝置及選擇閥能確實動作可放射試驗用氣體、配管內之試驗用氣體應無洩漏、放射表示燈應確實亮燈。注意事項則載明在未完成完全換氣前不得進入放射區域，遇不得已之情形非進入時應著空氣呼吸器，檢查結束後應將試驗用氣體容器換裝回復為原設置之儲存容器。另移動式（限使用二氧化碳氣體者）之綜合檢查不按百分比，而是以 5 支噴射瞄子內、該設備一具儲存容器量為之，是常見的混淆點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-016","乾粉滅火設備進行性能檢查時，關於滅火藥劑量之敘述，下列何者正確？",16,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-018","依各類場所消防安全設備設置標準規定，總樓地板面積 100 平方公尺之何種場所應設置滅火器？ ①咖啡廳 ②幼兒園 ③陳列館 ④商場",18,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-015","採用移動式放射方式之乾粉滅火設備，藥劑種類為第四種乾粉時，每一具噴射瞄子所需藥劑放射量為何？",15,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-019","下列有關滅火器性能檢查之敘述，何者正確？",19,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-014","開放式自動撒水設備之自動啟動裝置，感知撒水頭應設在裝置面距樓地板面高度多少公尺以下，且能有效探測火災處？",14,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-020","電子工業廠房潔淨室設置消防安全設備，下列敘述何者正確？",20,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-017",113,"有關冷卻撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-017",112,"有關室內消防栓之水平距離、瞄子放水壓力、消防栓及位置之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-017",110,"密閉乾式或預動式之流水檢知裝置二次側配管，為有效排水，支管每 10 公尺傾斜 A 公分，主管每 10 公尺傾斜 B 公分。下列 A，B 何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-017",109,"某爆竹煙火儲存場所設置室外消防栓設備共 8 具，進行設備檢修綜合檢查時，至少應選擇配管上最遠最高處多少數量之室外消防栓實施放水試驗？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-017",108,"依各類場所消防安全設備檢修及申報作業基準，有關室內消防栓設備之第一種消防栓水帶及瞄子檢查方法，製造年份超過 10 年或無法辨識製造年份之水帶，應將消防水帶兩端之快速接頭連接於耐水壓試驗機，施以 X kgf\u002Fcm2 以上水壓試驗 Y 分鐘合格，始得繼續使用。則 X+Y 為若干？",1785129972145]