[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-027":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-警報與避難系統消防安全設備概要-027","fire-111-1-alarm-evacuation-027",111,1,27,"以絕緣電阻計量測 220 V 電源之火警受信總機回路絕緣電阻，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"探測器回路之共線與分區線間應在 0.2 MΩ 以上","探測器回路分區線與大地間應在 0.1 MΩ 以上","電源回路線與大地間應在 0.1 MΩ 以上","電源回路之兩線之間應在 0.1 MΩ 以上","B",null,[],false,"本題考點：火警自動警報設備配線的絕緣電阻判定值，電源回路與探測器回路分開規定，見《各類場所消防安全設備設置標準》第 127 條第四款。\n【正解理由】第 127 條第四款前段規定，電源回路導線間及導線與大地間之絕緣電阻值，以直流二百五十伏特額定之絕緣電阻計測定，對地電壓在一百五十伏特以下者在零點一ＭΩ以上，對地電壓超過一百五十伏特者在零點二ＭΩ以上；後段則規定探測器回路導線間及導線與大地間，每一火警分區在零點一ＭΩ以上，不隨對地電壓提高。故選 B。\n【逐項排除】\n(A) 探測器回路之共線與分區線間即條文所稱導線間，該款後段訂的是每一火警分區零點一ＭΩ以上，不是零點二ＭΩ。\n(B) 探測器回路分區線與大地間，正是後段「導線與大地間，每一火警分區在零點一ＭΩ以上」之情形，為本題應選者。\n(C) 二二○伏特電源之對地電壓已超過一百五十伏特（《消防安全設備及必要檢修項目檢修基準》配線章表 27-3 註明非接地式電路之對地電壓指電線間之電壓），電源回路與大地間應在零點二ＭΩ以上。\n(D) 電源回路之兩線之間同屬前段所稱導線間，二二○伏特下亦應在零點二ＭΩ以上。\n【記憶點】探測器回路一律零點一ＭΩ；電源回路以對地電壓一百五十伏特為界，分零點一與零點二ＭΩ。","絕緣電阻題有三個變數要一起看：測定電壓、回路種類、對地電壓。《各類場所消防安全設備設置標準》第 127 條第四款的火警自動警報設備一律以直流二百五十伏特額定之絕緣電阻計測定；電源回路依對地電壓分級（一百五十伏特以下零點一ＭΩ以上、超過一百五十伏特零點二ＭΩ以上），探測器回路則不分級，每一火警分區零點一ＭΩ以上。第 139 條第一款的緊急廣播設備寫法與電源回路相同（直流二百五十伏特額定、零點一與零點二ＭΩ）；第 144 條第一款的瓦斯漏氣火警自動警報設備數值相同但測定電壓改為直流五百伏特額定，檢知器回路每一警報分區零點一ＭΩ以上。三條並列，差異只在測定電壓與回路名稱。\n「對地電壓」的定義出自《消防安全設備及必要檢修項目檢修基準》配線章性能檢查的表 27-3：在接地式電路指電線和大地間之電壓，在非接地式電路指電線間之電壓。該表把判定值整理為五列：三百伏特以下且對地電壓一百五十伏特以下者零點一ＭΩ、三百伏特以下其他情形零點二ＭΩ、超過三百伏特者零點四ＭΩ、三千伏特高壓電路三ＭΩ、六千伏特高壓電路六ＭΩ。同章並規定低壓回路開關器或斷路器之每一分岐回路以五百伏特以下之絕緣電阻計測量，高壓回路以一千、二千或五千伏特之絕緣電阻計測量，且量測前應切斷電源並以電壓計等確認已無充電之情形。\n第 127 條其餘各款也是同一題組的常客：常開式之探測器信號回路配線採串接式並加設終端電阻，以便藉由火警受信總機作回路斷線自動檢出；Ｐ型受信總機採用數個分區共用一公用線方式配線時，該公用線供應之分區數不得超過七個；Ｐ型受信總機之探測器回路電阻在五十Ω以下；埋設於屋外或有浸水之虞之配線，採用電纜並穿於金屬管或塑膠導線管，與電力線保持三十公分以上之間距。把「七個分區、五十Ω、三十公分」與絕緣電阻值一起背，一條就守住好幾個考點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-alarm-evacuation-026","因疫情消毒需求，某醫院院區之一間獨立庫房存放 75%酒精之備用囤放量遽增，下列何因素使該庫房須設置火警自動警報設備移報至火警總機？",26,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-alarm-evacuation-028","非局限型探測器為有效偵知火災，下列何者為設置標準規定裝設於小空間內至少應有的長度或元件數量？",28,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-alarm-evacuation-025","依 119 火災通報裝置認可基準規定，當常用電源停電，持續 X 分鐘待機狀態後，需保有 Y 分鐘以上可進行火災通報之電源容量；通話功能及回鈴應答試驗於 Z 秒內未收到回鈴信號，應可重複進行撥號。則 X、Y、Z 為何？",25,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-alarm-evacuation-029","緩降機為顧及使用之安全，裝置時應考慮之位置下列何者為佳？",29,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-alarm-evacuation-024","某工廠室內製程區其燃氣設備使用之燃氣以丙烷（C3H8）為主成分，現場欲設置可燃氣漏氣警報設備時，檢知器應如何安裝？",24,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-alarm-evacuation-030","依各類場所消防安全設備設置標準規定，有關緊急廣播設備敘述下列何者錯誤？",30,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-027",113,"有關出口標示燈、避難方向指示燈與緊急照明燈之緊急電源規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-027",112,"依各類場所消防安全設備設置標準之規定，有關緊急電源插座之設置場所與位置規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-027",110,"依緊急廣播設備之揚聲器設置規定，廣播區域超過 100 平方公尺時，距揚聲器 1 公尺處所測得之音壓應為多少分貝以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-027",109,"有關緩降機支固器具之裝置，下列何者與各類場所消防安全設備設置標準之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-027",108,"依各類場所消防安全設備設置標準第 112 條，有關火警自動警報設備之火警分區劃定規定，下列何者錯誤？",1785129963647]