[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-water-chemical-032":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-水與化學系統消防安全設備概要-032","fire-110-1-water-chemical-032",110,1,32,"公共危險物品等場所消防設計及消防安全設備，有關設置冷卻撒水設備規定，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"撒水噴孔符合 CNS、12855 之規定","撒水量按槽壁總防護面積每平方公尺每分鐘 2 公升以上計算之，其管徑依水力計算配置","水源容量在最大一座儲槽連續放水 1 小時之水量以上","撒水噴孔孔徑在 6 毫米以上","B",null,[],false,"本題考點：公共危險物品儲槽之冷卻撒水設備，撒水噴孔所引國家標準、孔徑、撒水量與水源容量四組法定數值。\n【正解理由】依《各類場所消防安全設備設置標準》第二百十六條第三款，「撒水量按槽壁總防護面積每平方公尺每分鐘二公升以上計算之，其管徑依水力計算配置」，與本選項敘述逐字相符，故選 B。\n【逐項排除】\n(A) 錯誤：同條第一款所引國家標準為 CNS 一二八五四，即 CNS 12854，並非 12855；第 229 條可燃性高壓氣體場所之冷卻撒水設備採配管穿孔方式者，所引亦為 CNS 12854。\n(B) 正確：撒水量按槽壁總防護面積每平方公尺每分鐘二公升以上計算、管徑依水力計算配置，即第 216 條第三款本文，為本題應選者。\n(C) 錯誤：同條第五款為「水源容量在最大一座儲槽連續放水四小時之水量以上」，選項寫成 1 小時，與條文所定時間不符。\n(D) 錯誤：同條第一款規定撒水噴孔「孔徑在四毫米以上」，選項寫 6 毫米，與條文不符。\n【記憶點】第 216 條儲槽冷卻撒水記四個值：CNS 12854、孔徑 4 毫米以上、撒水量每平方公尺每分鐘 2 公升以上、水源 4 小時。","第 216 條的適用要件寫在本文首句：以室內、室外儲槽儲存閃火點在攝氏七十度以下之第四類公共危險物品之顯著滅火困難場所，除設置固定式泡沫滅火設備外，並依該條設置冷卻撒水設備。也就是冷卻撒水在此是「加設」而非替代，命題常在此設陷阱。\n全條九款可分三組。硬體組：第一款撒水噴孔符合 CNS 12854 之規定，孔徑在四毫米以上；第二款撒水管設於槽壁頂部，撒水噴頭之配置數量依其裝設之放水角度及撒水量核算，儲槽設有風樑或補強環等阻礙水路徑者，於其下方增設撒水管及撒水噴孔。水量組：第三款撒水量按槽壁總防護面積每平方公尺每分鐘二公升以上計算，管徑依水力計算配置；第四款加壓送水裝置為專用，幫浦出水量在前款撒水量乘以所防護之面積以上；第五款水源容量在最大一座儲槽連續放水四小時之水量以上。操作組：第六款選擇閥（未設選擇閥者為開關閥）設於防液堤外，操作位置距地面零點八公尺以上一點五公尺以下；第七款設手動啟動裝置及遠隔啟動裝置，但送水區域距加壓送水裝置在三百公尺以內者得免設遠隔啟動裝置；第八款加壓送水裝置啟動後五分鐘以內能有效撒水，且距撒水區域在五百公尺以下，設有保壓措施者不在此限；第九款連接緊急電源，其供電容量應在連續放水時間以上。\n同為冷卻撒水設備，另有一套適用不同場所的規定：第 229 條就可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽，定撒水量為防護面積每平方公尺每分鐘五公升以上，惟以厚度二十五毫米以上之岩棉或同等以上防火性能之隔熱材被覆，外側再以厚度零點三五毫米以上符合 CNS 1244 之鋅鐵板等材料被覆者，得將撒水量減半；水源容量為加壓送水裝置連續撒水三十分鐘之水量以上，構造及手動啟動裝置準用第 216 條。兩條分屬不同場所層級，數值各自適用。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-water-chemical-031","公共危險物品等場所消防設計及消防安全設備，室外消防栓設備採用鑄鐵管配管時，使用符合 CNS 832 規定之壓力管路鑄鐵管或具同等以上強度者，其標稱壓力在每平方公分多少公斤以上？",31,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-water-chemical-033","依消防安全設備及必要檢修項目檢修基準，滅火器設置間距規定，下列何者錯誤？",33,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-water-chemical-030","公共危險物品等場所消防設計及消防安全設備，其他滅火困難場所，應設置第幾種滅火設備？",30,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-water-chemical-034","依消防安全設備及必要檢修項目檢修基準，乾粉加壓式滅火器性能檢查之檢查抽樣頻率，應幾年實施一次性能檢查？",34,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-water-chemical-029","公共危險物品等場所消防設計及消防安全設備，設置第五種滅火設備者，公共危險物品每達管制量之幾倍（含未滿）應有一滅火效能值？",29,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-water-chemical-035","依消防安全設備及必要檢修項目檢修基準，製造日期超過 10 年或無法辨識製造日期之何種滅火器，非經水壓測試合格，不得再行更換及充填藥劑，應予報廢？",35,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-032",113,"某電信機房使用二氧化碳滅火系統，其配管規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-032",112,"依各類場所消防安全設備設置標準規定，下列何者應設置消防專用蓄水池？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-032",111,"二氧化碳滅火設備屬於公共危險物品等場所的那一類滅火設備？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-032",109,"二氧化碳滅火設備採用移動放射方式時，每一具噴射瞄子所需滅火藥劑量在多少公斤以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-032",108,"依法令規定下列場所何者應設置滅火器？",1785129972509]