[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-034":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-警報與避難系統消防安全設備概要-034","fire-111-1-alarm-evacuation-034",111,1,34,"二氧化碳滅火系統全區放射的空間，以往造成人員死傷之動作噴發，與防護空間下列因素何者無關？",{"A":16,"B":17,"C":18,"D":19},"電銲施工高溫使感熱探測器誤動作","電銲施工的煙生成使偵煙探測器誤動作","電銲施工電弧電磁效應使偵煙探測器誤動作","設計藥劑量太多，人員關閉空間換氣裝置所致","D",null,[],false,"本題考點：二氧化碳滅火設備全區放射之「動作噴發」（誤放射）成因辨識——誤放射源自探測器誤動作連動啟動，與藥劑設計量、換氣裝置停止的法定程序無涉。\n【正解理由】依《各類場所消防安全設備設置標準》第 91 條，啟動裝置分手動與自動，第一項第二款明定「自動啟動裝置與火警探測器感應連動啟動」；因此凡使探測器誤動作者，都可能連動放射。而設計藥劑量係依同標準第 83 條表列核算，換氣裝置停止則是第 85 條「全區或局部放射方式防護區域內之通風換氣裝置，應在滅火藥劑放射前停止運轉」所定的放射前程序，兩者影響的是放射後區域內的濃度與滯留，並非觸發動作噴發的因素，故選 D。\n【逐項排除】\n(A) 電銲施工高溫使定溫式、差動式等感熱型探測器誤動作，經第 91 條第一項第二款之連動即可能誤放射，與動作噴發有關。\n(B) 電銲產生的煙使偵煙式探測器誤動作，同樣經自動啟動裝置連動放射，有關。\n(C) 電銲電弧的電磁效應使偵煙式探測器誤發信號，仍屬探測器誤動作一類，經連動即誤放射，有關。\n(D) 藥劑量核算屬第 83 條、放射前停止通風換氣屬第 85 條，均不會使設備自行啟動放射，為與動作噴發無關者。\n【記憶點】誤放射要看啟動路徑：第 91 條自動啟動與火警探測器連動，凡使探測器誤動作者皆為成因；第 83 條藥劑量與第 85 條放射前停止換氣，講的是放射本身的規定。","二氧化碳全區放射的危險性來自兩件事同時成立：藥劑以稀釋氧氣滅火，而防護區劃又必須密閉。設置標準第 82 條把放射方式分三款——全區放射方式須以不燃材料建造之牆、柱、樓地板或天花板等區劃間隔，且開口部設有自動關閉裝置，但能有效補充開口部洩漏量者得免設；移動放射方式則要求皮管接頭至防護對象任一部分之水平距離在十五公尺以下。第 85 條要求防護區域內之通風換氣裝置應在滅火藥劑放射前停止運轉，用意在維持設計濃度，卻也使誤放射時區域內無法換氣。\n藥劑量與放射時間可整組記。第 83 條第一款全區放射方式的表列，電信機械室、總機室為每立方公尺 1.2 公斤、開口部每平方公尺追加 10 公斤；其他場所依防護區域容積分為五十立方公尺未滿 1.0、五十以上一百五十未滿 0.9、一百五十以上一千五百未滿 0.8、一千五百以上 0.75 公斤，開口部追加量均為每平方公尺 5 公斤。第 84 條第二款定放射壓力：常溫儲存之高壓式為每平方公分十四公斤以上或 1.4MPa 以上，儲存於攝氏零下十八度以下之低壓式為每平方公分九公斤以上或 0.9MPa 以上；第三款定放射時間為電信機械室、總機室 3.5 分、其他場所 1 分，第五款局部放射方式應於三十秒內放射完畢。\n真正的人身安全設計集中在第 91 條：手動啟動裝置須設於能看清區域內部且操作後能容易退避之防護區域外、每一防護區域或防護對象裝設一套、操作部設在距樓地板面高度零點八公尺以上一點五公尺以下、外殼漆紅色、操作開關或拉桿操作時同時發出警報音響並設透明塑膠製之有效保護裝置；自動、手動切換裝置須設於易於操作處所、設自動及手動表示燈，且切換必須以鑰匙或拉桿操作。第 88 條另規範以氣體啟動者之啟動用氣體容器（內容積一公升以上、二氧化碳重量零點六公斤以上、充填比一點五以上，且不得兼供防護區域之自動關閉裝置使用）。檢修基準各氣體系統章節的性能檢查因此要求先取下容器閥開放裝置、將自動手動切換裝置置於「手動」後再試驗；綜合檢查判定則含警報裝置確實鳴響、遲延裝置確實動作、開口部自動關閉裝置正常且換氣裝置確實停止、放射表示燈確實亮燈。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-alarm-evacuation-033","依消防安全設備測試報告書測試方法及判定要領，有關瓦斯漏氣火警自動警報設備檢知器之動作試驗，以加瓦斯試驗器將試驗瓦斯加進檢知器，測定至瓦斯漏氣表示為止之時間，下列何者正確？",33,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-alarm-evacuation-036","探測器安裝與天花板冷氣出風口應保持適當之距離，與火警探測器認可基準之下列何者有關？",36,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-alarm-evacuation-032","某場所進行緊急廣播設備綜合檢查，使用噪音計（A 特性）量測揚聲器之音壓位準，在距 L 級揚聲器 1 公尺處，音壓位準值應在 X dB 以上；又挑高空間採性能設計之指向型揚聲器，於廣播區域內任一位置距樓地板面 Y 公尺處，音壓位準值應在 Z dB 以上。則 X、Y、Z 值，下列何者正確？",32,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-alarm-evacuation-037","醫院之排煙設備進行綜合檢查時，緊急電源之檢查應如何落實？",37,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-alarm-evacuation-031","設置 119 火災通報裝置的主要功能為何？",31,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-alarm-evacuation-038","依消防安全設備及必要檢修項目檢修基準，針對緩降機之下降空間進行外觀檢查時，確認有無妨礙下降之物品，及有無確保下降必要之空間，下列何者錯誤？",38,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-034",113,"依據消防安全設備及必要檢修項目檢修基準，針對 119 火災通報裝置本體實施性能檢查，其中以火警自動警報設備連動啟動將一區段蓄積語音送出後，再操作手動啟動裝置，應能再送出蓄積語音，此為下列何種檢查項目？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-034",112,"有關無線電通信輔助設備無線電接頭之外觀試驗，依據無線電通信輔助設備測試報告書判定要領，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-034",110,"依消防安全設備及必要檢修項目檢修基準，救助袋進行開口部外觀檢查時，開口部面積之限制，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-034",109,"有關排煙設備綜合檢查之判定方法與注意事項，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-034",108,"依各類場所消防安全設備設置標準之規定，下列何種避難器具的開口面積應為高 60 公分以上，寬 60 公分以上？",1785129963704]