[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-fire-law-037":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-消防法規概要-037","fire-111-1-fire-law-037",111,1,37,"依據乾粉滅火設備各種標示規格規定，其標示規格為長 480 mm 以上，寬 270 mm 以上，黃底黑字，每字大小為 25 mm×25 mm 以上，係屬下列何者？",{"A":16,"B":17,"C":18,"D":19},"手動啟動裝置","音響警報裝置","移動放射方式","放射表示燈","B",null,[],false,"本題考點：乾粉滅火設備各種標示規格中，長 480 mm 以上、寬 270 mm 以上、黃底黑字、每字 25 mm×25 mm 以上者，係何種裝置之標示。\n【正解理由】依《各類場所消防安全設備設置標準》第 98 條，乾粉滅火設備之放射方式、音響警報裝置、安全裝置及各種標示規格，準用第八十二條、第九十條至第九十三條及第九十七條規定；而第 97 條明定各種標示規格「由中央消防機關另定之」，其依據即題幹所稱《乾粉滅火設備各種標示規格》。該規格所列長 480 mm 以上、寬 270 mm 以上、黃底黑字之大型告示，係音響警報裝置之標示，故選 B。（候選條文未附該規格原文。）\n【逐項排除】\n(A) 手動啟動裝置之標示設於啟動操作處供辨識之用，規格另有規定，與本題所列大型黃底黑字告示不符。\n(B) 依準用之第 92 條，音響警報裝置於手動或自動裝置動作後應自動發出警報，藥劑未全部放射前不得中斷，並應有效報知防護區域或防護對象內所有人員；配合此一警示機能，其標示採大面積黃底黑字，為本題應選者。\n(C) 移動放射方式依準用之第 82 條第三款，係皮管接頭至防護對象任一部分之水平距離在十五公尺以下之放射方式規定，非標示規格。\n(D) 放射表示燈依準用之第 93 條第二款，設於防護區域出入口等易於辨認處所，屬燈具而非告示牌。\n【記憶點】乾粉設備標示中面積最大的黃底黑字牌，就是音響警報裝置之標示。","氣體與乾粉系統的條文設計是「以二氧化碳滅火設備為母法、其餘準用」。《設置標準》第 82 條把放射方式分為全區放射、局部放射與移動放射三種：全區放射須以不燃材料建造之牆、柱、樓地板或天花板等區劃間隔，開口部設自動關閉裝置，但能有效補充開口部洩漏量者得免設；局部放射依防護對象之形狀、構造、數量及性質配置噴頭；移動放射方式則要求皮管接頭至防護對象任一部分之水平距離在十五公尺以下。第 92 條定音響警報裝置三款要件：動作後自動發出警報且藥劑未全部放射前不得中斷、應有效報知防護區域或防護對象內所有人員、全區放射方式者採用人語發音（平時無人駐守者除外）。第 93 條定全區放射方式之安全裝置：啟動裝置開關或拉桿開始動作至儲存容器之容器閥開啟，應設二十秒以上之遲延裝置，並於防護區域出入口等易於辨認處所設置放射表示燈。第 97 條把各種標示規格授權中央消防機關另定，第 98 條則讓乾粉滅火設備準用上述各條。\n這一整組規定的共同目的是「放射前把人清出去」：二十秒以上遲延、人語發音之音響警報、出入口的放射表示燈、以及大面積的警示標示，構成由聽覺到視覺的多重告知。標示之所以採黃底黑字並訂出最小尺寸與最小字級，是因為它必須在防護區域周邊被遠距辨識，與設在啟動裝置本體旁的操作標示、或屬於燈具的放射表示燈，功能層級完全不同。\n乾粉設備的其他常考點可一併整理：第 108 條規定加壓式乾粉滅火設備之定壓動作裝置，啟動裝置動作後儲存容器壓力達設定壓力時應使放出閥開啟，且定壓動作裝置設於各儲存容器。公共危險物品等場所另有第四編之特別規定，第 223 條明定乾粉滅火設備準用第九十八條至第一百十一條，但全區放射方式者，應依該編表列滅火劑之係數乘以第九十九條所算出之量，未表列之公共危險物品則依中央主管機關認可之試驗求其係數——一般場所與公共危險物品場所的藥劑量算法不同，作答時要先確認題幹的場所屬性。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-fire-law-036","受託辦理檢修之檢修機構應依相關規定檢修完成消防安全設備後，依照消防安全設備檢修及申報辦法規定，應附加檢修完成標示檢修機構專業樣式以何種顏色為底？",36,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-fire-law-038","有關加壓送水裝置之電動機，其種類、構造及機能等之敘述，何者正確？",38,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-fire-law-035","某合法 KTV 視聽歌唱場所經當地消防機關會勘通過依法取得室內裝修許可，依照消防安全設備檢修及申報辦法規定，自該室內裝修許可核發之日期起算，距申報期限在多少個月以內，免辦理當次檢修及申報備查？",35,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-fire-law-039","避難器具裝置在固定部上之固定器具材料如為鋼材，其鋼索之容許拉伸應力為剪斷荷重的多少比例？",39,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-fire-law-034","依消防安全設備及必要檢修項目檢修基準規定，對二氧化碳滅火器進行重量檢查時，如失重超過多少比例以上或壓力表示值在綠色範圍外時，應予以更新，下列何者正確？",34,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-fire-law-040","依建築技術規則建築設計施工編規定，有關分戶牆及分間牆構造，下列敘述何者正確？",40,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-037",114,"依建築技術規則建築設計施工編規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-037",113,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定，六類物品製造場所及一般處理場所，其外牆或相當於該外牆之設施外側，與廠區外鄰近公共危險物品及可燃性高壓氣體製造、儲存或處理場所、加油站、加氣站、天然氣儲槽、可燃性高壓氣體儲槽、爆竹煙火製造、儲存、販賣場所及其他危險性類似場所之安全距離，應在多少公尺以上？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-037",112,"依建築技術規則建築設計施工編之規定，有關建築技術用語之定義，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-law-037",110,"有關二氧化碳滅火設備使用之各種標示規格，下列敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-037",109,"依建築技術規則建築設計施工編之定義，每層陽臺面積之和，以不超過建築面積多少為限？其未達 8 平方公尺者，得建築 8 平方公尺。",1785129969581]