[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-016":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-016","fire-111-1-water-chemical-016",111,1,16,"乾粉滅火設備進行性能檢查時，關於滅火藥劑量之敘述，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"灰色為第一種乾粉","白色或淡藍色為第二種乾粉","粉紅色為第三種乾粉","紫色系為第四種乾粉","C",null,[],false,"本題考點：乾粉滅火設備性能檢查中，滅火藥劑量判定所依據的「藥劑顏色對應第幾種乾粉」。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》乾粉滅火設備之性能檢查，滅火藥劑量之判定方法明載「儲存所定之滅火藥劑應達規定量以上（灰色為第四種乾粉；粉紅色為第三種乾粉；紫色系為第二種乾粉；白色或淡藍色為第一種乾粉）」。四組對應中，粉紅色即第三種乾粉，故選 C。\n【逐項排除】\n(A) 錯誤。灰色對應的是第四種乾粉，不是第一種；第一種乾粉為白色或淡藍色。\n(B) 錯誤。白色或淡藍色對應的是第一種乾粉，不是第二種；第二種乾粉為紫色系。\n(C) 正確。粉紅色即第三種乾粉，其主成分依《各類場所消防安全設備設置標準》第 99 條表列為磷酸二氫銨。\n(D) 錯誤。紫色系對應的是第二種乾粉，不是第四種；第四種乾粉為灰色。\n【記憶點】顏色順著背：一白（或淡藍）、二紫、三粉紅、四灰；同一判定方法還要求藥劑無雜質、變質、固化，自地面上高度五十公分處落下應呈粉狀。","乾粉的顏色不是裝飾，而是現場辨識藥劑種類、避免混充與誤填的手段，所以規定落在檢修基準的「性能檢查—滅火藥劑量」而非設置標準。該項檢查方法為：蓄壓式者先以釋壓閥將壓力洩放出並確認不得有殘壓，取下滅火藥劑充填蓋，自充填口測量滅火藥劑高度，或將容器置於台秤上測定重量，再取少量（約 300 ㏄）樣品確認有無變色或結塊，並以手輕握檢視有無異常；判定方法即以顏色對應種類，並要求不得有雜質、變質、固化，以手輕握搓揉並自地面上高度五十公分處使其落下應呈粉狀。同項注意事項載明，溫度超過 40℃以上、濕度超過 60％以上時應暫停檢查——乾粉最怕受潮結塊，這也是判定固化的原因所在。加壓式儲存容器的檢查與判定方式相同。\n顏色背後是主成分。依《設置標準》第 99 條全區放射方式藥劑量表所載，第一種乾粉主成分為碳酸氫鈉、第二種為碳酸氫鉀、第三種為磷酸二氫銨、第四種為碳酸氫鉀及尿素化合物；同表每立方公尺防護區域所需滅火藥劑量依序為 0.6、0.36、0.36、0.24 公斤，每平方公尺開口部追加量為 4.5、2.7、2.7、1.8 公斤。第 102 條第一款的充填比同樣按種類分組：第一種 0.85 以上 1.45 以下、第二種或第三種 1.05 以上 1.75 以下、第四種 1.5 以上 2.5 以下。第 101 條另定供室內停車空間使用之滅火藥劑以第三種乾粉為限，正好與第三種（粉紅色、磷酸二氫銨）能對 A、B、C 類火災通用的性質相互對照。\n同章性能檢查還會考加壓用氣體容器的氣體量判定：使用氮氣者，在溫度 35℃、0kgf\u002F㎝² 狀態下，每 1 公斤乾粉滅火藥劑需氮氣 40 公升以上；使用二氧化碳者，每 1 公斤滅火藥劑需二氧化碳 20 公克以上，並加算清洗配管所需要量（20g\u002F1 ㎏）以上，且應以另外之容器儲存。顏色題與這些數值題常在同一份考卷交錯出現。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-015","採用移動式放射方式之乾粉滅火設備，藥劑種類為第四種乾粉時，每一具噴射瞄子所需藥劑放射量為何？",15,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-017","惰性氣體滅火設備進行綜合檢查時，採低壓式者進行放射試驗時，其放射試驗所需之藥劑量，為該放射區域所設滅火藥劑量之多少以上？",17,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-014","開放式自動撒水設備之自動啟動裝置，感知撒水頭應設在裝置面距樓地板面高度多少公尺以下，且能有效探測火災處？",14,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-018","依各類場所消防安全設備設置標準規定，總樓地板面積 100 平方公尺之何種場所應設置滅火器？ ①咖啡廳 ②幼兒園 ③陳列館 ④商場",18,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-013","有關自動撒水設備末端查驗閥之敘述，下列何者正確？",13,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-019","下列有關滅火器性能檢查之敘述，何者正確？",19,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-016",113,"有關自動撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-016",112,"有關二氧化碳滅火設備構件之安全措施規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-016",110,"某觀光飯店餐廳的廚房面積 750 平方公尺，其使用火源處所設置滅火器核算之最低滅火效能值應為多少？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-016",109,"製造年份超過 10 年之室內消防栓水帶進行耐水壓試驗時，施以 7 kgf\u002Fcm²以上水壓試驗多久時間，始得視為合格可繼續使用？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-016",108,"依各類場所消防安全設備檢修及申報作業基準，公共危險物品等場所達顯著滅火困難者設置之第一種滅火設備之室內消防栓，其放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。則 X+Y 為若干？",1785129972140]