[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-005":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-警報與避難系統消防安全設備概要-005","fire-111-1-alarm-evacuation-005",111,1,5,"玻璃工場、熔接作業場所等設有用火設備，其火焰外露之場所，在選擇探測器時，下列何者較為適用？",{"A":16,"B":17,"C":18,"D":19},"差動式局限型 1 種","補償式局限型 1 種","定溫式局限型 1 種","離子式局限型 1 種","C",null,[],false,"本題考點：用火設備火焰外露場所之探測器適應性，關鍵在第 117 條的兩層禁設清單與定溫式的動作原理。\n【正解理由】《各類場所消防安全設備設置標準》第 117 條第 1 項第 8 款明定「設有用火設備其火焰外露之場所」不得設置偵煙式或熱煙複合式局限型探測器；同條第 2 項第 1 款又規定火焰式探測器不得設於前項第 8 款所列處所。可用者僅餘感熱式，而玻璃工場、熔接作業場所平時即有火焰造成之急遽溫升，須以達標稱動作溫度才動作之定溫式因應，故選 C。\n【逐項排除】\n(A) 差動式局限型 1 種：以一定時間內之溫度上升率動作，火焰外露會使溫升率頻繁超過設定值而誤報，非該類場所之適用型式。\n(B) 補償式局限型 1 種：兼具差動與定溫兩種性能，其差動部分同受火焰外露之溫升率影響，仍非該類場所之適用型式。\n(C) 定溫式局限型 1 種：僅在周圍溫度達標稱動作溫度時動作，不受溫升率干擾；《消防安全設備及必要檢修項目檢修基準》第十三章火警自動警報設備外觀檢查表 13-1 備考亦載明，有火災急速擴大顧慮之場所之定溫式探測器應儘可能使用特種且標稱動作溫度在 75℃ 以下者，為本題應選者。\n(D) 離子式局限型 1 種：屬偵煙式局限型，正落入第 117 條第 1 項第 8 款之禁設範圍。\n【記憶點】火焰外露先劃掉偵煙式與火焰式（第 117 條），剩下的感熱式再挑不吃溫升率的定溫式。","第 117 條是探測器適應性的核心條文，體例為兩層禁設清單加一張選設表。第 1 項列九款偵煙式或熱煙複合式局限型不得設置之處所：塵埃、粉末或水蒸氣會大量滯留、會散發腐蝕性氣體、廚房及其他平時煙會滯留、顯著高溫、排放廢氣會大量滯留、煙會大量流入、會結露、設有用火設備其火焰外露，以及其他對探測器機能會造成障礙之場所。第 2 項列火焰式不得設置之處所：前項第 2 款至第 4 款或第 6 款至第 8 款所列處所、水蒸氣會大量滯留之處所及其他造成機能障礙之處所。第 3 項再指示前二項所列場所依表選擇適當探測器。玻璃工場、熔接作業場所同時是顯著高溫與火焰外露場所，第 1 項第 4 款與第 8 款都命中。\n與之相鄰的是第 116 條的免設清單：探測器除火焰式外裝置面高度超過二十公尺者、外氣流通無法有效探測火災之場所、洗手間廁所或浴室、冷藏庫等設有能早期發現火災之溫度自動調整裝置者、主要構造為防火構造且開口設有具一小時以上防火時效防火門之金庫、室內游泳池之水面或溜冰場之冰面上方、不燃性石材或金屬等加工場未儲存或未處理可燃性物品處等。玻璃工場不在此列，且題幹場所設有用火設備，也不能援用第 7 款的不燃性材料加工場免設。\n選型還受第 114 條的裝置場所高度限制：未滿四公尺可選差動式局限型、差動式分布型、補償式局限型、定溫式、離子式局限型、光電式局限型、光電式分離型與火焰式；四公尺以上未滿八公尺者，定溫式限特種或一種。因此定溫式局限型一種在八公尺以下的場所都站得住。配套條件見第 120 條第 3 款：具有定溫式性能之探測器，應裝設在平時之最高周圍溫度比其標稱動作溫度低攝氏二十度以上處，具二種以上標稱動作溫度者，以最低標稱動作溫度為準——高溫場所選定溫式時，這一款是同時要過的關。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-alarm-evacuation-004","某建築物火警自動警報設備之鳴動方式依規定採分區鳴動，在分區鳴動經多少分鐘內或受信總機再接受火災信號時，應立即全區鳴動？",4,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-alarm-evacuation-006","探測器依其工作原理，下列探測器何者具有搜集環境變異之功能，並採數位通訊方式傳回總機，再由總機根據歷史紀錄來決定是否作動？",6,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-alarm-evacuation-003","下列場所何者依規定應設置火警自動警報設備？",3,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-alarm-evacuation-007","依消防安全設備及必要檢修項目檢修基準，差動式分布型空氣管式之火災動作或動作持續試驗，不動作或測定之時間超過範圍時，應即確認空氣管與旋塞台之連接部位是否栓緊，且應進行何種試驗？",7,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-alarm-evacuation-002","平時有人之公共危險物品製造、儲存或處理場所，若未達應設置火警自動警報設備之規定時，其儲存、處理公共危險物品數量達幾倍管制量以上，應設置手動報警設備或具同等功能之緊急通報裝置？",2,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-alarm-evacuation-008","一場所設置定溫式局限型 1 種探測器（非再用型）共有 32 個，今進行動作試驗時，應抽取 X 個探測器以加熱試驗器加熱，測定至探測器動作時間為 Y 秒內合格，則 X、Y 為何？",8,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-alarm-evacuation-005",113,"依據現行出口標示燈及避難方向指示燈認可基準，對於內置型引導燈具相關試驗等標準，何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-alarm-evacuation-005",112,"有關瓦斯漏氣檢知器一回路設置數量，依據瓦斯漏氣火警自動警報設備檢修基準之性能檢查，有關撰取檢查數量，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-005",110,"避難方向指示燈之認可作業中，其引導燈具不包括下列何種附加功能？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-005",109,"差動式局限型探測器係利用下列何構件，來防止設置場所因正常溫度變化而造成火災誤報？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-005",108,"瓦斯漏氣火警自動警報設備進行性能檢查，下列敘述何者正確？",1785129963381]