[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-007":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-警報與避難系統消防安全設備概要-007","fire-111-1-alarm-evacuation-007",111,1,7,"依消防安全設備及必要檢修項目檢修基準，差動式分布型空氣管式之火災動作或動作持續試驗，不動作或測定之時間超過範圍時，應即確認空氣管與旋塞台之連接部位是否栓緊，且應進行何種試驗？",{"A":16,"B":17,"C":18,"D":19},"回路導通試驗及洩漏試驗","流通試驗及回路導通試驗","接點水高試驗及洩漏試驗","流通試驗及接點水高試驗","D",null,[],false,"本題考點：差動式分布型（空氣管式）四項性能試驗的分工，動作異常時應續行哪兩項。\n【正解理由】《消防安全設備測試報告書測試方法及判定要領》第九章火警自動警報設備乙、性能試驗列出空氣管式之測試項目為火災動作試驗、動作持續試驗、流通試驗與接點水高試驗四項：流通試驗以流體壓力表水位升至約 100 毫米後打開送氣口，測上升水位降至 1\u002F2 之時間並依空氣管長度查表判定，水位不停止即表示空氣管有外漏之虞；接點水高試驗則測接點閉合時之水位是否在各檢出部所標示之值的範圍內。題幹之火災動作、動作持續試驗結果異常，原因不外空氣管阻塞漏氣或檢出部接點水高不當，故續行者為此二項，故選 D。\n【逐項排除】\n(A) 回路導通試驗及洩漏試驗：回路導通（斷線）試驗是就受信總機各回路確認配線有無斷線；候選之測試項目亦無獨立之洩漏試驗，空氣管外漏是在流通試驗中發現。\n(B) 流通試驗及回路導通試驗：流通試驗正確，但回路導通試驗屬受信總機與中繼器之配線項目，不是空氣管式的續行項目。\n(C) 接點水高試驗及洩漏試驗：接點水高試驗正確，惟洩漏試驗非空氣管式所列之測試項目。\n(D) 流通試驗及接點水高試驗：分別驗證空氣管之通氣狀態與檢出部接點閉合水位，為本題應選者。\n【記憶點】空氣管動作不良先摸連接部位，再跑流通試驗查管路、接點水高試驗查檢出部。","差動式分布型（空氣管式）的原理是：空氣管受熱時管內空氣膨脹，壓力經檢出部的隔膜推動接點閉合而發訊；為避免緩慢溫升造成誤報，檢出部另設洩漏孔讓緩慢升壓洩掉。四項性能試驗正好對應這條路徑上的四個環節。火災動作試驗以測試幫浦接在檢出部之試驗孔，將試驗旋塞對合動作試驗位置，注入相當於探測器動作空氣壓之空氣量，測自該時點至接點閉合為止之時間；動作持續試驗測動作試驗中探測器開始動作之後至接點開放為止之時間，兩者都應在該檢出部所標示之範圍內。流通試驗把流體壓力表接在試驗孔或空氣管一端，注入空氣使水位上升至約 100 毫米後停止，再打開送氣口測上升水位降至 1\u002F2 之時間，依空氣管長度查表判定。接點水高試驗將流體壓力表及測試幫浦接在試驗孔或空氣管一端，試驗旋塞對合接點水高試驗位置，緩緩注入空氣測接點閉合時之水位。\n因此動作時間過長或不動作，可能是空氣管被壓扁、彎折或接續處漏氣，屬管路問題，由流通試驗判定；也可能是檢出部隔膜接點的間隙偏移，屬靈敏度問題，由接點水高試驗判定。反之接點水高偏低會使動作過快而誤報。這也說明為何要先確認空氣管與旋塞台之連接部位是否栓緊——鬆脫是最容易排除、也最常見的原因。\n設置端的配套規定在第 121 條第 1 款：每一探測區域內之空氣管長度，露出部分在二十公尺以上；裝接於一個檢出器之空氣管長度在一百公尺以下；空氣管裝置在裝置面下方三十公分範圍內；裝置在自裝置面任一邊起一點五公尺以內之位置，其間距在防火構造建築物九公尺以下、其他建築物六公尺以下。另依第 119 條，差動式分布型探測器之探測區域，其裝置面四周淨高應為六十公分以上。試驗數值與設置數值是兩套規定，答題時不可互相套用。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-alarm-evacuation-006","探測器依其工作原理，下列探測器何者具有搜集環境變異之功能，並採數位通訊方式傳回總機，再由總機根據歷史紀錄來決定是否作動？",6,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-alarm-evacuation-008","一場所設置定溫式局限型 1 種探測器（非再用型）共有 32 個，今進行動作試驗時，應抽取 X 個探測器以加熱試驗器加熱，測定至探測器動作時間為 Y 秒內合格，則 X、Y 為何？",8,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-alarm-evacuation-005","玻璃工場、熔接作業場所等設有用火設備，其火焰外露之場所，在選擇探測器時，下列何者較為適用？",5,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-alarm-evacuation-009","一非防火構造建築物，某層高度 5.2 公尺供辦公室使用，其探測區域為 310 平方公尺，若裝設補償式局限型 1 種探測器，最少設置數量應為多少個？",9,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-alarm-evacuation-004","某建築物火警自動警報設備之鳴動方式依規定採分區鳴動，在分區鳴動經多少分鐘內或受信總機再接受火災信號時，應立即全區鳴動？",4,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-alarm-evacuation-010","依各類場所消防安全設備設置標準規定，有關揚聲器在居室樓地板面積在 X 平方公尺以下，其它非居室部分樓地板面積在 Y 平方公尺以下，且該區域與相鄰接區域揚聲器之水平距離相距 Z 公尺以下時，得免設。則 X、Y、Z 值，下列何者正確？",10,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-007",113,"醫療機構中的 3 樓，經容納病床數量、從業員工與相關區域之樓地板面積等相關條件評估後，其收容人數為 550 人，該樓層在無減設、免設考量下，至少應設多少具避難器具？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-007",112,"有關揚聲器設置場所之外觀試驗判定要領，依據緊急廣播設備測試報告書，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-007",110,"下列何種火警探測器在認可作業中須進行粉塵試驗？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-007",109,"除火焰式探測器外，一般局限型探測器裝設時，依各類場所消防安全設備設置標準之規定，不得傾斜幾度以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-007",108,"有關無線電通信輔助設備設置規定，下列何者正確？",1785129963390]