[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-023":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-警報與避難系統消防安全設備概要-023","fire-111-1-alarm-evacuation-023",111,1,23,"火焰探測器偵測火災為偵測火場的何種參數？",{"A":16,"B":17,"C":18,"D":19},"天花板噴射流之熱能","天花板噴射流之煙流","燃燒物之輻射能","環境影像清晰度","C",null,[],false,"本題考點：火焰式探測器的感測物理量——它捕捉的是燃燒火焰所輻射的紫外線或紅外線，不是熱氣流的溫升，也不是煙濃度。\n【正解理由】《消防安全設備及必要檢修項目檢修基準》火警自動警報設備之性能檢查於蓄積性能項目載明，火焰式探測器係「以火焰式探測器用動作試驗器之紅外線或紫外線照射」使其動作，可知其感測對象為燃燒物火焰輻射出的電磁波能量；《各類場所消防安全設備設置標準》第 124 條也要求火焰式探測器設在無日光照射之處（設有遮光功能可避免探測障礙者不在此限），正因日光同屬輻射光源會干擾感測。故選 C。\n【逐項排除】\n(A) 天花板噴射流之熱能是差動式、補償式、定溫式等感熱式探測器的感測對象，火焰式不靠溫升動作。\n(B) 煙流屬離子式、光電式偵煙探測器的感測對象，第 115 條第三款即專就偵煙式訂排氣口或回風口周圍一公尺範圍內之裝置規定。\n(C) 燃燒物之輻射能與上述紅外線、紫外線動作試驗方式相符，為本題應選者。\n(D) 環境影像清晰度屬影像判斷技術，第 114 條裝置場所高度表所列探測器種類並無此類。\n【記憶點】感熱看溫度、偵煙看煙濃度、火焰式看紫外線與紅外線輻射。","火焰式與感熱式、偵煙式的分野在感測的物理量：它以紫外線或紅外線感測器直接捕捉火焰輻射，不必等熱氣流或煙擴散到裝置面。這個特性反映在《各類場所消防安全設備設置標準》第 114 條的裝置場所高度表：未滿四公尺、四公尺以上未滿八公尺、八公尺以上未滿十五公尺、十五公尺以上未滿二十公尺四個級距，火焰式都列在可選種類中，而差動式局限型只出現在前兩個級距。第 116 條第一款更明定「探測器除火焰式外，裝置面高度超過二十公尺者」得免設探測器，換言之裝置面超過二十公尺時，法規承認可用的仍是火焰式。\n設置面依第 124 條四款：裝設於天花板、樓板或牆壁；距樓地板面一點二公尺範圍內之空間應在探測器標稱監視距離範圍內；不得設在有障礙物妨礙探測火災發生處；設在無日光照射之處，但設有遮光功能可避免探測障礙者不在此限。第 115 條第一款則指出，天花板上設有出風口時，火焰式、差動式分布型及光電式分離型探測器不受「應距離該出風口一點五公尺以上」之限制，理由同樣是它們不依賴局部熱氣流或煙的到達。\n不得設置之處所見第 117 條第二項，共三款：第一款為同條第一項第二款至第四款或第六款至第八款所列處所（散發腐蝕性氣體、廚房及其他平時煙會滯留、顯著高溫、煙會大量流入、會結露、設有用火設備其火焰外露之場所）；第二款為水蒸氣會大量滯留之處所；第三款為其他對探測器機能會造成障礙之處所，這一款是概括規定，不可漏列。\n檢修面，《消防安全設備及必要檢修項目檢修基準》火警自動警報設備之外觀檢查要求火焰探測器之監視空間或監視距離應適當正常、應無日光直射等影響性能之顧慮；性能檢查之蓄積性能則以動作試驗器之紅外線或紫外線照射，判定應在三十秒加上蓄積式中繼器或受信總機設定蓄積時間之合計時間（最大二十秒）內動作。與偵煙式局限型的三十秒、六十秒、九十秒（一種至三種）並列記憶，較不易混淆。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-alarm-evacuation-022","避難器具安裝完成實施性能試驗，針對支固器具進行荷重試驗，緩降機至少應載重 X kg 以上；救助袋應載重 Y kg 以上，試問 X、Y 分別為何？",22,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-alarm-evacuation-024","某工廠室內製程區其燃氣設備使用之燃氣以丙烷（C3H8）為主成分，現場欲設置可燃氣漏氣警報設備時，檢知器應如何安裝？",24,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-alarm-evacuation-021","依各類場所消防安全設備設置標準規定，下列有關出口標示燈及避難方向指示燈之敘述，何者正確？",21,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-alarm-evacuation-025","依 119 火災通報裝置認可基準規定，當常用電源停電，持續 X 分鐘待機狀態後，需保有 Y 分鐘以上可進行火災通報之電源容量；通話功能及回鈴應答試驗於 Z 秒內未收到回鈴信號，應可重複進行撥號。則 X、Y、Z 為何？",25,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-alarm-evacuation-020","依消防安全設備及必要檢修項目檢修基準，實施緊急照明設備性能檢查，檢查數量下列之敘述何者正確？",20,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-alarm-evacuation-026","因疫情消毒需求，某醫院院區之一間獨立庫房存放 75%酒精之備用囤放量遽增，下列何因素使該庫房須設置火警自動警報設備移報至火警總機？",26,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-023",113,"依各類場所消防安全設備設置標準規定，下列何場所或建築物未達應設置火警自動警報設備條件？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-023",112,"有關特別安全梯或緊急昇降機間排煙室之排煙設備，當設置直接面向戶外之窗戶時，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-023",110,"依各類場所消防安全設備設置標準，火警探測器之探測區域係指裝置面之四周以淨高 X 公分以上之樑或類似構造體區劃包圍者。偵煙式探測器，其裝置面之四周淨高應為 Y 公分，其中 X 及 Y 分別為：",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-023",109,"有關地下建築物總樓地板面積在幾平方公尺以上應設置無線電通信輔助設備，下列何者與各類場所消防安全設備設置標準之規定相同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-023",108,"偵煙式局限型探測器裝設於防火構造建築物天花板高度 8 公尺之裝置面時，若樓地板面積為 500 平方公尺，且其天花板中間有一下垂 40 公分的樑隔開，試問至少須設置幾個偵煙式局限型 1 種探測器？",1785129963597]