[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-004":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":51,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-警報與避難系統消防安全設備概要-004","fire-111-1-alarm-evacuation-004",111,1,4,"某建築物火警自動警報設備之鳴動方式依規定採分區鳴動，在分區鳴動經多少分鐘內或受信總機再接受火災信號時，應立即全區鳴動？",{"A":16,"B":17,"C":18,"D":19},"5 分鐘","10 分鐘","15 分鐘","20 分鐘","B",null,[],false,"本題考點：火警自動警報設備採分區鳴動時，轉為全區鳴動的時間門檻。\n【正解理由】十分鐘的法源是《各類場所消防安全設備設置標準》第 113 條第四款：「前三款之鳴動於十分鐘內或受信總機再接受火災信號時，應立即全區鳴動。」該款係一百十年六月二十五日修正公布、一百十一年七月一日施行，晚於本場考試日；考試當時有效之第 113 條僅一至三款，只定分區鳴動範圍而無分鐘數，官方即以該款之十分鐘命題。第 125 條第 1 項第 9 款的角色是要求受信總機「具有於接受火災信號後一定時間內或再接受火災信號時，強制地區警報音響裝置鳴動之功能」，該條未出現分鐘數，「一定時間」之具體數值由第 113 條第四款定之。故選 B。\n【逐項排除】\n(A) 5 分鐘：條文未定此值；第 125 條第 1 項第 7 款以秒計者為蓄積時間（每一火警分區合計六十秒以下），與全區鳴動時限無關。\n(B) 10 分鐘：即第 113 條第四款明定之時限，逾此或受信總機再接受火災信號即應全區鳴動，為本題應選者。\n(C) 15 分鐘：法無此門檻；第 128 條所定十分鐘係緊急電源蓄電池之有效動作時間，屬另一事項。\n(D) 20 分鐘：亦無此門檻；二十之數值見於第 125 條第 1 項第 7 款蓄積時間二十秒，單位為秒而非分。\n【記憶點】分區鳴動只是暫時限縮範圍，十分鐘一到或受信總機再收到火災信號，即應強制全區鳴動（第 113 條第四款）。","鳴動方式的法源分兩層看：第 113 條規範「分區鳴動的範圍與轉為全區鳴動的時限」，第 125 條第 1 項第 9 款規範「受信總機必須具備強制地區警報音響裝置鳴動的功能」。第 113 條的適用門檻是建築物在五樓以上且總樓地板面積在三千平方公尺以上，未達此門檻者本無分區鳴動可言；達門檻者按起火層限縮：起火層為地上二層以上時，限該樓層與其直上二層及其直下層鳴動；起火層為地面層時，限該樓層與其直上層及地下層各層鳴動；起火層為地下層時，限地面層及地下層各層鳴動。立法著眼於避免全棟同時鳴動造成樓梯間人流對撞，先讓受威脅最大的樓層優先避難。第四款所定「十分鐘內或受信總機再接受火災信號時應立即全區鳴動」，係一百十年六月二十五日修正公布、一百十一年七月一日施行，晚於本場考試日，故當年適用的第 113 條只有前三款；而第 125 條第 1 項第 9 款自始只寫「一定時間內」，未載分鐘數。\n延伸關係有三處。第 135 條規定緊急廣播設備與火警自動警報設備連動時，其火警音響之鳴動準用第 113 條，音響警報應以語音方式播放，緊急電源準用第 128 條。《消防安全設備及必要檢修項目檢修基準》第十四章緊急廣播設備之性能檢查，在揚聲器鳴動方式項下同樣以起火層為地上二層以上、地面層、地下層三種情形判定分區鳴動是否正常。《消防安全設備測試報告書測試方法及判定要領》第九章火警自動警報設備乙、性能試驗之鳴動方式試驗，則明定「一定時間以內及接受新的火災信號時，地區音響裝置應一齊鳴動」，與第 125 條第 1 項第 9 款相互對應——設置、檢修、驗收三個階段講的是同一件事。\n容易與本題混淆的是幾個同樣帶十的數值：第 128 條火警自動警報設備緊急電源蓄電池容量能有效動作十分鐘以上；第 145 條瓦斯漏氣火警自動警報設備緊急電源能使二回路有效動作十分鐘以上、其他回路監視十分鐘以上；第 133 條第 2 款第 4 目揚聲器水平距離十公尺以下。單位與規範對象各不相同，逐條連著條號記才不會互換。",true,[28,32,36,40,44,47],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-alarm-evacuation-003","下列場所何者依規定應設置火警自動警報設備？",3,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-alarm-evacuation-005","玻璃工場、熔接作業場所等設有用火設備，其火焰外露之場所，在選擇探測器時，下列何者較為適用？",5,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-alarm-evacuation-002","平時有人之公共危險物品製造、儲存或處理場所，若未達應設置火警自動警報設備之規定時，其儲存、處理公共危險物品數量達幾倍管制量以上，應設置手動報警設備或具同等功能之緊急通報裝置？",2,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-alarm-evacuation-006","探測器依其工作原理，下列探測器何者具有搜集環境變異之功能，並採數位通訊方式傳回總機，再由總機根據歷史紀錄來決定是否作動？",6,{"webId":45,"stem":46,"number":12,"year":11,"session":12},"fire-111-1-alarm-evacuation-001","依各類場所消防安全設備設置標準規定，公共危險物品室內儲存場所總樓地板面積在多少平方公尺以上者，應設置火警自動警報設備？",{"webId":48,"stem":49,"number":50,"year":11,"session":12},"fire-111-1-alarm-evacuation-007","依消防安全設備及必要檢修項目檢修基準，差動式分布型空氣管式之火災動作或動作持續試驗，不動作或測定之時間超過範圍時，應即確認空氣管與旋塞台之連接部位是否栓緊，且應進行何種試驗？",7,[52,56,60,64,68],{"webId":53,"year":54,"stem":55,"number":13},"fire-114-1-alarm-evacuation-004",114,"某電影院放映場所火警自動警報設備所使用之蓄積型偵煙探測器有 10 秒之蓄積時間，其所使用之中繼器有 10 秒之蓄積時間，則其受信總機之蓄積時間，最多可為多少秒？",{"webId":57,"year":58,"stem":59,"number":13},"fire-113-1-alarm-evacuation-004",113,"工業廠房設置機械排煙設備，其中特別安全梯與緊急升降機間兼用排煙室，該區域排煙閘門大小為 6 m2，並連接排煙管道時，不考慮溫度影響之因素，請問排煙風速（m\u002Fs）應達多少才能符合其法令規定？",{"webId":61,"year":62,"stem":63,"number":13},"fire-112-1-alarm-evacuation-004",112,"依據一一九火災通報裝置檢修基準之性能檢查，下列何者非預備電源檢查方法之項目？",{"webId":65,"year":66,"stem":67,"number":13},"fire-110-1-alarm-evacuation-004",110,"有一棟總樓地板面積 4,000 平方公尺的七層辦公建築物，當起火層為地上第二層時，下列有關其火警自動警報設備分區鳴動方式的敘述，何者正確？",{"webId":69,"year":70,"stem":71,"number":13},"fire-109-1-alarm-evacuation-004",109,"某火警受信總機設有 15 回路，進行回路能否同時動作測試時，應不要復舊使任意幾回路進行測試？",1785129963372]