[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-036":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-警報與避難系統消防安全設備概要-036","fire-111-1-alarm-evacuation-036",111,1,36,"探測器安裝與天花板冷氣出風口應保持適當之距離，與火警探測器認可基準之下列何者有關？",{"A":16,"B":17,"C":18,"D":19},"老化試驗","動作試驗","濕度試驗","震動試驗","B",null,[],false,"本題考點：探測器與天花板出風口保持距離的目的——確保煙與熱氣流到得了探測器並在規定時間內動作，對應到認可基準的動作試驗。\n【正解理由】依《各類場所消防安全設備設置標準》第 115 條第一款，天花板上設有出風口時，除火焰式、差動式分布型及光電式分離型探測器外，應距離該出風口一點五公尺以上；同條第二款定牆上設有出風口時亦應距離一點五公尺以上，但該出風口距天花板在一公尺以上時不在此限。此距離的意義在於冷氣氣流會吹散、稀釋煙與熱氣流，使探測器延遲甚至無法感知；而「以加煙試驗器、加熱試驗器或減光罩測定至探測器動作為止之時間是否在規定值以內」正是動作試驗的內容（《消防安全設備測試報告書測試方法及判定要領》第九章火警自動警報設備乙、性能試驗即以此方式逐種測定動作時間），故選 B。\n【逐項排除】\n(A) 老化試驗檢驗長時間使用後性能是否維持，屬耐久性項目，與設置位置的氣流條件無關。\n(B) 動作試驗量測探測器自受煙、受熱到動作所需之時間，出風口氣流直接左右這段時間，與該距離規定相關。\n(C) 濕度試驗檢驗高濕環境下性能是否正常，關切的是水分而非風速與氣流方向。\n(D) 震動試驗檢驗承受振動後性能是否維持，屬機械強度項目，與煙、熱氣流能否到達探測器無關。\n【記憶點】距出風口一點五公尺是為了讓煙與熱到得了探測器，量的就是動作時間；第一款（天花板）有火焰式等三種除外，第二款（牆上）不分種類。","探測器與氣流的關係在設置標準第 115 條是一整組規定，五款要一併看。第一款把距天花板出風口一點五公尺以上的要求，明文排除火焰式、差動式分布型及光電式分離型三種——火焰式感知火焰輻射，差動式分布型以空氣管配合檢出器感知大範圍溫升，光電式分離型以光軸長距離監視，都不倚賴局部熱氣流或煙的滯留。第二款處理牆上出風口，同樣一點五公尺以上，但該出風口距天花板在一公尺以上時不在此限。第三款方向相反：天花板設排氣口或回風口時，偵煙式探測器應裝置於排氣口或回風口周圍一公尺範圍內，因為氣流會把煙帶往回風口。第四款要求局限型探測器以裝置在探測區域中心附近為原則，第五款定局限型探測器不得傾斜四十五度以上，但火焰式探測器不在此限。\n動作時間的判定值，《消防安全設備測試報告書測試方法及判定要領》第九章寫得最完整：定溫式局限型（非再用型）以加熱試驗器加熱，特種 40 秒、第一種 60 秒、第二種 120 秒以內，但標稱動作溫度和周圍溫度的差超過 50 度時，得將動作時間設定為 2 倍之值；差動式局限型與補償式局限型第一種、第二種均為 30 秒；離子式局限型、光電式局限型第一種 30 秒、第二種 60 秒、第三種 90 秒，蓄積型則為表列時間加上標稱蓄積時間及 5 秒；光電式分離型使用減光罩，非蓄積型 30 秒以內；火焰型探測器室內型、室外型、道路型均為 30 秒。《消防安全設備及必要檢修項目檢修基準》第十三章火警自動警報設備二、性能檢查之蓄積性能，以表 13-7、表 13-8 同一組動作時間判定；而偵煙式探測器（局限型）取下後以感度試驗器確認感度是否在探測器所定範圍內、分離型使用適合之減光罩進行動作及不動作試驗，則列在同章三、綜合檢查的探測器感度項下，兩者分屬不同檢查階段。\n延伸考點是選設：第 114 條依裝置場所高度限定可用種類，第 122 條定偵煙式探測器（光電式分離型除外）之有效探測範圍與走廊、通道步行距離每三十公尺（使用第三種探測器每二十公尺）至少設置一個。候選原文未附《火警探測器認可基準》全文，故本題僅就設置目的與各試驗項目之性質說明，未引用該基準之章項。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-alarm-evacuation-034","二氧化碳滅火系統全區放射的空間，以往造成人員死傷之動作噴發，與防護空間下列因素何者無關？",34,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-alarm-evacuation-037","醫院之排煙設備進行綜合檢查時，緊急電源之檢查應如何落實？",37,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-alarm-evacuation-033","依消防安全設備測試報告書測試方法及判定要領，有關瓦斯漏氣火警自動警報設備檢知器之動作試驗，以加瓦斯試驗器將試驗瓦斯加進檢知器，測定至瓦斯漏氣表示為止之時間，下列何者正確？",33,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-alarm-evacuation-038","依消防安全設備及必要檢修項目檢修基準，針對緩降機之下降空間進行外觀檢查時，確認有無妨礙下降之物品，及有無確保下降必要之空間，下列何者錯誤？",38,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-alarm-evacuation-032","某場所進行緊急廣播設備綜合檢查，使用噪音計（A 特性）量測揚聲器之音壓位準，在距 L 級揚聲器 1 公尺處，音壓位準值應在 X dB 以上；又挑高空間採性能設計之指向型揚聲器，於廣播區域內任一位置距樓地板面 Y 公尺處，音壓位準值應在 Z dB 以上。則 X、Y、Z 值，下列何者正確？",32,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-alarm-evacuation-039","民國 84 年取得使用執照之大樓，測試其火警地區音響裝置之音壓何者正確？",39,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-036",113,"依住宅用火災警報器設置辦法規定，住宅用火災警報器應安裝於寢室、廚房、樓梯。若非屬前三類處所且任一樓層有超過 X 平方公尺之居室達 Y 間以上者，則設於走廊。則 X、Y 分別為何？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-036",112,"依消防安全設備及必要檢修項目檢修基準，有關火警自動警報設備偵煙探測器局限型，其性能檢查的敘述，下列何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-036",110,"某場所第五層需設置排煙設備，樓地板面積為 1200 平方公尺並區分為 450、400 及 350 平方公尺等三個防煙區劃，試問該層排煙機之排煙量最少應為每分鐘多少立方公尺？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-036",109,"有關定溫式感知線型探測器之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-036",108,"依各類場所消防安全設備設置標準第 28 條應設置排煙設備之規定，下列何者錯誤？",1785129963758]