[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-010":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-010","fire-111-1-water-chemical-010",111,1,10,"樓地板面積 250 平方公尺之變壓器室，依各類場所消防安全設備設置標準規定，可選擇下列何種消防安全設備？①水霧 ②泡沫 ③二氧化碳 ④乾粉",{"A":16,"B":17,"C":18,"D":19},"①②","①②③","①③④","①②③④","C",null,[],false,"本題考點：變壓器室這類使用電力設備之場所，依《各類場所消防安全設備設置標準》可選設之滅火設備種類。\n【正解理由】變壓器室即第 14 條第四款所稱「設有放映室或變壓器、配電盤及其他類似電氣設備」之場所，其火災型態為帶電中的電氣火災，滅火藥劑必須不導電或經絕緣設計。依《各類場所消防安全設備設置標準》關於應設置水霧、泡沫、二氧化碳、乾粉滅火設備場所之規定，變壓器、配電盤等電氣設備場所所適用者為水霧、二氧化碳與乾粉三種：水霧之水粒微細、水柱不連續，並須維持規定之絕緣措施，得用於電氣設備；二氧化碳與乾粉藥劑本身不導電且不含水分。泡沫滅火設備係以泡沫水溶液大量發泡覆蓋滅火，含水比例高、導電性強，不列為該類場所之可選項目，故①③④可選，故選 C。\n【逐項排除】\n(A) ①② 誤將泡沫列為可選，且漏列同屬可選之二氧化碳與乾粉。\n(B) ①②③ 雖納入二氧化碳，仍誤含泡沫，且漏列乾粉。\n(C) ①③④ 為水霧、二氧化碳、乾粉，均屬電氣設備場所可選設之滅火設備，為本題應選者。\n(D) ①②③④ 為全選，錯在把以水溶液為基底的泡沫滅火設備也納入電氣設備場所之可選範圍。\n【記憶點】電氣設備場所（變壓器室、配電盤室）記「水霧、二氧化碳、乾粉」；含大量水溶液的泡沫不在其列。","電氣設備場所的滅火藥劑選擇，核心是三個判準：藥劑本身是否導電、放射後是否造成設備二次損害、以及能否在不斷電的情況下安全施放。變壓器室內的變壓器與匯流排在滅火過程中往往仍帶電，若以大量水溶液覆蓋，除人員感電風險外，絕緣油與繞組吸水後亦難以復用；泡沫滅火設備是以泡沫水溶液發泡覆蓋滅火，含水比例高，因此不列入電氣設備場所的可選項目。水霧滅火設備雖以水為介質，但霧化後的水粒細小、水柱不連續，且設計上須維持規定之絕緣措施，故得用於電氣設備。二氧化碳滅火設備以窒息與冷卻作用滅火，乾粉滅火設備以抑制燃燒連鎖反應為主，兩者藥劑皆不導電且不含水分，是電氣火災的典型選項。\n本題的法源是《各類場所消防安全設備設置標準》中關於應設置水霧、泡沫、二氧化碳、乾粉滅火設備場所之規定，該規定以表列方式指定各類場所可選設之滅火設備種類；候選條文未涵蓋這部分內容，故本題僅引至章節層級，不寫具體條號。候選條文中可確認的相關規定是第 14 條第四款：設有放映室或變壓器、配電盤及其他類似電氣設備之各類場所應設置滅火器，可見變壓器室在本標準中被獨立列為一類須特別處置的空間；第 7 條則界定滅火設備係指以水或其他滅火藥劑滅火之器具或設備，水霧、泡沫、二氧化碳、乾粉均屬之。\n延伸考點有二。其一是免設關係：第 17 條第二項規定應設自動撒水設備之場所，依本標準設有水霧、泡沫、二氧化碳、乾粉等滅火設備者，在該有效範圍內得免設自動撒水設備；第 16 條第二項對室外消防栓設備亦有結構相同的免設規定，命題者常以「已設某滅火設備」翻轉答案。其二是二氧化碳滅火設備的放射方式，第 82 條分為全區放射方式（以不燃材料建造之牆、柱、樓地板或天花板等區劃間隔，且開口部設有自動關閉裝置之區域）、局部放射方式，以及移動放射方式（皮管接頭至防護對象任一部分之水平距離在十五公尺以下），變壓器室這類可完整區劃的空間多採全區放射方式。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-009","泡沫滅火設備之減水警報裝置進行性能檢查時，當呼水槽水量減少到多少時，應發出警報？",9,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-011","依各類場所消防安全設備設置標準規定，消防專用蓄水池應設置於消防車能接近至多少公尺範圍內，易於抽取處？",11,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-008","固定式泡沫滅火設備（低發泡）進行綜合檢查作業時，發泡倍率應在幾倍以上？",8,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-012","有關水霧滅火設備，依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",12,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-007","下列有關撒水頭設置之敘述，何者正確？",7,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-013","有關自動撒水設備末端查驗閥之敘述，下列何者正確？",13,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-010",113,"有關室內消防栓測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-010",112,"水霧滅火設備係利用特殊水霧噴頭，使水呈微粒霧狀及特定角度、形狀噴出，並均勻地覆蓋燃燒表面，達到滅火效果。下列何者非水霧滅火設備針對油類火災之滅火作用與原理？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-010",110,"實施泡沫噴頭外觀檢查，應進行之項目內容不包括下列那一項？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-010",109,"全區放射方式之二氧化碳滅火設備，應設置從啟動裝置動作至二氧化碳放出時間至少多久的遲延裝置？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-010",108,"有一電信機械室，設置二氧化碳滅火設備，採全區放射方式，其所核算之滅火藥劑量應於多少秒內全部放射完畢？",1785129972103]