[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-water-chemical-008":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-水與化學系統消防安全設備概要-008","fire-110-1-water-chemical-008",110,1,8,"消防搶救上之必要設備中，連結送水管之送水口設置，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"送水口為單口形，接裝口徑 63 毫米陰式快速接頭","距基地地面之高度在 1 公尺以下 0.5 公尺以上","在屋頂上適當位置至少設置一個測試用送水口","送水口在其附近便於檢查確認處，裝設測試用出水口","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 180 條就連結送水管出水口及送水口所定之設置規定，尤其是兩者規定的交叉辨識。\n【正解理由】依《各類場所消防安全設備設置標準》第 180 條第五款，條文明定送水口「為雙口形，接裝口徑六十三毫米陰式快速接頭，距基地地面之高度在一公尺以下零點五公尺以上，且標明連結送水管送水口字樣」；本選項所述高度區間與條文相符，故選 B。\n【逐項排除】\n(A) 敘述錯誤：第 180 條第五款所定送水口為雙口形，非單口形；得用單口形者是同條第二款設於第十層以下樓層之出水口。\n(B) 敘述正確：距基地地面之高度在一公尺以下零點五公尺以上，與第 180 條第五款相符，為正解。\n(C) 敘述錯誤：第 180 條第三款規定「在屋頂上適當位置至少設置一個測試用出水口」，屋頂上設的是出水口而非送水口。\n(D) 敘述錯誤：第 180 條第六款規定送水口在其附近便於檢查確認處，裝設的是逆止閥及止水閥，並非測試用出水口。\n【記憶點】連結送水管送水口記「雙口形、63 毫米陰式快接、高度 0.5～1 公尺」；屋頂上設的是測試用出水口。","第 180 條把連結送水管的「出水口」與「送水口」寫在同一條，本題四個選項正是在兩者之間交叉設陷。出水口部分：設於地下建築物各層或建築物第三層以上各層樓梯間或緊急升降機間等（含該處五公尺以內之處所）消防人員易於施行救火之位置，且各層任一點至出水口之水平距離在五十公尺以下；出水口為雙口形，接裝口徑六十三毫米快速接頭，距樓地板面之高度在零點五公尺以上一點五公尺以下，並設於厚度在一點六毫米以上之鋼板或同等性能以上之不燃材料製箱內，箱面短邊在四十公分以上、長邊在五十公分以上，標明出水口字樣且每字在二十平方公分以上，但設於第十層以下之樓層得用單口形；另在屋頂上適當位置至少設置一個測試用出水口。\n\n送水口部分：設於消防車易於接近且無送水障礙處，其數量在立管數以上；為雙口形，接裝口徑六十三毫米陰式快速接頭，距基地地面之高度在一公尺以下零點五公尺以上，並標明連結送水管送水口字樣；送水口在其附近便於檢查確認處，裝設逆止閥及止水閥。\n\n易混淆概念對照：自動撒水設備的送水口另依第 59 條設置，同為口徑六十三毫米，設於地面層室外臨建築線、消防車容易接近處，高度亦為距基地地面一公尺以下零點五公尺以上，但數量規則是裝置自動撒水設備之樓層樓地板面積在三千平方公尺以下至少設雙口形送水口一個、每超過三千平方公尺增設一個、應設數量超過三個時以三個計，且標明的是自動撒水送水口字樣及送水壓力範圍。屋頂測試用出水口亦非連結送水管專有，室內消防栓設備依第 34 條第二項第四款同樣應在屋頂上適當位置至少設置一個測試用出水口並標明字樣，斜屋頂設置有困難時得免設。\n\n體系定位見第 7 條與第 11 條：第 7 條把消防安全設備分為滅火設備、警報設備、避難逃生設備、消防搶救上之必要設備及其他經中央主管機關認定者五類；第 11 條列出消防搶救上之必要設備種類為連結送水管、消防專用蓄水池、排煙設備、緊急電源插座、無線電通信輔助設備及防災監控系統綜合操作裝置。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-water-chemical-007","依密閉式撒水頭認可基準規定，其中之耐洩漏試驗，係將撒水頭施予多少之靜水壓力，保持 5 分鐘不得有漏水現象？",7,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-water-chemical-009","依據密閉式撒水頭認可基準之規定，進行玻璃球之強度試驗時，標示溫度在多少以上者將採用油浴方式進行測試？",9,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-water-chemical-006","有關撒水頭位置裝置之規定，下列敘述何者錯誤？",6,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-water-chemical-010","實施泡沫噴頭外觀檢查，應進行之項目內容不包括下列那一項？",10,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-water-chemical-005","消防幫浦加壓送水裝置之啟動用水壓開關裝置，下列規定何者正確？",5,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-water-chemical-011","室內消防栓設備之加壓送水裝置，若採用壓力水箱方式，則其水箱內空氣不得小於水箱容積的幾分之幾？",11,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-008",113,"有關幫浦之形狀、構造部分，依據消防幫浦認可基準規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-008",112,"某引擎試驗室設置有泡沫滅火設備，採高發泡放出口局部放射方式，依規定高發泡放出口之泡沫水溶液放射量，防護面積每 1 平方公尺應在每分鐘 X 公升以上。又防護面積係指防護對象外周線以高出防護對象物高度 Y 倍數值（該數值小於 1 公尺時，以 1 公尺計）所包圍之面積。其中 X+Y=？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-008",111,"固定式泡沫滅火設備（低發泡）進行綜合檢查作業時，發泡倍率應在幾倍以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-008",109,"預動式自動撒水設備竣工測試進行放水試驗時，開放末端查驗閥後，應在多久時間內正常放水？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-008",108,"移動式泡沫滅火設備之加壓送水裝置使用消防幫浦時，若同一樓層設 3 個泡沫消防栓箱時，其出水量應在每分鐘多少公升以上？",1785129972346]