[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-water-chemical-016":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-水與化學系統消防安全設備概要-016","fire-110-1-water-chemical-016",110,1,16,"某觀光飯店餐廳的廚房面積 750 平方公尺，其使用火源處所設置滅火器核算之最低滅火效能值應為多少？",{"A":16,"B":17,"C":18,"D":19},"3","6","24","30","D",null,[],false,"本題考點：滅火器最低滅火效能值之核算，廚房等大量使用火源之處所所適用之面積級距。\n【正解理由】依《各類場所消防安全設備設置標準》第 31 條第 1 款第 3 目，「鍋爐房、廚房等大量使用火源之處所，以樓地板面積每二十五平方公尺（含未滿）有一滅火效能值」。觀光飯店餐廳之廚房屬一般場所之使用火源處所，非第四編公共危險物品等場所，故適用本目而不適用第 199 條之核算方式；以 750 平方公尺按每 25 平方公尺一滅火效能值核算得 30，故選 D。\n【逐項排除】\n(A) 3：3 × 25 ＝ 75 平方公尺，僅相當於題目廚房面積的十分之一。\n(B) 6：6 × 25 ＝ 150 平方公尺，與題目所示之 750 平方公尺不符。\n(C) 24：24 × 25 ＝ 600 平方公尺，漏計其餘 150 平方公尺之樓地板面積。\n(D) 30：30 × 25 ＝ 750 平方公尺，與題目廚房面積相符，為正解。\n【演算步驟】核算式：最低滅火效能值＝樓地板面積 ÷ 每一滅火效能值對應面積（未滿一格者仍計一格）。代入：750 平方公尺 ÷ 25 平方公尺／效能值 ＝ 30 效能值。750 ÷ 25 為整數，無「含未滿」進位問題，結果為 30。\n【記憶點】鍋爐房、廚房這類大量使用火源處所是第 31 條最密的一格：每 25 平方公尺一個滅火效能值。","第 31 條第 1 款把最低滅火效能值的核算切成三層，作答時先定場所類別再選面積：供第 12 條第 1 款（甲類場所）及第 5 款（戊類場所）使用之場所，各層樓地板面積每一百平方公尺（含未滿）有一滅火效能值；供第 12 條第 2 款至第 4 款（乙、丙、丁類場所）使用之場所，每二百平方公尺（含未滿）有一滅火效能值；鍋爐房、廚房等大量使用火源之處所，每二十五平方公尺（含未滿）有一滅火效能值。觀光旅館飯店為第 12 條第 1 款第 3 目、餐廳為同款第 5 目，均屬甲類場所，故其一般部分依每一百平方公尺一格核算，廚房則另依第 3 目每二十五平方公尺一格核算，同一建築物內兩個層級分別計算。\n同條其餘各款是配套記憶點：電影片映演場所放映室及電氣設備使用之處所，每一百平方公尺（含未滿）另設一滅火器；設有滅火器之樓層，自樓面居室任一點至滅火器之步行距離在二十公尺以下；標識為紅底白字，每字應在二十平方公分以上；懸掛於牆上或放置滅火器箱中者，其上端與樓地板面之距離，十八公斤以上者在一公尺以下，未滿十八公斤者在一點五公尺以下。第 14 條並定應設滅火器之場所五款，其中第 5 款正是「設有鍋爐房、廚房等大量使用火源之各類場所」。\n公共危險物品等場所另有一套核算方式，並列以免互套：第 199 條第 1 款，製造或處理場所之建築物外牆為防火構造者，總樓地板面積每一百平方公尺（含未滿）有一滅火效能值，非防火構造者每五十平方公尺；第 2 款儲存場所之建築物，防火構造者每一百五十平方公尺、非防火構造者每七十五平方公尺；第 4 款公共危險物品每達管制量之十倍（含未滿）應有一滅火效能值。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-water-chemical-015","公共危險物品儲槽設置補助泡沫消防栓之規定，下列敘述何者錯誤？",15,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-water-chemical-017","密閉乾式或預動式之流水檢知裝置二次側配管，為有效排水，支管每 10 公尺傾斜 A 公分，主管每 10 公尺傾斜 B 公分。下列 A，B 何者正確？",17,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-water-chemical-014","高壓電器設備其電壓在 7000 伏特以下時，水霧噴頭及配管與高壓電器設備應保持多少公分之標準離開距離？",14,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-water-chemical-018","有關滅火器設置規定，下列何者錯誤？",18,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-water-chemical-013","使用主成分為碳酸氫鈉之移動放射方式乾粉滅火設備，每一具噴射瞄子之每分鐘藥劑放射量應為下列何者？",13,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-water-chemical-019","依各類場所消防安全設備設置標準，應設置室內消防栓設備之場所，下列規定何者正確？",19,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-016",113,"有關自動撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-016",112,"有關二氧化碳滅火設備構件之安全措施規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-016",111,"乾粉滅火設備進行性能檢查時，關於滅火藥劑量之敘述，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-016",109,"製造年份超過 10 年之室內消防栓水帶進行耐水壓試驗時，施以 7 kgf\u002Fcm²以上水壓試驗多久時間，始得視為合格可繼續使用？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-016",108,"依各類場所消防安全設備檢修及申報作業基準，公共危險物品等場所達顯著滅火困難者設置之第一種滅火設備之室內消防栓，其放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。則 X+Y 為若干？",1785129972406]