[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-006":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-警報與避難系統消防安全設備概要-006","fire-111-1-alarm-evacuation-006",111,1,6,"探測器依其工作原理，下列探測器何者具有搜集環境變異之功能，並採數位通訊方式傳回總機，再由總機根據歷史紀錄來決定是否作動？",{"A":16,"B":17,"C":18,"D":19},"火焰式探測器","定址式感熱探測器","定址式偵煙探測器","類比定址式偵煙探測器","D",null,[],false,"本題考點：探測器依信號傳輸與判斷方式之分類，類比定址式的特徵是回傳連續量值、由受信總機判斷。\n【正解理由】類比定址式探測器除具識別位址外，會把所測得之煙濃度等環境量以類比值經數位通訊回傳受信總機，由總機比對歷次紀錄後決定是否判定為火災；《消防安全設備測試報告書測試方法及判定要領》第九章火警自動警報設備乙、性能試驗即把「離子化類比式局限型、光電類比式局限型」與一般離子式、光電式局限型分列為不同型式，動作判斷主體不同，故選 D。\n【逐項排除】\n(A) 火焰式探測器：感知火焰之紫外線或紅外線，依第 124 條裝設於天花板、樓板或牆壁，且距樓地板面一點二公尺範圍內之空間應在標稱監視距離內，動作判斷在探測器本身。\n(B) 定址式感熱探測器：只多了位址資訊供受信總機辨識個別位置，仍由本體達設定溫度條件自行發出動作信號。\n(C) 定址式偵煙探測器：同樣僅具位址功能，煙濃度達自身設定值即動作，不回傳連續量值供總機判斷。\n(D) 類比定址式偵煙探測器：回傳煙濃度類比值，由受信總機依歷史紀錄判斷是否作動，三項特徵全數符合，為本題應選者。\n【記憶點】定址式只回答「我在哪裡、我動作了」，類比定址式回答「我這裡的煙濃度是多少」，判斷權在受信總機。","探測器的分類軸有三條，常被混在一起考。第一條是感知對象：感熱式（差動式、定溫式、補償式、熱類比式）、偵煙式（離子式、光電式，各有局限型與分離型）、火焰式（紫外線式、紅外線式）。第二條是信號形式：一般型只送出動作與否的接點信號；定址式在同一回路上給每個探測器一組位址，受信總機能指出是哪一個探測器動作；類比式則送出連續量值，由受信總機依設定的多段閾值與歷次紀錄判斷。第三條是時間處理：蓄積式在感知後先累積一段時間才報警，用以抑制瞬間干擾造成的誤報。\n第 125 條可以看出受信總機端對這些型式的配套要求：第 1 項第 6 款規定裝置蓄積式探測器或中繼器之火警分區，該分區在受信總機不得有雙信號功能；第 7 款規定受信總機、中繼器及偵煙式探測器有設定蓄積時間時，其蓄積時間之合計每一火警分區在六十秒以下，使用其他探測器時在二十秒以下；第 9 款要求受信總機具有於接受火災信號後一定時間內或再接受火災信號時，強制地區警報音響裝置鳴動之功能。類比定址式把判斷權移到總機，正是這些總機端功能條款的延伸應用。\n《消防安全設備測試報告書測試方法及判定要領》第九章火警自動警報設備乙、性能試驗把離子式局限型、光電式局限型、離子化類比式局限型、光電類比式局限型並列於同一張動作時間表（第一種 30 秒、第二種 60 秒、第三種 90 秒；蓄積型另加標稱蓄積時間及 5 秒），光電式分離型與光電類比式分離型非蓄積型者則為 30 秒以內。可見類比式在法定體例中是獨立型式，不是廠商的行銷名詞。相關延伸考點還有第 119 條的探測區域界定（差動式分布型及偵煙式探測器，其裝置面四周淨高應為六十公分以上），以及第 117 條偵煙式局限型的禁設場所——類比定址式縱使判斷精細，仍受同一套適應性規定拘束。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-alarm-evacuation-005","玻璃工場、熔接作業場所等設有用火設備，其火焰外露之場所，在選擇探測器時，下列何者較為適用？",5,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-alarm-evacuation-007","依消防安全設備及必要檢修項目檢修基準，差動式分布型空氣管式之火災動作或動作持續試驗，不動作或測定之時間超過範圍時，應即確認空氣管與旋塞台之連接部位是否栓緊，且應進行何種試驗？",7,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-alarm-evacuation-004","某建築物火警自動警報設備之鳴動方式依規定採分區鳴動，在分區鳴動經多少分鐘內或受信總機再接受火災信號時，應立即全區鳴動？",4,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-alarm-evacuation-008","一場所設置定溫式局限型 1 種探測器（非再用型）共有 32 個，今進行動作試驗時，應抽取 X 個探測器以加熱試驗器加熱，測定至探測器動作時間為 Y 秒內合格，則 X、Y 為何？",8,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-alarm-evacuation-003","下列場所何者依規定應設置火警自動警報設備？",3,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-alarm-evacuation-009","一非防火構造建築物，某層高度 5.2 公尺供辦公室使用，其探測區域為 310 平方公尺，若裝設補償式局限型 1 種探測器，最少設置數量應為多少個？",9,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-006",113,"依據各類場所消防安全設備設置標準之規定，避難器具於開口部應保有必要開口面積，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-006",112,"有關室內排煙綜合試驗之排煙風量測試，依據排煙設備測試報告書判定要領，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-006",110,"緊急廣播設備在樓梯或斜坡通道以外之場所，其設置之揚聲器採性能設計時，在揚聲器標示上如加註下列那二種項目者，該廣播區域內任一點至揚聲器之水平距離方可不受到 10 公尺以下的限制？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-006",109,"差動式局限型探測器進行性能檢查時，使用加熱式試驗器加熱確認動作時間，加熱後到探測器動作應在多少時間以內？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-006",108,"探測器應依裝置場所高度選擇探測器種類裝設，下列何者錯誤？",1785129963386]