[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-017":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-警報與避難系統消防安全設備概要-017","fire-111-1-alarm-evacuation-017",111,1,17,"下列何者非各類場所消防安全設備設置標準明定應設置防災監控系統綜合操作裝置之場所？",{"A":16,"B":17,"C":18,"D":19},"總樓地板面積在 3 萬平方公尺以上之建築物","總樓地板面積在 5 萬平方公尺以上之建築物","總樓地板面積在 1000 平方公尺以上之地下建築物","高度在 50 公尺或樓層在 16 層以上之建築物","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 30-1 條應設置防災監控系統綜合操作裝置之場所，四款門檻要逐字記牢。\n【正解理由】第 30-1 條規定應設置防災監控系統綜合操作裝置者為：一、高層建築物；二、總樓地板面積在五萬平方公尺以上之建築物；三、總樓地板面積在一千平方公尺以上之地下建築物；四、其他經中央主管機關公告之供公眾使用之場所。條文對一般建築物的面積門檻只有五萬平方公尺一個，三萬平方公尺並非該條所定門檻，故選 A。\n【逐項排除】\n(A) 總樓地板面積三萬平方公尺以上之建築物不在第 30-1 條四款之內，該條對建築物所定的是五萬平方公尺以上，為本題應選者。\n(B) 對應第 30-1 條第二款總樓地板面積在五萬平方公尺以上之建築物。\n(C) 對應第 30-1 條第三款總樓地板面積在一千平方公尺以上之地下建築物。\n(D) 高度在五十公尺或樓層在十六層以上者，即建築技術規則所稱之高層建築物，對應第 30-1 條第一款。\n【記憶點】第 30-1 條四款記成「高層建築物、建築物五萬平方公尺、地下建築物一千平方公尺、公告場所」；選項出現三萬平方公尺就與該條不符。","防災監控系統綜合操作裝置在第 11 條被列為消防搶救上之必要設備第六款，與連結送水管、消防專用蓄水池、排煙設備（緊急昇降機間、特別安全梯間排煙設備、室內排煙設備）、緊急電源插座、無線電通信輔助設備同屬一類。應設場所寫在第 30-1 條的四款，其中第一款是與用途無關的高層建築物，第二款以建築物總樓地板面積五萬平方公尺為界，第三款以地下建築物總樓地板面積一千平方公尺為界，第四款保留給中央主管機關公告之供公眾使用場所。\n設置處所與功能規定則在第 192-1 條：應設置於防災中心、中央管理室或值日室等經常有人之處所，並監控或操作九項消防安全設備——火警自動警報設備之受信總機、瓦斯漏氣火警自動警報設備之受信總機、緊急廣播設備之擴大機及操作裝置、連結送水管之加壓送水裝置及與其送水口處之通話連絡、緊急發電機、常開式防火門之偵煙型探測器、室內消防栓與自動撒水、泡沫及水霧等滅火設備之加壓送水裝置、乾粉與惰性氣體及鹵化烴等滅火設備、排煙設備。同條第二項並明定其緊急電源準用第三十八條規定，且供電容量應供其有效動作二小時以上。九項清單是常考點，可記成「兩台受信總機、廣播、連結送水管、發電機、常開式防火門、水系加壓送水裝置、氣體與乾粉、排煙」。\n「地下建築物總樓地板面積一千平方公尺以上」是這一章反覆出現的門檻，可以整組並列記憶：第 21 條第三款瓦斯漏氣火警自動警報設備、第 26 條第二款連結送水管、第 29 條第二款緊急電源插座、第 30 條第二款無線電通信輔助設備、第 30-1 條第三款防災監控系統綜合操作裝置，用的都是同一個數字。第 30 條另有兩個門檻：樓高在一百公尺以上建築物之地下層，以及地下層在四層以上且地下層樓地板面積合計在三千平方公尺以上建築物之地下層。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-alarm-evacuation-016","依各類場所消防安全設備設置標準規定，下列何種場所得免設排煙設備？",16,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-alarm-evacuation-018","局限型偵煙探測器光電式的偵測原理若設計為散亂光式，其對火場中何種信號較不敏感？",18,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-alarm-evacuation-015","依各類場所消防安全設備設置標準規定，為確保排煙設備動作時，不受空調等通風換氣裝置影響排煙效果，下列何項排煙設備元件動作時應連動停止空氣調節及通風設備運轉？",15,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-alarm-evacuation-019","有關緊急照明燈的緊急電源及配線之規定，下列敘述何者正確？",19,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-alarm-evacuation-014","依各類場所消防安全設備設置標準規定，供失智照顧型長期照顧服務機構、老人福利機構（安養機構）、產後護理機構等避難弱勢場所之樓層，符合規定者得免設避難器具，下列何者非免設之必要條件？",14,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-alarm-evacuation-020","依消防安全設備及必要檢修項目檢修基準，實施緊急照明設備性能檢查，檢查數量下列之敘述何者正確？",20,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-017",113,"電子工業廠房潔淨區，因潔淨環境及構造特殊，特訂定潔淨區消防安全設備設置要點，對於潔淨室設置吸氣式偵煙探測系統時，依據此設置要點，下列說明何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-017",112,"有一地下建築物總樓地板面積超過 1 千平方公尺，依據各類場所消防安全設備設置標準，下列何者非依法應設之消防安全設備？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-017",110,"下列那二種避難器具在性能檢查時，均須對其下降空地附近之支持或固定裝置進行判定？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-017",109,"一一九火災通報裝置之設置規定，下列敘述何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-017",108,"某商場有一樓層，以防煙垂壁區劃為四區，各區劃樓地板面積分別為 100 平方公尺、300 平方公尺、250 平方公尺、200 平方公尺，採用機械排煙方式，四區劃僅設置 1 台排煙風機，試問該排煙風機之排煙量每分鐘不得小於多少立方公尺？",1785129963514]