[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-water-chemical-011":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-水與化學系統消防安全設備概要-011","fire-110-1-water-chemical-011",110,1,11,"室內消防栓設備之加壓送水裝置，若採用壓力水箱方式，則其水箱內空氣不得小於水箱容積的幾分之幾？",{"A":16,"B":17,"C":18,"D":19},"1\u002F2","1\u002F3","1\u002F4","1\u002F5","B",null,[],false,"本題考點：室內消防栓設備之加壓送水裝置採壓力水箱方式時，水箱內空氣占水箱容積之比例下限。\n【正解理由】依《各類場所消防安全設備設置標準》第 37 條第 1 項第 2 款第 2 目，壓力水箱應符合「水箱內空氣占水箱容積之三分之一以上，壓力在使用建築物最遠處之消防栓維持規定放水水壓所需壓力以上。當水箱內壓力及液面減低時，能自動補充加壓。空氣壓縮機及加壓幫浦與緊急電源相連接」，條文所定之空氣占比下限即為三分之一，故選 B。\n【逐項排除】\n(A) 1\u002F2：該目所定為三分之一以上，並未以二分之一為下限，屬把法定比例記大之誘答。\n(B) 1\u002F3：與該目「水箱內空氣占水箱容積之三分之一以上」逐字相符，為正解。\n(C) 1\u002F4：空氣僅占容積四分之一，未達該目所定之三分之一，不符規定。\n(D) 1\u002F5：空氣僅占容積五分之一；壓力水箱係靠壓縮空氣推水，空氣量不足時放水中壓力隨液面下降而迅速衰減，該目因此設下三分之一之下限。\n【記憶點】壓力水箱靠壓縮空氣推水，「空氣占水箱容積三分之一以上」是硬下限。","第 37 條是室內消防栓設備加壓送水裝置的總條文，三種方式擇一設置，各有各的計算式：重力水箱者，必要落差＝消防水帶摩擦損失水頭＋配管摩擦損失水頭＋17（公尺），並應有水位計、排水管、溢水用排水管、補給水管及人孔；壓力水箱者，空氣占水箱容積三分之一以上，必要壓力＝消防水帶摩擦損失水頭＋配管摩擦損失水頭＋落差＋1.7（公斤／平方公分），並應有壓力表、水位計、排水管、補給水管、給氣管、空氣壓縮機及人孔；消防幫浦者，出水量第一種消防栓每支每分鐘一百五十公升、第二種每支每分鐘九十公升（超過二支以二支計算），幫浦全揚程＝消防水帶摩擦損失水頭＋配管摩擦損失水頭＋落差＋17（公尺）。式中的 17 公尺與 1.7 公斤／平方公分是同一件事的兩種單位表示，對應第 34 條所定瞄子放水壓力每平方公分一點七公斤以上。\n同樣是壓力水箱，各設備規定並列如下，條號與末項加壓值各自獨立：第 42 條室外消防栓設備，空氣占三分之一以上，必要壓力＝消防水帶摩擦損失水頭＋配管摩擦損失水頭＋落差＋2.5；第 58 條自動撒水設備，空氣占三分之一以上，必要壓力＝配管摩擦損失水頭＋落差＋1；第 221 條公共危險物品等場所之泡沫滅火設備，空氣占三分之一以上，必要壓力另加計泡沫放出口、泡沫瞄子或泡沫射水槍之放射壓力。三分之一這個比例在上開各條一致，變動的是末項數值。\n延伸考點：第 37 條第 2 項另定加壓送水裝置之共通要求——設在便於檢修且無受火災等災害損害之處所；使用消防幫浦者，以具一小時以上防火時效之牆壁、樓地板及防火門窗等防火設備區劃分隔；設自動或手動啟動裝置且停止僅限於手動操作，手動啟動裝置設於每一室內消防栓箱內，箱上方有紅色啟動表示燈；瞄子放水壓力超過每平方公分七公斤時應採取有效之減壓措施。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-water-chemical-010","實施泡沫噴頭外觀檢查，應進行之項目內容不包括下列那一項？",10,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-water-chemical-012","進行乾粉滅火設備性能檢查時，對於滅火藥劑檢查注意事項，溫度及濕度超過多少以上時，應暫停檢查？",12,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-water-chemical-009","依據密閉式撒水頭認可基準之規定，進行玻璃球之強度試驗時，標示溫度在多少以上者將採用油浴方式進行測試？",9,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-water-chemical-013","使用主成分為碳酸氫鈉之移動放射方式乾粉滅火設備，每一具噴射瞄子之每分鐘藥劑放射量應為下列何者？",13,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-water-chemical-008","消防搶救上之必要設備中，連結送水管之送水口設置，下列敘述何者正確？",8,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-water-chemical-014","高壓電器設備其電壓在 7000 伏特以下時，水霧噴頭及配管與高壓電器設備應保持多少公分之標準離開距離？",14,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-011",113,"室內消防栓進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-011",112,"建築物高度在 X 公尺以下時，其連結送水管得與室內消防栓共用立管，其管徑在 Y 毫米以上，支管管徑在 Z 毫米以上。其中 X、Y 與 Z 分別為多少？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-011",111,"依各類場所消防安全設備設置標準規定，消防專用蓄水池應設置於消防車能接近至多少公尺範圍內，易於抽取處？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-011",109,"乾粉滅火設備之緊急電源應為發電機設備或蓄電池設備，其容量應能使該設備有效動作多少時間以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-011",108,"二氧化碳滅火設備使用氣體啟動者，啟動用氣體容器之內容積應有 1 公升以上，其所儲存之二氧化碳重量在 0.6 公斤以上，且其充填比應在多少以上？",1785129972374]