[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-fire-law-033":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-消防法規概要-033","fire-111-1-fire-law-033",111,1,33,"依消防法施行細則規定，供公眾使用建築物應遴選防火管理人並制定消防防護計畫，其相關規定下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"防火避難設施之自行檢查：每月至少檢查一次","滅火、通報及避難訓練之實施：每年至少應舉辦一次，每次不得少於 4 小時","增建、改建、修建、室內裝修施工時，應另定消防防護計畫","員工在 50 人以上者，自衛消防編組應增編安全防護班及救護班","B",null,[],false,"本題考點：《消防法施行細則》第 15 條消防防護計畫應包括事項中，自衛消防編組、自行檢查與訓練之頻率、時數。\n【正解理由】依第 15 條第一項第五款，滅火、通報及避難訓練之實施「每半年至少應舉辦一次，每次不得少於四小時，並應事先通報當地消防機關」。選項 B 把頻率寫成「每年至少應舉辦一次」，與條文之「每半年」不符，屬錯誤敘述，故選 B。\n【逐項排除】\n(A) 與第 15 條第一項第二款相符：防火避難設施之自行檢查每月至少檢查一次，檢查結果遇有缺失，應報告管理權人立即改善。\n(B) 訓練頻率應為每半年至少一次；選項後段「每次不得少於四小時」雖與條文相同，但前段頻率已誤，且條文尚要求事先通報當地消防機關，為本題應選者。\n(C) 與第 15 條第二項相符：遇有增建、改建、修建、室內裝修施工時，應另定消防防護計畫，以監督施工單位用火、用電情形。\n(D) 與第 15 條第一項第一款相符：員工在十人以上者至少編組滅火班、通報班及避難引導班，員工在五十人以上者應增編安全防護班及救護班。\n【記憶點】防火管理三個數字：自行檢查每月一次、訓練每半年一次且每次四小時、員工五十人以上加編安全防護班與救護班。","防火管理制度的法源在《消防法》第 13 條：一定規模以上供公眾使用建築物，應由管理權人遴用防火管理人，責其製定消防防護計畫，報請消防機關核備，並依該計畫執行防火管理上必要之業務；地面樓層達十一層以上建築物、地下建築物或中央主管機關指定之建築物，管理權有分屬時，各管理權人應協議製定共同消防防護計畫；防火管理人遴用後應報請直轄市、縣（市）消防機關備查，異動時亦同。細則第 16 條補充，協議製定共同消防防護計畫者，由各管理權人互推一人為召集人，無法互推時得申請消防機關指定。\n「一定規模以上供公眾使用建築物」的範圍在細則第 13 條，共九款，包含電影片映演場所、演藝場、歌廳、舞廳、夜總會、俱樂部、保齡球館、三溫暖；理容院、指壓按摩場所、錄影節目帶播映場所、視聽歌唱場所、酒家、酒吧、PUB、酒店（廊）；觀光旅館、旅館；總樓地板面積五百平方公尺以上之百貨商場、超級市場及遊藝場；三百平方公尺以上之餐廳；醫院、療養院、養老院；學校、二百平方公尺以上之補習班或訓練班；五百平方公尺以上且員工三十人以上之工廠或機關（構）等。這些面積與人數門檻是另一組高頻考點。\n防火管理人的資格在細則第 14 條：應為管理或監督層次人員，並經中央消防機關認可之訓練機構或直轄市、縣（市）消防機關講習訓練合格領有證書；講習訓練分初訓與複訓，初訓合格後每三年至少應接受複訓一次，初訓時數不得少於十二小時、複訓不得少於六小時。把它和第 15 條的訓練規定並列記憶：防火管理人自己是「初訓十二小時、複訓六小時、每三年複訓一次」，場所的滅火、通報及避難訓練則是「每半年一次、每次四小時」，命題者最愛互換這兩組數字。另可對照細則第 19-2 條之安全技術人員，講習訓練不得少於十六小時、每二年複訓一次且每次不得少於八小時，三套時數一起記，考場上不會混。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-fire-law-032","供某住宿式長期照顧機構使用之五層樓建築物，各樓層若符合下列何者之規定，得免設避難器具？",32,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-fire-law-034","依消防安全設備及必要檢修項目檢修基準規定，對二氧化碳滅火器進行重量檢查時，如失重超過多少比例以上或壓力表示值在綠色範圍外時，應予以更新，下列何者正確？",34,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-fire-law-031","依消防安全設備及必要檢修項目檢修基準規定，使用加熱試驗器分別對差動式局限型 1 種探測器及離子式局限型光電式局限型 2 種探測器加熱，確認其應動作之時間分別是 A 秒內及 B 秒內，A+B 為多少？",31,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-fire-law-035","某合法 KTV 視聽歌唱場所經當地消防機關會勘通過依法取得室內裝修許可，依照消防安全設備檢修及申報辦法規定，自該室內裝修許可核發之日期起算，距申報期限在多少個月以內，免辦理當次檢修及申報備查？",35,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-fire-law-030","依各類場所消防安全設備設置標準規定，某樓層高度超過 10 公尺且樓地板面積在 700 平方公尺以上之高架儲存倉庫，其撒水頭設置應符合之規定，下列敘述何者正確？",30,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-fire-law-036","受託辦理檢修之檢修機構應依相關規定檢修完成消防安全設備後，依照消防安全設備檢修及申報辦法規定，應附加檢修完成標示檢修機構專業樣式以何種顏色為底？",36,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-033",114,"依六類公共危險物品製造儲存及處理場所標示板規格及設置要點規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-113-1-fire-law-033",113,"依建築技術規則建築設計施工編規定，下列何者不視為居室？",{"webId":62,"year":63,"stem":64,"number":13},"fire-112-1-fire-law-033",112,"依消防幫浦加壓送水裝置等及配管摩擦損失計算基準之規定，下列敘述何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-law-033",110,"依消防安全設備及必要檢修項目檢修基準規定，有關固定式泡沫滅火設備（低發泡）綜合檢查之檢查方法，下列敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-033",109,"依各類場所消防安全設備檢修及申報作業基準之規定，各類場所之管理權人應委託檢修專業機構或消防法第 7 條規定之人員辦理檢修，並於檢修完成後多少日內，分別填具消防安全設備檢修申報表及檢附消防安全設備檢修報告書，向當地消防機關申報？",1785129969543]