[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-008":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-008","fire-111-1-water-chemical-008",111,1,8,"固定式泡沫滅火設備（低發泡）進行綜合檢查作業時，發泡倍率應在幾倍以上？",{"A":16,"B":17,"C":18,"D":19},"3","5","8","10","B",null,[],false,"本題考點：《消防安全設備及必要檢修項目檢修基準》泡沫滅火設備綜合檢查中，固定式（低發泡）之發泡倍率判定值。\n【正解理由】依檢修基準泡沫滅火設備綜合檢查「（一）固定式泡沫滅火設備（低發泡）」之判定方法，於距加壓送水裝置最遠之放射區域進行泡沫放射，依附表之發泡倍率及 25％還原時間測定方法測定後，判定為「其發泡倍率應在 5 倍以上，其混合比率應為設計時之稀釋容量濃度」；《消防安全設備測試報告書測試方法及判定要領》泡沫滅火設備綜合試驗亦載「發泡倍率應在 5 倍以上」，兩份文件一致，故選 B。\n【逐項排除】\n(A) 3：未達判定方法所定之 5 倍，且檢修基準與判定要領均未以 3 倍作為低發泡之判定門檻。\n(B) 5：與檢修基準綜合檢查判定方法及判定要領綜合試驗逐字相符，為本題應選者。\n(C) 8：非發泡倍率之判定值；八十以上一千以下是第 70 條表列的高發泡膨脹比範圍，屬設備選型參數。\n(D) 10：亦非判定值；第 70 條所稱低發泡為膨脹比二十以下，勿與綜合檢查之發泡倍率判定值混用。\n【記憶點】低發泡綜合檢查抓三個數字：發泡倍率 5 倍以上、蛋白與水成膜泡沫 25％還原時間 60 秒以上、合成界面活性劑泡沫 30 秒以上。","發泡倍率的定義寫在檢修基準泡沫滅火設備綜合檢查所附之「泡沫滅火設備發泡倍率及 25％還原時間測定方法」附表裡：以 1400ml 容量之泡沫試料容器採樣，先測出容器重量，將泡沫試料量測至公克單位後，以「1400ml ÷ 扣除容器重量後之淨量(g)＝發泡倍率」計算。換句話說，發泡倍率量的是同一體積泡沫中究竟含有多少泡水溶液，淨重愈輕代表含氣愈多、倍率數值愈大。25％還原時間則指自所採集之泡沫消泡為泡水溶液，還原至全部泡沫水溶液量之 25％止所需之時間；附表以淨重 180g、25％容量值 45ml 的實例，示範用內插法由排液量記錄求得 2.25 分鐘。\n綜合檢查的取樣方式也常入題：設置泡沫頭者，每次選擇全部放射區域數之 20％以上之放射區域，進行逐區放水試驗，測其放射分布及放射壓力；再於距加壓送水裝置最遠之放射區域進行泡沫放射，依附表測其發泡倍率及 25％還原時間，並以所採取之泡水溶液，利用糖度計法或比色計法測其混合比率。移動式泡沫滅火設備之綜合檢查同樣要求發泡倍率應在 5 倍以上，混合比率應為設計時之稀釋容量濃度。\n易混淆概念對照：發泡倍率是檢查判定值，膨脹比是設備選型參數。第 70 條表列膨脹比二十以下者為低發泡，泡沫放出口選用泡沫噴頭或泡水噴頭；膨脹比八十以上一千以下者為高發泡，選用高發泡放出口；同條第二項並定義膨脹比為泡沫發泡體積與發泡所需泡沫水溶液體積之比值。至於藥劑濃度，《消防安全設備測試報告書測試方法及判定要領》泡沫滅火設備綜合試驗載明稀釋容量濃度如為 3%型者應在 3～4% 之範圍內、如為 6%型者應在 6～8% 之範圍內，25％還原時間則為蛋白泡沫滅火藥劑及水成膜泡沫滅火藥劑 60 秒以上、合成界面活性劑泡沫滅火藥劑 30 秒以上。把「倍率、還原時間、稀釋濃度」三組數字放在一起記，可一次涵蓋泡沫綜合檢查與綜合試驗的常見命題點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-007","下列有關撒水頭設置之敘述，何者正確？",7,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-009","泡沫滅火設備之減水警報裝置進行性能檢查時，當呼水槽水量減少到多少時，應發出警報？",9,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-006","消防幫浦之防止水溫上升用排放裝置，防止水溫上升用之排水管內之流水量，當幫浦在全閉狀態下連續運轉時，不使幫浦內部水溫，升高至攝氏多少度以上？",6,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-010","樓地板面積 250 平方公尺之變壓器室，依各類場所消防安全設備設置標準規定，可選擇下列何種消防安全設備？①水霧 ②泡沫 ③二氧化碳 ④乾粉",10,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-005","有關移動式泡沫滅火設備，依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",5,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-011","依各類場所消防安全設備設置標準規定，消防專用蓄水池應設置於消防車能接近至多少公尺範圍內，易於抽取處？",11,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-008",113,"有關幫浦之形狀、構造部分，依據消防幫浦認可基準規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-008",112,"某引擎試驗室設置有泡沫滅火設備，採高發泡放出口局部放射方式，依規定高發泡放出口之泡沫水溶液放射量，防護面積每 1 平方公尺應在每分鐘 X 公升以上。又防護面積係指防護對象外周線以高出防護對象物高度 Y 倍數值（該數值小於 1 公尺時，以 1 公尺計）所包圍之面積。其中 X+Y=？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-008",110,"消防搶救上之必要設備中，連結送水管之送水口設置，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-008",109,"預動式自動撒水設備竣工測試進行放水試驗時，開放末端查驗閥後，應在多久時間內正常放水？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-008",108,"移動式泡沫滅火設備之加壓送水裝置使用消防幫浦時，若同一樓層設 3 個泡沫消防栓箱時，其出水量應在每分鐘多少公升以上？",1785129972090]