[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-water-chemical-010":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-水與化學系統消防安全設備概要-010","fire-110-1-water-chemical-010",110,1,10,"實施泡沫噴頭外觀檢查，應進行之項目內容不包括下列那一項？",{"A":16,"B":17,"C":18,"D":19},"確認有無因隔間變更而未加設泡沫頭，造成未警戒之部分","以目視確認泡沫頭周圍有無妨礙泡沫分布之障礙","以目視確認外形有無變形、腐蝕、阻塞等","確認泡沫噴頭網孔大小及其發泡性能","D",null,[],false,"本題考點：泡沫噴頭之外觀檢查範圍，屬《檢修基準》泡沫滅火設備外觀檢查「泡沫放出口」一項，限於目視可判別之事項。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第七章泡沫滅火設備一、外觀檢查（九）泡沫放出口，其檢查方法僅列三目：外形（以目視確認有無變形、腐蝕、阻塞等，並確認有無被利用為支撐、吊架使用）、分布障礙（以目視確認泡沫頭周圍有無妨礙泡沫分布之障礙）、未警戒部分（確認有無因隔間變更而未加設泡沫頭，造成未警戒之部分）。網孔大小與發泡性能無從以目視判別，未列於該三目之內，故選 D。\n【逐項排除】\n(A) 與「未警戒部分」之檢查方法逐字相符，屬外觀檢查應進行之項目。\n(B) 與「分布障礙」之檢查方法逐字相符，屬外觀檢查應進行之項目。\n(C) 與「外形」之檢查方法逐字相符，屬外觀檢查應進行之項目。\n(D) 網孔大小屬放出口之構造規格，發泡性能屬藥劑與放出口之機能表現，二者非目視所能確認，該基準並未將之列入外觀檢查三目，為本題所問不包括者。\n【記憶點】泡沫放出口外觀檢查只有三目——外形、分布障礙、未警戒部分；凡要量測或實際放泡才知道的，都不是外觀檢查。","《消防安全設備及必要檢修項目檢修基準》把每種設備的檢修拆成外觀檢查、性能檢查與綜合檢查三層：外觀檢查以目視或簡易測定為主，確認設備是否仍在應有狀態；性能檢查要分解、操作或量測，確認個別機件之機能；綜合檢查則使設備實際動作，確認系統整體連動。網孔大小與發泡性能，性質上落在後兩層而非第一層，這正是命題者設計的分界線。\n值得一併記住的是，該基準對各種「噴頭類」的外觀檢查採同一套骨架，逐章比對即可看出規則形狀：第六章水霧滅火設備一、外觀檢查（八）水霧噴頭列外形、撒水分布障礙、未警戒部分；第四章自動撒水設備一、外觀檢查（四）撒水頭列外形、感熱及撒水分布障礙、未警戒部分；第五章水道連結型自動撒水設備（四）撒水頭同為外形、感熱及撒水分布障礙、未警戒部分；第二十五章冷卻撒水設備之冷卻撒水噴頭（噴孔）亦列外形、撒水分布障礙、未警戒部分。判定方法也同一形狀：應無洩漏、變形、損傷、顯著腐蝕、阻塞等，應無被利用為支撐、吊架使用，周圍應無妨礙分布之障礙物，並應無因隔間、垂壁、風管、棚架等之變更、增設而造成未警戒之部分。\n易混淆之處在「未警戒部分」與「分布障礙」：前者問的是該設而未設，也就是隔間變更後新增的空間沒有加設放出口；後者問的是設了卻被擋住，也就是周圍有障礙物妨礙泡沫流動或分布。該基準對高發泡放出口另有一句「以目視確認高發泡放出口周圍，有無妨礙泡沫流動之障礙」，用語由「分布」改為「流動」，也是考點。\n延伸考點：同章外觀檢查尚含泡沫原液儲存量、閥類、配管、加壓送水裝置等項目，命題方向多為「何者不屬外觀檢查」或「檢查方法與判定方法之配對」。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-water-chemical-009","依據密閉式撒水頭認可基準之規定，進行玻璃球之強度試驗時，標示溫度在多少以上者將採用油浴方式進行測試？",9,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-water-chemical-011","室內消防栓設備之加壓送水裝置，若採用壓力水箱方式，則其水箱內空氣不得小於水箱容積的幾分之幾？",11,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-water-chemical-008","消防搶救上之必要設備中，連結送水管之送水口設置，下列敘述何者正確？",8,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-water-chemical-012","進行乾粉滅火設備性能檢查時，對於滅火藥劑檢查注意事項，溫度及濕度超過多少以上時，應暫停檢查？",12,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-water-chemical-007","依密閉式撒水頭認可基準規定，其中之耐洩漏試驗，係將撒水頭施予多少之靜水壓力，保持 5 分鐘不得有漏水現象？",7,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-water-chemical-013","使用主成分為碳酸氫鈉之移動放射方式乾粉滅火設備，每一具噴射瞄子之每分鐘藥劑放射量應為下列何者？",13,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-010",113,"有關室內消防栓測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-010",112,"水霧滅火設備係利用特殊水霧噴頭，使水呈微粒霧狀及特定角度、形狀噴出，並均勻地覆蓋燃燒表面，達到滅火效果。下列何者非水霧滅火設備針對油類火災之滅火作用與原理？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-010",111,"樓地板面積 250 平方公尺之變壓器室，依各類場所消防安全設備設置標準規定，可選擇下列何種消防安全設備？①水霧 ②泡沫 ③二氧化碳 ④乾粉",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-010",109,"全區放射方式之二氧化碳滅火設備，應設置從啟動裝置動作至二氧化碳放出時間至少多久的遲延裝置？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-010",108,"有一電信機械室，設置二氧化碳滅火設備，採全區放射方式，其所核算之滅火藥劑量應於多少秒內全部放射完畢？",1785129972366]