[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-water-chemical-026":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-水與化學系統消防安全設備概要-026","fire-110-1-water-chemical-026",110,1,26,"固定式泡沫滅火設備之泡沫放出口，若採用高發泡放出口，其泡沫膨脹比應選擇下列何者設置之？",{"A":16,"B":17,"C":18,"D":19},"膨脹比 20 以下","膨脹比 20 以上 1000 以下","膨脹比 80 以上 1000 以下","膨脹比 1000 以上","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 70 條，固定式泡沫滅火設備之泡沫放出口如何依膨脹比選擇設置。\n【正解理由】依《各類場所消防安全設備設置標準》第 70 條之表，膨脹比二十以下者為低發泡，應設泡沫噴頭或泡水噴頭；膨脹比八十以上一千以下者為高發泡，應設高發泡放出口。題目既指定採用高發泡放出口，其膨脹比即為八十以上一千以下，故選 C。\n【逐項排除】\n(A) 錯誤。膨脹比二十以下屬同表的低發泡，對應的放出口種類是泡沫噴頭或泡水噴頭，不是高發泡放出口。\n(B) 錯誤。膨脹比二十以上一千以下並非表列任何一格；表把區間切成二十以下與八十以上一千以下兩段，二十至八十之間並未列入。\n(C) 正確。與第 70 條表「膨脹比八十以上一千以下（高發泡）對應高發泡放出口」該列逐字相符。\n(D) 錯誤。膨脹比一千以上已逾表列高發泡區間的上限一千，該表未就此區間規定放出口種類。\n【記憶點】第 70 條只有兩格：二十以下配泡沫噴頭或泡水噴頭，八十以上一千以下配高發泡放出口。","膨脹比的定義寫在第 70 條第 2 項：指泡沫發泡體積與發泡所需泡沫水溶液體積之比值。同樣一份泡沫水溶液，發泡倍數越高，泡沫體積越大、含水量越低，滅火機制也隨之改變，低發泡偏重覆蓋與冷卻，高發泡則以充填防護空間、窒息並阻隔輻射熱為主，條文因此用膨脹比把放出口種類切成兩段。\n第 70 條認定型式後，水源容量回到第 76 條。使用泡沫頭時，依第 72 條核算之最低放射量，在最大一個泡沫放射區域能繼續放射二十分鐘以上。使用高發泡放出口時分兩種情形：全區放射時，以最大樓地板面積之防護區域依表核算，該表所列「冠泡體積每一立方公尺之泡沫水溶液量」為第一種零點零四立方公尺、第二種零點零一三立方公尺、第三種零點零零八立方公尺，防護區域開口部未設閉鎖裝置者，另加算開口洩漏泡沫水溶液量；局部放射時，依第 73 條核算之泡沫水溶液放射量，在樓地板面積最大區域能繼續放射二十分鐘以上。移動式泡沫滅火設備之水源容量，則為二具泡沫瞄子同時放水十五分鐘之水量以上。第 76 條第 2 項並要求：前項各款計算之水溶液量，應加算充滿配管所需之泡沫水溶液量，且應加算總泡沫水溶液量之百分之二十，這個加算百分之二十是計算題常漏的一步。\n放射方式另定於第 69 條：固定式須視防護對象之形狀、構造、數量及性質配置泡沫放出口，其設置數量、位置及放射量應能有效滅火；移動式則要求水帶接頭至防護對象任一點之水平距離在十五公尺以下。命題時常把第 69、70、76 條串成一組，先問放射方式，再問膨脹比與放出口種類，最後問水源容量，本題屬其中的第二段。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-water-chemical-025","自動撒水設備之水源容量規定，若使用側壁型或小區劃型撒水頭時，十層以下樓層在 X 個撒水頭、十一層以上樓層在 Y 個撒水頭繼續放水 20 分鐘之水量以上。X、Y 分別為何？",25,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-water-chemical-027","二氧化碳滅火設備之全區放射或局部放射方式防護區域，對放射之滅火藥劑之排放規定，下列何者錯誤？",27,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-water-chemical-024","需設置自動撒水設備之場所中，下列何者應設開放式？",24,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-water-chemical-028","消防專用蓄水池規定之有效水量，指蓄水池深度在基地地面下多少公尺範圍內之水量，但採機械方式引水時，不在此限？",28,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-water-chemical-023","下列場所何者可選擇第二種室內消防栓選擇設置之？",23,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-water-chemical-029","公共危險物品等場所消防設計及消防安全設備，設置第五種滅火設備者，公共危險物品每達管制量之幾倍（含未滿）應有一滅火效能值？",29,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-026",113,"設於外浮頂式儲槽之泡沫放出口為？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-026",112,"依據各類場所消防安全設備設置標準，有關撒水頭裝置之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-026",111,"壓力開關高程 0 m，屋頂水箱高程 33 m，最高處撒水頭高程 30 m，加壓送水裝置利用啟動用壓力開關連動啟動。當壓力開關小於何值時，加壓送水裝置即應啟動？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-026",109,"密閉式撒水頭之自動撒水設備末端查驗閥規定，下列何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-026",108,"依各類場所消防安全設備設置標準之規定，建築物高度超過 60 公尺者，連結送水管應採用濕式，其中繼幫浦設置規定之敘述何者錯誤？",1785129972464]