[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-water-chemical-009":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-水與化學系統消防安全設備概要-009","fire-110-1-water-chemical-009",110,1,9,"依據密閉式撒水頭認可基準之規定，進行玻璃球之強度試驗時，標示溫度在多少以上者將採用油浴方式進行測試？",{"A":16,"B":17,"C":18,"D":19},"57 ℃","68 ℃","79 ℃","121 ℃","C",null,[],false,"本題考點：密閉式撒水頭玻璃球感熱元件之強度試驗，其加熱介質依標示溫度分流，達一定溫度以上者改採油浴。\n【正解理由】依《密閉式撒水頭認可基準》玻璃球強度試驗之規定，試驗時加熱浴槽之介質須視玻璃球標示溫度而定，標示溫度在七十九度以上者改以油浴方式加熱測試；本批候選條文未涵蓋該認可基準之原文，故僅能引至該基準玻璃球強度試驗之項目層級。四個選項中，79 ℃ 即為改採油浴之起算門檻，故選 C。\n【逐項排除】\n(A) 57 ℃：屬玻璃球撒水頭常見之低標示溫度值，未達改採油浴之起算溫度，其玻璃球強度試驗不以油浴為之。\n(B) 68 ℃：同為起算溫度以下之標示溫度，亦非該基準所定改採油浴之分界值。\n(C) 79 ℃：為該基準所定之分界溫度，標示溫度自此溫度起（含）之玻璃球，強度試驗採油浴方式進行，為正解。\n(D) 121 ℃：此值雖在分界溫度以上，但題目問的是起算門檻而非門檻以上的任一溫度；121 度另見《各類場所消防安全設備設置標準》第 48 條標示溫度分級表之級距端點，與本題之試驗介質無涉。\n【記憶點】玻璃球強度試驗按標示溫度分流，79 ℃ 是改採油浴的那條線，未達此線者不以油浴為之。","《密閉式撒水頭認可基準》屬中央主管機關公告之認可技術基準，體例為壹、貳、參之章節結構而無條號，引用時寫基準名稱與試驗項目即可；本批候選條文未涵蓋該基準原文，故上開門檻溫度僅引至試驗項目層級，把握度標為低。\n就學理而言，玻璃球型撒水頭係以封入液體受熱膨脹脹破玻璃球而動作，強度試驗須將玻璃球加熱至遠高於標示溫度之狀態並施予壓力，確認球體不致先行破裂；加熱介質之所以在某一標示溫度以上改用油，是因為水在常壓下約 100 ℃ 即沸騰，無法穩定提供更高且均勻之浴溫，油浴則可在較高溫域維持穩定。\n與標示溫度相關而在候選條文中查得到的規定有二，兩者分屬不同事項、數值各有出處，不可互相套用：其一為《各類場所消防安全設備設置標準》第 48 條，密閉式撒水頭應就裝置場所平時最高周圍溫度選擇標示溫度——最高周圍溫度三十九度未滿者，標示溫度七十五度未滿；三十九度以上六十四度未滿者，標示溫度七十五度以上一百二十一度未滿；六十四度以上一百零六度未滿者，標示溫度一百二十一度以上一百六十二度未滿；一百零六度以上者，標示溫度一百六十二度以上。其二為同標準第 52 條，開放式自動撒水設備之自動啟動裝置，感知撒水頭使用標示溫度在七十九度以下者，且每二十平方公尺設置一個，並設在裝置面距樓地板面高度五公尺以下。\n延伸考點：同標準第 56 條之末端查驗閥，管徑二十五毫米以上，接裝在各層放水壓力最低之最遠支管末端，一次側設壓力表、二次側設與撒水頭同等放水性能之限流孔，距地板面高度二點一公尺以下——這是密閉式撒水頭相關條文另一組高頻數值。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-water-chemical-008","消防搶救上之必要設備中，連結送水管之送水口設置，下列敘述何者正確？",8,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-water-chemical-010","實施泡沫噴頭外觀檢查，應進行之項目內容不包括下列那一項？",10,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-water-chemical-007","依密閉式撒水頭認可基準規定，其中之耐洩漏試驗，係將撒水頭施予多少之靜水壓力，保持 5 分鐘不得有漏水現象？",7,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-water-chemical-011","室內消防栓設備之加壓送水裝置，若採用壓力水箱方式，則其水箱內空氣不得小於水箱容積的幾分之幾？",11,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-water-chemical-006","有關撒水頭位置裝置之規定，下列敘述何者錯誤？",6,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-water-chemical-012","進行乾粉滅火設備性能檢查時，對於滅火藥劑檢查注意事項，溫度及濕度超過多少以上時，應暫停檢查？",12,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-009",113,"高度危險工作場所設置室外消防栓進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-009",112,"室外儲槽儲存閃火點在 70℃以下之第四類公共危險物品之顯著滅火困難場所，應依規定檢討設置下列何種設備？①補助泡沫消防栓 ②泡沫射水槍滅火設備 ③連結送液口 ④冷卻撒水設備 ⑤固定式泡沫滅火設備",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-009",111,"泡沫滅火設備之減水警報裝置進行性能檢查時，當呼水槽水量減少到多少時，應發出警報？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-009",109,"進行低發泡水成膜泡沫放射試驗時，其 25%還原時間應在多久時間以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-009",108,"有一總機室，設置二氧化碳滅火設備，採全區放射方式，其每立方公尺防護區域所需滅火藥劑量為多少公斤？",1785129972359]