[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-water-chemical-017":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-水與化學系統消防安全設備概要-017","fire-110-1-water-chemical-017",110,1,17,"密閉乾式或預動式之流水檢知裝置二次側配管，為有效排水，支管每 10 公尺傾斜 A 公分，主管每 10 公尺傾斜 B 公分。下列 A，B 何者正確？",{"A":16,"B":17,"C":18,"D":19},"A=5；B= 3","A=4；B=4","A=4；B= 2","A=2；B= 4","C",null,[],false,"本題考點：密閉乾式或預動式自動撒水設備，流水檢知裝置二次側配管為有效排水所需之傾斜規定。\n【正解理由】依《各類場所消防安全設備設置標準》第 44 條第 2 款第 1 目，「密閉乾式或預動式之流水檢知裝置二次側配管，為有效排水」，應依規定裝置為「支管每十公尺傾斜四公分，主管每十公尺傾斜二公分」。題目之 A 指支管、B 指主管，故 A＝4、B＝2，故選 C。\n【逐項排除】\n(A) A＝5；B＝3：支管 5 公分、主管 3 公分均非該目所定之數值。\n(B) A＝4；B＝4：支管 4 公分與條文相符，但主管該目所定為二公分，非四公分。\n(C) A＝4；B＝2：與該目「支管每十公尺傾斜四公分，主管每十公尺傾斜二公分」逐字相符，為正解。\n(D) A＝2；B＝4：兩個數值雖都見於該目，但支管與主管對調，該目所定支管為每十公尺四公分、主管為每十公尺二公分。\n【記憶點】乾式、預動式二次側配管排水坡度記「支四主二」，兩者都以每十公尺為基準，別把支管與主管對調。","為什麼只有密閉乾式與預動式要求二次側配管傾斜？因為這兩種方式的流水檢知裝置二次側平時是空氣而非水：依《各類場所消防安全設備設置標準》第 43 條第 2 款，密閉乾式平時管內貯滿高壓空氣，撒水頭動作時先排空氣，繼而撒水；同條第 4 款，預動式平時管內貯滿低壓空氣，以感知裝置啟動流水檢知裝置，且撒水頭動作時即撒水。動作或試驗過後管內殘水若排不乾淨，會積水並腐蝕管內壁而影響下次動作，故第 44 條第 2 款除給定排水坡度外，第 1 款要求二次側配管施予鍍鋅等防腐蝕處理（一齊開放閥二次側配管亦同），第 2 款第 2 目要求於明顯易見處設排水閥並標明排水閥字樣；同條第 3 款另定立管連接屋頂水箱時，屋頂水箱之容量在一立方公尺以上；而本條開宗明義即載明，自動撒水設備之配管、配件及屋頂水箱，除準用第 32 條第 1 款、第 2 款規定外，始依本條各款設置，作答時勿把準用來源與本條自訂事項混為一談。\n同一設備的其他數值一併記住：第 55 條規定密閉乾式或預動式流水檢知裝置二次側之加壓空氣，其空氣壓縮機為專用，並能在三十分鐘內加壓達二次側配管之設定壓力值；二次側之減壓警報設於平時有人處；撒水頭動作後，流水檢知裝置應在一分鐘內使撒水頭放水；撒水頭使用向上型，但配管能採取有效措施者不在此限。\n檢修面的對應規定是《消防安全設備及必要檢修項目檢修基準》第四章自動撒水設備二、性能檢查（六）配管：關閉乾式或預動式一次側之制水閥後，打開二次側配管之排水閥，確認是否能適當排水；判定方法為「配管之二次側應無積水」。法規給坡度、檢修基準查積水，兩者是同一件事的兩端，常被合併命題。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-water-chemical-016","某觀光飯店餐廳的廚房面積 750 平方公尺，其使用火源處所設置滅火器核算之最低滅火效能值應為多少？",16,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-water-chemical-018","有關滅火器設置規定，下列何者錯誤？",18,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-water-chemical-015","公共危險物品儲槽設置補助泡沫消防栓之規定，下列敘述何者錯誤？",15,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-water-chemical-019","依各類場所消防安全設備設置標準，應設置室內消防栓設備之場所，下列規定何者正確？",19,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-water-chemical-014","高壓電器設備其電壓在 7000 伏特以下時，水霧噴頭及配管與高壓電器設備應保持多少公分之標準離開距離？",14,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-water-chemical-020","飛機修理廠、飛機庫樓地板面積在 200 平方公尺以上者，可就水霧、泡沫、乾粉、二氧化碳滅火設備等選擇下列何者設置之？",20,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-017",113,"有關冷卻撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-017",112,"有關室內消防栓之水平距離、瞄子放水壓力、消防栓及位置之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-017",111,"惰性氣體滅火設備進行綜合檢查時，採低壓式者進行放射試驗時，其放射試驗所需之藥劑量，為該放射區域所設滅火藥劑量之多少以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-017",109,"某爆竹煙火儲存場所設置室外消防栓設備共 8 具，進行設備檢修綜合檢查時，至少應選擇配管上最遠最高處多少數量之室外消防栓實施放水試驗？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-017",108,"依各類場所消防安全設備檢修及申報作業基準，有關室內消防栓設備之第一種消防栓水帶及瞄子檢查方法，製造年份超過 10 年或無法辨識製造年份之水帶，應將消防水帶兩端之快速接頭連接於耐水壓試驗機，施以 X kgf\u002Fcm2 以上水壓試驗 Y 分鐘合格，始得繼續使用。則 X+Y 為若干？",1785129972410]