[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-029":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-警報與避難系統消防安全設備概要-029","fire-111-1-alarm-evacuation-029",111,1,29,"緩降機為顧及使用之安全，裝置時應考慮之位置下列何者為佳？",{"A":16,"B":17,"C":18,"D":19},"設置於安全梯內窗口","設置於電梯排煙室窗口","設置於屋頂平台女兒牆","設置於樓梯反方向走廊端窗口","D",null,[],false,"本題考點：緩降機設置位置的選擇原則，依《消防安全設備測試報告書測試方法及判定要領》避難器具外觀試驗之判定要領認定。\n【正解理由】該判定要領對避難器具設置場所訂明：關於樓梯、出入口或其他相關避難設施之關連，應在適當之位置；應設置在容易接近，且無礙避難器具使用之空間，有安全構造之開口部；至樓地板面或其他著地點之下降空間，應無妨礙避難之障礙物；著地點附近應確保無礙著地之下降空地空間，且通向安全的道路或廣場。設在樓梯反方向之走廊端窗口，使避難動線與樓梯分屬不同方向，接近性、開口部與著地空間均易確保，最符合上述關連性要求，故選 D。\n【逐項排除】\n(A) 安全梯內窗口與樓梯屬同一條避難動線，未形成不同方向之避難手段，與「關於樓梯之關連應在適當位置」不合。\n(B) 電梯排煙室之窗戶依《各類場所消防安全設備設置標準》第 189 條第一款須位於天花板高度二分之一以上範圍內且平時關閉並設手動開關裝置，屬排煙用有效開口，不是避難器具之開口部。\n(C) 屋頂平臺女兒牆非居室之開口部，第 25 條並規定避難器具設於除十一層以上樓層及避難層外之各樓層；第 158 條第二款所稱屋頂平臺搭配的是避難橋。\n(D) 樓梯反方向之走廊端窗口與樓梯避難方向分離，且接近性、開口部與著地空間均易確保，為本題應選者。\n【記憶點】避難器具位置四要件：與樓梯之關連適當、容易接近、開口部安全、下降空間與下降空地無礙。","避難器具的位置，法規是用「關連性」而非單一距離值在管。《消防安全設備測試報告書測試方法及判定要領》避難器具之外觀試驗把設置場所等拆成種類、開口部大小（長×寬×腰高）、設置狀況、有無障礙物、下降空間確保、著地點狀況等查核欄，判定要領要求與樓梯、出入口或其他相關避難設施之關連應在適當之位置，並確保容易接近、有安全構造之開口部、與其他樓層之避難器具相互無妨礙、下降空間無障礙物、著地點附近有下降空地且通向安全的道路或廣場。把緩降機放在樓梯反方向的走廊端，正是讓兩條避難動線分開，避免同一路徑被火煙封閉時失去替代手段。\n《消防安全設備及必要檢修項目檢修基準》避難器具之外觀檢查把同一原則量化：設置地點應無因設置後之改裝被變更為個人房間或倉庫等而不容易接近，設置之居室其出入口應無加鎖，應無放置妨礙接近之物品；操作面積內除輕量而容易移動之物品外，不得放置會妨礙之大型椅子、桌子、書架；開口部應無加設固定板、木條，由地板面至開口部下端之高度應在一五○公分以下，開口部太高可能形成避難上之障礙時應設有固定式或半固定式之踏台；下降空間有電線時應距離一點二公尺以上。這幾項正好解釋為什麼女兒牆、排煙室高窗、梯間窗口都不是好位置——腰高、下降空間或接近性至少有一項過不了。\n數值面可對照《各類場所消防安全設備設置標準》：第 25 條規定建築物除十一層以上樓層及避難層外，各樓層應選設滑臺、避難梯、避難橋、救助袋、緩降機、避難繩索、滑杆或經中央主管機關認可具同等性能之避難器具；第 163 條定操作面積（緩降機零點五平方公尺以上，不含避難器具所佔面積，但邊長應為六十公分以上）；第 164 條定下降空間（緩降機為以器具中心半徑零點五公尺圓柱形範圍內，突出物在十公分以內且無避難障礙者，或超過十公分時能採取不損繩索措施者，該突出物得在下降空間範圍內）。第 158 條的減設規定則從反面提示避難方向的重要性：主要構造為防火構造且設有二座以上不同避難方向之安全梯者（剪刀式樓梯視為一座），其應設數量欄所列收容人員一百人、二百人及三百人得分別以加倍數值重新核算。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-alarm-evacuation-028","非局限型探測器為有效偵知火災，下列何者為設置標準規定裝設於小空間內至少應有的長度或元件數量？",28,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-alarm-evacuation-030","依各類場所消防安全設備設置標準規定，有關緊急廣播設備敘述下列何者錯誤？",30,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-alarm-evacuation-027","以絕緣電阻計量測 220 V 電源之火警受信總機回路絕緣電阻，下列何者正確？",27,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-alarm-evacuation-031","設置 119 火災通報裝置的主要功能為何？",31,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-alarm-evacuation-026","因疫情消毒需求，某醫院院區之一間獨立庫房存放 75%酒精之備用囤放量遽增，下列何因素使該庫房須設置火警自動警報設備移報至火警總機？",26,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-alarm-evacuation-032","某場所進行緊急廣播設備綜合檢查，使用噪音計（A 特性）量測揚聲器之音壓位準，在距 L 級揚聲器 1 公尺處，音壓位準值應在 X dB 以上；又挑高空間採性能設計之指向型揚聲器，於廣播區域內任一位置距樓地板面 Y 公尺處，音壓位準值應在 Z dB 以上。則 X、Y、Z 值，下列何者正確？",32,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-029",113,"有關特別安全梯與緊急昇降機間排煙室兼用時，其排煙設備採機械排煙、自然進風方式，則排煙機之排煙量應在 X m3\u002Fsec 以上；直接面向戶外之進風口開口面積應在 Y m2 以上則 X、Y 各為多少？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-029",112,"某建築物總樓地板面積在 5 萬平方公尺以上其主要避難路徑的地方，該出口標示燈及避難方向指示燈之緊急電源容量應在 60 分鐘以上，下列場所何者不是主要避難路徑？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-029",110,"有關瓦斯漏氣檢知器之設置，當瓦斯對空氣之比重小於 1 時，應設於距瓦斯燃燒器具水平距離 A 公尺以內；當瓦斯對空氣之比重大於 1 時，應設於距瓦斯燃燒器具水平距離 B 公尺以內，其中 A 及 B 分別為：",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-029",109,"有關瓦斯漏氣火警自動警報設備檢知器外觀檢查選取之檢查數量，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-029",108,"消防安全設備測試報告書測試方法及判定要領中規定，火警自動警報設備外觀試驗，其定溫式感知線型探測器之判定要領中，下列何者正確？",1785129963667]