[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-037":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-警報與避難系統消防安全設備概要-037","fire-111-1-alarm-evacuation-037",111,1,37,"醫院之排煙設備進行綜合檢查時，緊急電源之檢查應如何落實？",{"A":16,"B":17,"C":18,"D":19},"有困難之場所，得使用常用電源進行檢查","應務必以緊急電源測試偵煙探測器連動排煙機之啟動","應落實以緊急電源運轉測試電動機電流","應落實以緊急電源運轉測試排煙機風量","A",null,[],false,"本題考點：排煙設備綜合檢查原則須切換緊急電源，以及醫院等場所在注意事項中的例外處理。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第二十二章排煙設備之綜合檢查，檢查方法為「切換成緊急電源的狀態，使偵煙式探測器動作及操作手動啟動裝置，以確認各部分之性能」，同節注意事項則明定「醫院等切換成緊急電源進行檢查有困難之場所，應使用常用電源進行檢查」。題幹場所即醫院，正落在該注意事項的射程內，故選 A。\n【逐項排除】\n(A) 與注意事項所定「醫院等…有困難之場所」改用常用電源進行檢查之意旨相符；同基準第二十章連結送水管、第四章自動撒水設備、第六章水霧滅火設備等章之綜合檢查亦寫「得使用常用電源檢查」。\n(B) 檢查方法固然以緊急電源狀態使偵煙式探測器動作，但醫院有困難時依注意事項改用常用電源，寫成「務必」與該注意事項牴觸。\n(C) 運轉電流確為判定方法第二項，惟醫院仍得改用常用電源，「應落實以緊急電源」的限定不成立。\n(D) 該章綜合檢查的四項判定為連動啟動排煙機、運轉電流在規定範圍內、無異常聲音及振動、回轉葉片回轉方向正常，並無風量測定；排煙風量屬《消防安全設備測試報告書測試方法及判定要領》第十七章排煙設備丙、綜合試驗之項目。\n【記憶點】排煙設備綜合檢查原則切換緊急電源，醫院等有困難者依注意事項使用常用電源；檢修基準量的是電流、聲音振動與回轉方向，排煙風量在測試要領的綜合試驗。","「醫院得改用常用電源」不是排煙設備的特例，而是檢修基準綜合檢查的通例。候選原文中，第二章室內消防栓設備、第三章室外消防栓設備、第四章自動撒水設備（密閉式與開放式）、第六章水霧滅火設備、第七章泡沫滅火設備、第二十章連結送水管的綜合檢查注意事項都寫「於檢查類似醫院之場所，因切換成緊急電源可能會造成困擾時，得使用常用電源檢查」，第二十二章排煙設備則寫成「醫院等切換成緊急電源進行檢查有困難之場所，應使用常用電源進行檢查」。緣由在於醫院有維生設備與不可中斷之用電，切斷常用電源的風險高於該項檢查所能取得的資訊。\n排煙設備的檢查層次要分清楚。檢修基準第二十二章的性能檢查查三大塊：電動機之控制裝置（各開關、保險絲、繼電器、表示燈、結線接續、接地）、啟動裝置（自動啟動裝置確認偵煙式探測器動作後能否連動排煙機啟動；手動啟動方式確認操作箱把手及操作桿之轉動與打開動作，操作桿應無破損、鋼索應無斷落或生鏽）、排煙機（電動機之回轉軸、軸承部潤滑油、動力傳達裝置之皮帶輪及Ｖ型皮帶、本體有無顯著發熱與異常震動，以及回轉葉片之回轉方向）。綜合檢查則只有四項判定，且注意事項要求留意測試對所連動空調機械造成的影響。\n排煙量與開口面積的數值在兩處並列出現：《消防安全設備測試報告書測試方法及判定要領》第十七章排煙設備丙、綜合試驗的判定要領載，排煙口之開口面積不得小於防煙區劃面積之百分之二且應以自然方式直接排至戶外，無法自然排至戶外時應設排煙機；排煙機應能隨任一排煙口之開啟而動作，其排煙量不得小於每分鐘一百二十立方公尺，在一防煙區劃時不得小於該防煙區劃面積每平方公尺每分鐘一立方公尺，在二區以上之防煙區劃時不得小於最大防煙區劃面積每平方公尺每分鐘二立方公尺，但地下建築物之地下通道，總排煙量不得小於每分鐘六百立方公尺。設置標準第 188 條第七款、第八款是同一組數值，同條第九款並定排煙設備應連接緊急電源，其供電容量應供其有效動作三十分鐘以上，第十一款要求排煙口開啟時應連動停止空氣調節及通風設備運轉。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-alarm-evacuation-036","探測器安裝與天花板冷氣出風口應保持適當之距離，與火警探測器認可基準之下列何者有關？",36,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-alarm-evacuation-038","依消防安全設備及必要檢修項目檢修基準，針對緩降機之下降空間進行外觀檢查時，確認有無妨礙下降之物品，及有無確保下降必要之空間，下列何者錯誤？",38,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-alarm-evacuation-034","二氧化碳滅火系統全區放射的空間，以往造成人員死傷之動作噴發，與防護空間下列因素何者無關？",34,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-alarm-evacuation-039","民國 84 年取得使用執照之大樓，測試其火警地區音響裝置之音壓何者正確？",39,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-alarm-evacuation-033","依消防安全設備測試報告書測試方法及判定要領，有關瓦斯漏氣火警自動警報設備檢知器之動作試驗，以加瓦斯試驗器將試驗瓦斯加進檢知器，測定至瓦斯漏氣表示為止之時間，下列何者正確？",33,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-alarm-evacuation-040","光電式分離型探測器進行外觀試驗，以目視確認探測器光軸應平行牆壁距離 X 公分以上，且探測器之光軸高度應在天花板等高度 Y%以上之位置。而使用減光罩進行動作試驗，非蓄積型探測器之動作時間應在 Z 秒內。則 X、Y、Z 值，下列何者正確？",40,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-037",113,"有關第三種偵煙局限型探測器之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不符？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-037",112,"下列何者非各類場所消防安全設備設置標準規定應設置無線電通信輔助設備之場所？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-037",110,"下列有關緊急電源插座之設置，何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-037",109,"有關警報系統消防安全設備設置，下列何者與各類場所消防安全設備設置標準之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-037",108,"某機場候機室樓地板面積 300 m2，自然排煙設備其窗戶都在天花板或其下方 80 公分範圍內，共有 10 扇窗，採正向由上往外推可達 90°，請問每一扇窗面積多大才合格？",1785129963764]