[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-025":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-警報與避難系統消防安全設備概要-025","fire-111-1-alarm-evacuation-025",111,1,25,"依 119 火災通報裝置認可基準規定，當常用電源停電，持續 X 分鐘待機狀態後，需保有 Y 分鐘以上可進行火災通報之電源容量；通話功能及回鈴應答試驗於 Z 秒內未收到回鈴信號，應可重複進行撥號。則 X、Y、Z 為何？",{"A":16,"B":17,"C":18,"D":19},"X=30、Y=20、Z=10","X=30、Y=10、Z=20","X=60、Y=20、Z=10","X=60、Y=10、Z=20","D",null,[],false,"本題考點：一一九火災通報裝置的預備電源容量與回撥應答開放時間，屬認可基準所定的判定值。\n【正解理由】《消防安全設備測試報告書測試方法及判定要領》一一九火災通報裝置之外觀試驗，就預備電源設置狀況判定「其容量能使其持續 60 分鐘待機狀態後，保有 10 分鐘以上可進行火災通報」；同一章性能試驗之通話機能則載明，一區段蓄積語音送出並完成通話後「自動開放 20 秒時間的電話回路」，再由試驗機消防機關側送出回撥信號確認應答狀態，其修正說明並敘明係配合一百零九年四月十七日修正發布之一一九火災通報裝置認可基準，將「回鈴」修正為「回撥」、「10 秒」修正為「20 秒」。故 X＝60、Y＝10、Z＝20，故選 D。\n【逐項排除】\n(A) X＝30 與待機六十分鐘不符，Y＝20 亦非十分鐘，Z＝10 是一百零九年修正前的舊值。\n(B) Y＝10、Z＝20 雖與判定要領相符，但 X＝30 分鐘待機不足六十分鐘。\n(C) X＝60 正確，惟 Y＝20 應為十分鐘、Z＝10 為修正前舊值。\n(D) 待機六十分鐘、通報十分鐘、回撥開放二十秒三值全部相符，為本題應選者。\n【記憶點】待機 60 分鐘、通報 10 分鐘、回撥開放 20 秒。","電源判定值之所以是「待機長、通報短」，來自兩種狀態耗電差異：待機只需維持電源監視與電話回路連接，六十分鐘是停電後仍須保持可用的最低要求；一旦啟動，要驅動撥號、送出蓄積語音並維持通話，耗電大增，故另訂十分鐘以上的通報能力。判定要領同時要求預備電源種類為密閉型蓄電池，配線設置無鬆脫，蓄電池無變形、損壞、腐蝕等現象。\n通報試驗的判定內容值得整組記：蓄積語音應在發出撥號信號並偵測應答後自動送出；訊息由通報信號音及自動語音組成；手動啟動部分之通報信號音為單音，連續三音並重複兩次，連動啟動部分為單音，連續兩音並重複兩次；自動語音訊息應包含火災表示（連動啟動者為火警自動警報設備啟動）、建築物所在地址、建築物名稱、聯絡電話及結尾語「確認後請掛斷回撥」；每一區段之蓄積語音應在三十秒內，且為電子迴路所合成之女聲發音。通話試驗除回撥開放二十秒外，還包含消防機關側不應答時應繼續送出蓄積語音，以及切換狀況（以手動操作使蓄積語音通報停止後，應可與消防機關側電話機相互通話）。\n設置面回到《各類場所消防安全設備設置標準》：第 9 條把一一九火災通報裝置列為警報設備第五款；第 22-1 條定應設場所；第 145-1 條定六款設置規定，含應具手動及自動啟動功能、應設於值日室等經常有人之處所（設有防災中心時應設於該中心）、設置遠端啟動裝置時應設有可與設置場所通話之設備、手動啟動裝置之操作開關距樓地板面零點八公尺以上一點五公尺以下、裝置附近應設置送、收話器並與其他內線電話明確區分、應避免斜裝置並採取有效防震措施。\n本題點名的認可基準原文未在候選之列，但判定要領的修正說明已敘明其修正係配合該認可基準，三個數值因而可以對得起來。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-alarm-evacuation-024","某工廠室內製程區其燃氣設備使用之燃氣以丙烷（C3H8）為主成分，現場欲設置可燃氣漏氣警報設備時，檢知器應如何安裝？",24,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-alarm-evacuation-026","因疫情消毒需求，某醫院院區之一間獨立庫房存放 75%酒精之備用囤放量遽增，下列何因素使該庫房須設置火警自動警報設備移報至火警總機？",26,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-alarm-evacuation-023","火焰探測器偵測火災為偵測火場的何種參數？",23,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-alarm-evacuation-027","以絕緣電阻計量測 220 V 電源之火警受信總機回路絕緣電阻，下列何者正確？",27,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-alarm-evacuation-022","避難器具安裝完成實施性能試驗，針對支固器具進行荷重試驗，緩降機至少應載重 X kg 以上；救助袋應載重 Y kg 以上，試問 X、Y 分別為何？",22,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-alarm-evacuation-028","非局限型探測器為有效偵知火災，下列何者為設置標準規定裝設於小空間內至少應有的長度或元件數量？",28,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-025",113,"依各類場所消防安全設備設置標準之規定，有關緊急電源插座之設置規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-025",112,"有關發電機設備設置場所之外觀試驗，依據緊急電源（發電機設備）測試報告書判定要領，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-025",110,"下列有關火警受信總機之裝置規定，何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-025",109,"有關火焰式探測器之設置，下列何者與各類場所消防安全設備設置標準之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-025",108,"依各類場所消防安全設備設置標準規定，火警自動警報設備之火警發信機（非定址式）與 P 型受信總機，其配線為何種配線？",1785129963619]