[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-water-chemical-014":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-水與化學系統消防安全設備概要-014","fire-110-1-water-chemical-014",110,1,14,"高壓電器設備其電壓在 7000 伏特以下時，水霧噴頭及配管與高壓電器設備應保持多少公分之標準離開距離？",{"A":16,"B":17,"C":18,"D":19},"25","50","150","250","A",null,[],false,"本題考點：水霧滅火設備之水霧噴頭及配管與高壓電器設備間應保持之離開距離，屬依電壓查表並須注意單位換算之題型。\n【正解理由】依《各類場所消防安全設備設置標準》第 66 條附表，離開距離依電壓分級，並分「最低」與「標準」兩欄；電壓 7 KV 以下者，最低離開距離 150 ㎜、標準離開距離 250 ㎜。題目問的是標準離開距離，250 ㎜ 換算為公分為 250 ÷ 10 ＝ 25 公分，故選 A。\n【逐項排除】\n(A) 25：即 250 ㎜，與第 66 條表中 7 KV 以下之標準離開距離相符，為正解。\n(B) 50：即 500 ㎜，為該表中電壓 30 KV 以下之標準離開距離，並非 7 KV 以下者。\n(C) 150：即 1500 ㎜，為該表中電壓 100 KV 以下之標準離開距離；若把 7 KV 以下「最低」欄之 150 ㎜ 直接讀成 150 公分，也會落入此選項。\n(D) 250：係把表上 250 ㎜ 的數字原樣改稱公分，單位換算漏做，與條文所定之 250 ㎜ 相差十倍。\n【記憶點】第 66 條表的單位是㎜不是㎝：7 KV 以下記「最低 150、標準 250」，答公分先除以 10。","第 66 條的表以電壓由低到高分十級，最低與標準離開距離（單位㎜）成對出現：7 KV 以下 150／250、10 KV 以下 200／300、20 KV 以下 300／400、30 KV 以下 400／500、60 KV 以下 700／1000、70 KV 以下 800／1100、100 KV 以下 1100／1500、140 KV 以下 1500／1900、200 KV 以下 2100／2600、345 KV 以下 2600／3300。分兩欄的意義在於同一電壓級距同時給出不得低於的最低值，與作為設置依據的標準值，作答時務必先確認題目問的是哪一欄。水霧滅火設備會有這段規定，是因為水霧雖以微細水滴降低導電性，仍非絕緣體，噴頭與配管過於接近帶電體會有閃絡之虞，故以電壓愈高、距離愈大的級距表處理。\n易混淆對照（兩者條號與規範事項各自獨立，不可互換）：《公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法》第 13 條第 1 項第 5 款、第 6 款規範的是「場所外牆與廠區外高架電線」之安全距離——與電壓超過三萬五千伏特之高架電線應在五公尺以上，與電壓超過七千伏特、三萬五千伏特以下之高架電線應在三公尺以上；該條同項另定與其他場所之距離分別為五十、三十、二十、十公尺以上，並於設有擋牆防護或具同等以上防護性能者得減半計算。那是六類物品製造場所及一般處理場所之安全距離，與本題噴頭、配管對電器設備之離開距離是兩件事。\n延伸考點：與電氣有關的另一組常考數值是絕緣電阻。《設置標準》第 127 條第 4 款規定火警自動警報設備電源回路導線間及導線與大地間，以直流二百五十伏特額定之絕緣電阻計測定，對地電壓一百五十伏特以下者在零點一ＭΩ以上、超過一百五十伏特者在零點二ＭΩ以上；探測器回路每一火警分區在零點一ＭΩ以上。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-water-chemical-013","使用主成分為碳酸氫鈉之移動放射方式乾粉滅火設備，每一具噴射瞄子之每分鐘藥劑放射量應為下列何者？",13,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-water-chemical-015","公共危險物品儲槽設置補助泡沫消防栓之規定，下列敘述何者錯誤？",15,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-water-chemical-012","進行乾粉滅火設備性能檢查時，對於滅火藥劑檢查注意事項，溫度及濕度超過多少以上時，應暫停檢查？",12,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-water-chemical-016","某觀光飯店餐廳的廚房面積 750 平方公尺，其使用火源處所設置滅火器核算之最低滅火效能值應為多少？",16,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-water-chemical-011","室內消防栓設備之加壓送水裝置，若採用壓力水箱方式，則其水箱內空氣不得小於水箱容積的幾分之幾？",11,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-water-chemical-017","密閉乾式或預動式之流水檢知裝置二次側配管，為有效排水，支管每 10 公尺傾斜 A 公分，主管每 10 公尺傾斜 B 公分。下列 A，B 何者正確？",17,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-014",113,"依據消防安全設備及必要檢修項目檢修基準，於檢查類似醫院之場所時，因切換成緊急電源可能會造成困擾時，得使用常用電源檢查，下列消防安全設備何者不適用此一規定？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-014",112,"有關二氧化碳滅火設備相關規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-014",111,"開放式自動撒水設備之自動啟動裝置，感知撒水頭應設在裝置面距樓地板面高度多少公尺以下，且能有效探測火災處？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-014",109,"測量室內消防栓瞄子直線放水之壓力時，應將壓力表之進水口，放置於瞄子前端多少距離處，讀取壓力表的指示值？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-014",108,"依各類場所消防安全設備設置標準之規定，加壓式乾粉滅火設備應設壓力調整裝置，可調整壓力至若干 MPa 以下？",1785129972393]