[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-028":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-警報與避難系統消防安全設備概要-028","fire-111-1-alarm-evacuation-028",111,1,28,"非局限型探測器為有效偵知火災，下列何者為設置標準規定裝設於小空間內至少應有的長度或元件數量？",{"A":16,"B":17,"C":18,"D":19},"定溫式線型探測器至少應 20 公尺長","差動式分布型空氣管至少應 15 公尺長","差動式分布型熱電偶式至少 4 個熱電偶","差動式分布型熱半導體式至少 4 個熱半導體","C",null,[],false,"本題考點：差動式分布型與線型探測器的最小長度或元件數量，全部規定在《各類場所消防安全設備設置標準》第 121 條。\n【正解理由】第 121 條第二款第二目之表明訂，差動式分布型熱電偶式在防火構造建築物之探測區域樓地板面積八十八平方公尺以下、其他建築物七十二平方公尺以下者，應設探測器數為「至少四個」；面積超過時再按每增加二十二平方公尺（其他建築物十八平方公尺，均包括未滿）增設一個。小空間即落在表列的下限級距，故至少四個熱電偶，故選 C。\n【逐項排除】\n(A) 二十公尺是空氣管式的規定（同條第一款第一目：每一探測區域內之空氣管長度，露出部分在二十公尺以上），不是定溫式線型探測器的規定。\n(B) 空氣管式的露出長度下限為二十公尺以上，並非十五公尺。\n(C) 熱電偶式在表列面積下限即應設至少四個，與條文相符，為本題應選者。\n(D) 熱半導體式依同條第三款第二目為每一有效探測範圍至少設置二個，裝置面高度未滿八公尺時至少設置一個，都不是四個。\n【記憶點】空氣管露出二十公尺、熱電偶至少四個、熱半導體二個（未滿八公尺一個）。","第 121 條把差動式分布型分成三型，各有一組數值。空氣管式：每一探測區域內之空氣管長度露出部分在二十公尺以上；裝接於一個檢出器之空氣管長度在一百公尺以下；空氣管裝置在裝置面下方三十公分範圍內；裝置在自裝置面任一邊起一點五公尺以內之位置，其間距在防火構造建築物九公尺以下、其他建築物六公尺以下，但依探測區域規模及形狀能有效探測火災發生者不在此限。熱電偶式：熱電偶應裝置在裝置面下方三十公分範圍內；應設探測器數依表，防火構造建築物八十八平方公尺以下至少四個、超過者每增加二十二平方公尺增設一個，其他建築物七十二平方公尺以下至少四個、超過者每增加十八平方公尺增設一個；裝接於一個檢出器之熱電偶數在二十個以下。熱半導體式：探測器下端裝設在裝置面下方三十公分範圍內；各探測區域依探測器種類及裝置面高度，在每一有效探測範圍至少設置二個，但裝置面高度未滿八公尺時至少設置一個。\n這些設置數值在《消防安全設備測試報告書測試方法及判定要領》火警自動警報設備之外觀試驗有對應的驗收判定：空氣管應設在裝置面下方零點三公尺以內、距離裝置面各邊一點五公尺以內；相互間隔在防火構造九公尺以下（其他結構六公尺以下）；任一感知區域之空氣管露出長度應在二十公尺以上；任一接續於檢出部之空氣管長應在一百公尺以下；檢出部不得前後傾斜五度以上；直線部分以零點三五公尺以內間隔固定，接續或彎曲部分以五公分以內間隔固定；彎曲半徑應在五公厘以上。定溫式感知線型的判定則為感知線設在裝置面下方零點三公尺以內、設於周圍溫度低於標稱動作溫度二十度以上之場所、直線部分每零點五公尺（有下垂之虞時零點三五公尺）以內間隔固定、彎曲部分每零點一公尺以內固定、彎曲半徑零點零五公尺以上——通篇沒有最小長度規定，這正是選項(A)的破口。\n性能面另有接點水高試驗（空氣管式，接點閉合時之水位應在各檢出部所標示之值的範圍內）與動作試驗、回路合成阻抗試驗（熱電偶式、熱半導體式，均以各檢出部標示值為準），可與設置數值分開記。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-alarm-evacuation-027","以絕緣電阻計量測 220 V 電源之火警受信總機回路絕緣電阻，下列何者正確？",27,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-alarm-evacuation-029","緩降機為顧及使用之安全，裝置時應考慮之位置下列何者為佳？",29,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-alarm-evacuation-026","因疫情消毒需求，某醫院院區之一間獨立庫房存放 75%酒精之備用囤放量遽增，下列何因素使該庫房須設置火警自動警報設備移報至火警總機？",26,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-alarm-evacuation-030","依各類場所消防安全設備設置標準規定，有關緊急廣播設備敘述下列何者錯誤？",30,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-alarm-evacuation-025","依 119 火災通報裝置認可基準規定，當常用電源停電，持續 X 分鐘待機狀態後，需保有 Y 分鐘以上可進行火災通報之電源容量；通話功能及回鈴應答試驗於 Z 秒內未收到回鈴信號，應可重複進行撥號。則 X、Y、Z 為何？",25,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-alarm-evacuation-031","設置 119 火災通報裝置的主要功能為何？",31,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-028",113,"依消防安全設備及必要檢修項目檢修基準，針對防災監控系統綜合操作裝置進行性能檢查，有關消防搶救支援性能項目，於 LCD 螢幕應能針對下列各樓層平面圖，以簡明易操作之方式切換其表示。所敘述之樓層平面圖下列何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-028",112,"某一地下街其地下層設有瓦斯漏氣火警自動警報設備，其某一回路之檢知器數量有 40 個，依消防安全設備及必要檢修項目檢修基準使用「加瓦斯試驗器」進行加瓦斯測試，檢知器選取檢查數量為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-028",110,"瓦斯漏氣火警自動警報設備進行性能檢查時，檢知區域警報裝置其音壓在距 1 公尺處應為多少分貝以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-028",109,"有關緊急廣播設備啟動裝置與緊急電話設置場所之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-028",108,"有關緊急廣播設備之敘述，下列何者錯誤？",1785129963662]